6EP3334-8SB00-0AY0

Data sheet
6EP3334-8SB00-0AY0
SITOP PSU8200 24 V/10 A STABILIZED POWER SUPPLY INPUT:
120/230 V AC OUTPUT: 24 V/10 A DC
Technical specifications
Product
SITOP PSU8200
Power supply, type
24 V/10 A
Input
Input
1-phase AC
Supply voltage 1 with AC Rated value
120 V
Supply voltage 2 with AC Rated value
230 V
● Note
Automatic range selection
Input voltage 1 with AC
85 ... 132 V
Input voltage 2 with AC
170 ... 264 V
Wide-range input
No
Mains buffering at Iout rated, min.
35 ms; at Vin = 120/230 V
Rated line frequency
50 ... 60 Hz
Rated line range
47 ... 63 Hz
Input current at rated input voltage 120 V Rated
value
4 A
Input current at rated input voltage 230 V Rated
value
1.9 A
Switch-on current limiting (+25 °C), max.
10 A
I²t, max.
0.3 A²·s
Built-in incoming fuse
T 6.3 A (not accessible)
6EP3334-8SB00-0AY0
Page 1/4
26.04.2015
Changes preserved
© Copyright Siemens AG
Protection in the mains power input (IEC 898)
Recommended miniature circuit breaker at 1-phase operation:
from 6 A (10 A) characteristic C (B); required at 2-phase
operation: circuit breaker 2-pole connected or circuit breaker
3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at
230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL
489) at 400/500 V
Output
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
Total tolerance, static ±
3 %
Static mains compensation, approx.
0.1 %
Static load balancing, approx.
0.3 %
Residual ripple peak-peak, max.
50 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
200 mV
Adjustment range
24 ... 28.8 V
Product function Output voltage adjustable
Yes
Output voltage setting
via potentiometer; max. 240 W
Status display
Green LED for 24 V OK
Signaling
Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
On/off behavior
Overshoot of Vout approx. 3 %
Startup delay, max.
1 s
Voltage rise, typ.
70 ms
Rated current value Iout rated
10 A
Current range
0 ... 10 A
● Note
+60 ... +70 °C: Derating 2%/K; as of Ua>24 V: 4% [Ia]/V [Ua]; at
Ue<100 V/<200 V: 80% Ia rated
Active power supplied typical
240 W
Constant overload current on short-circuiting during
the start-up typical
12 A
Short-term overload current at short-circuit during
operation typical
30 A
Duration of overloading capability for excess current
at short-circuit during operation
25 ms
Parallel switching for enhanced performance
Yes; switchable characteristic
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx.
94 %
Power loss at Vout rated, Iout rated, approx.
18 W
Active power loss during no-load operation maximum
1.5 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %),
max.
6EP3334-8SB00-0AY0
Page 2/4
0.1 %
26.04.2015
Changes preserved
© Copyright Siemens AG
Dynamic load smoothing (Iout: 50/100/50 %), Uout ±
typ.
4 %
Load step setting time 50 to 100%, typ.
0.25 ms
Load step setting time 100 to 50%, typ.
0.5 ms
Dynamic load smoothing (Iout: 10/90/10 %), Uout ±
typ.
4 %
Load step setting time 10 to 90%, typ.
0.25 ms
Load step setting time 90 to 10%, typ.
0.5 ms
Setting time maximum
1 ms
Protection and monitoring
Output overvoltage protection
< 33 V
Current limitation, typ.
12 A
Property of the output Short-circuit proof
Yes
Short-circuit protection
Alternatively, constant current characteristic approx. 12 A or
latching shutdown
Enduring short circuit current RMS value typical
12 A
Overcurrent overload capability in normal operation
overload capability 150 % Iout rated up to 5 s/min
Overload/short-circuit indicator
LED yellow for "overload", LED red for "latching shutdown"
Safety
Primary/secondary isolation
Yes
Galvanic isolation
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN
50178
Protection class
Class I
Leakage current maximum
3.5 mA
Leakage current typical
1 mA
CE mark
Yes
UL/CSA approval
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
Explosion protection
ATEX (EX) II 3G Ex nA nC IIC T3 Gc; cCSAus (CSA C22.2 No.
213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T3
Certificate of suitability IECEx
Yes
Certificate of suitability NEC Class 2
No
FM approval
-
CB approval
Yes
Marine approval
GL, ABS
Degree of protection (EN 60529)
IP20
EMC
Emitted interference
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
Noise immunity
EN 61000-6-2
Operating data
Ambient temperature during operation
6EP3334-8SB00-0AY0
Page 3/4
-25 ... +70 °C
26.04.2015
Changes preserved
© Copyright Siemens AG
● Note
with natural convection
Ambient temperature during transport
-40 ... +85 °C
Ambient temperature during storage
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, no condensation
Mechanics
Connection technology
screw-type terminals
Connections Supply input
L, N, PE: 1 screw terminal each for 0.2 ... 2.5 mm² singlecore/finely stranded
Connections Output
+, -: 2 screw terminals each for 0.2 ... 2.5 mm²
Connections Auxiliary
13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm²;
15, 16 (Remote): 1 screw terminal each for 0.14 ... 1.5 mm²
Product function removable terminal at input
No
Product function removable terminal at output
No
Width of the enclosure
55 mm
Height of the enclosure
125 mm
Depth of the enclosure
125 mm
Weight, approx.
1 kg
Product property of the enclosure housing for side-
Yes
by-side mounting
Installation
Snaps onto DIN rail EN 60715 35x7.5/15
Electrical accessories
Buffer module
Other information
Specifications at rated input voltage and ambient temperature +25
°C (unless otherwise specified)
6EP3334-8SB00-0AY0
Page 4/4
26.04.2015
Changes preserved
© Copyright Siemens AG