SITRANS P410 Catalog Specifications Sheet

© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 - Technical description
■ Overview
■ Application
SITRANS P410 pressure transmitters can be used in industrial
areas with extreme chemical and mechanical loads. Electromagnetic compatibility in the range 10 kHz to 1 GHz makes the
P410 suitable for locations with high electromagnetic emissions.
Pressure transmitters with type of protection "Flameproof enclosure" may be installed in hazardous areas (zone 1) or in zone 0.
The pressure transmitters are provided with an EC type examination certificate and comply with the corresponding harmonized European standards (ATEX).
Pressure transmitters with the type of protection "Intrinsic safety"
for use in zone 0 may be operated with power supply units of category "ia" and "ib".
The transmitters can be equipped with various designs of remote seals for special applications such as the measurement of
highly viscous substances.
SITRANS P410 pressure transmitters are digital pressure transmitters with a high level of operating convenience. Technically,
they are based on the SITRANS P DS III but offer an increased
measuring accuracy of 0.04%. This means the SITRANS P 410
is perfectly suited for measuring tasks with increased accuracy
requirements. The parameterization is performed using input
buttons or via HART or via PROFIBUS PA or FOUNDATION Fieldbus interface.
The comprehensive functionality makes for precise adjustment
of the pressure transmitter to the requirements of the plant. Operation is very simple, despite the variety of setting options.
Pressure transmitters with type of protection "Intrinsic safety" and
"Explosion-proof" may be installed in hazardous areas (zone 1)
or in zone 0. The transmitters are provided with an EC type examination certificate and comply with the respective harmonized
European standards (ATEX).
The transmitters can be equipped with various designs of remote seals for special applications such as the measurement of
highly viscous substances.
SITRANS P410 pressure transmitters are available in various versions for measuring:
• Gauge pressure
• Differential pressure
• Volume flow
• Mass flow
■ Benefits
•
•
•
•
•
•
•
•
•
•
High quality and service life
For aggressive and non-aggressive gases, vapors and liquids
Extensive diagnostics and simulation functions
Minimal conformity error
Good long-term stability
Wetted parts made of high-grade materials (e.g., stainless
steel, Hastelloy)
Infinitely adjustable spans from 0.01 bar to 160 bar (0.15 psi
to 2321 psi) for P410 with HART interface
Nominal measuring ranges from 1 bar to 160 bar (14.5 psi to
2321 psi) for P410 with PROFIBUS PA and FOUNDATION
Fieldbus interface
High measuring accuracy
Parameterization over input buttons and HART, PROFIBUS PA
or FOUNDATION Fieldbus interface.
1/198
Siemens FI 01 · 2016
The pressure transmitter can be operated locally over 3 input
buttons or programmed externally over HART or over PROFIBUS
PA or FOUNDATION Fieldbus interface.
Pressure transmitter for gauge pressure
Measured variable: Gauge pressure of aggressive and non-aggressive gases, vapors and liquids.
Span (infinitely adjustable)
for P410 with HART: 0.01 bar to 160 bar (0.15 psi to 2321 psi)
Nominal measuring range
for P410 with PROFIBUS PA and FOUNDATION Fieldbus:
1 bar to 160 bar (14.5 psi to 2321 psi)
Pressure transmitters for differential pressure and flow
Measured variables:
• Differential pressure
• Small positive or negative pressure
• Flow q ~ p (together with a primary differential pressure device (see Chapter "Flow Meters"))
Span (infinitely adjustable)
for P410 with HART: 1 mbar ... 30 bar (0.0145 ... 435 psi)
Nominal measuring range
for P410 with PROFIBUS PA and FOUNDATION Fieldbus:
20 mbar ... 30 bar (0.29 ... 435 psi)
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 - Technical description
■ Design
1
2
8
1
2
3
4
5
6
7
8
Plastic cover as access to
the input keys
Screw cover with
viewing pane
Digital display
Locking screw
7
Process connection
Screw cover with
viewing pane
6
Rating plate
Inlet with cable gland
3
4
5
Front view
The transmitter consists of various components depending on
the order. The possible versions are listed in the ordering information. The components described below are the same for all
transmitters.
The rating plate (7, Figure "Front view") with the Article No. is located
on the side of the housing. The specified number together with the
ordering information provide details on the optional design details
and on the possible measuring range (physical properties of built-in
sensor element).
The approval label is located on the opposite side.
The housing is made of die-cast aluminium or stainless steel precision casting. A round cover (6) is screwed on at the front and
rear of the housing. The front cover can be fitted with a viewing
pane so that the measured values can be read directly on the
display. The inlet (8) for the electrical connection is located either
on the left or right side. The unused opening on the opposite side
is sealed by a blanking plug. The protective earth connection is
located on the rear of the housing.
The electrical connections for the power supply and screen are
accessible by unscrewing the rear cover. The bottom part of the
housing contains the measuring cell with process connection
(5). The measuring cell is prevented from rotating by a locking
screw (4). As the result of this modular design, the measuring
cell and the electronics can be replaced separately from each
other. The set parameter data are retained.
At the top of the housing is a plastic cover (1), which hides the
input keys.
Example for an attached measuring point label
Y01 or Y02
= max. 27 char.
Y15 = max. 16 char.
Y99 = max. 10 char.
Y16 = max. 27 char.
.... to .... mbar
Measuring point number (TAG No.)
1234
Measuring point text
Siemens FI 01 · 2016
1/199
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 - Technical description
■ Function
Operation of electronics with HART communication
Operation of electronics with PROFIBUS PA communication
9
8
9
8
0.0.0.0.0
00
M
0.0.0.0.0
00
M
10
4
5
2
3
4
IA, UH
μC
5
μC
7
PA
interface
7
HART interface
EEPROM
EEPROM
Electronics
Electronics
6
Sensor
1
Sensor
pe Measuring cell
1
2
3
4
5
6
Measuring cell sensor
Instrument amplifier
Analog-to-digital converter
Microcontroller
Digital-to-analog converter
One non-volatile memory each in the measuring cell and
electronics
7 HART interface
8 Three input keys (local operation)
9 Digital display
10 Diode circuit and connection for external ammeter
IA Output current
UH Power supply
Pe Input variable
Function diagram of electronics
The bridge output voltage created by the sensor (1, Figure
"Function diagram of the electronics") is amplified by the measuring amplifier (2) and digitized in the analog-to-digital converter (3). The digital information is evaluated in a microcontroller, its linearity and temperature response corrected, and
converted in a digital-to-analog converter (5) into an output current of 4 to 20 mA.
The diode circuit (10) protects against incorrect polarity.
The data specific to the measuring cell, the electronics data, and
the parameter data are stored in the two non-volatile memories
(6). The one memory is coupled to the measuring cell, the other
to the electronics. As the result of this modular design, the electronics and the measuring cell can be replaced separately from
each other.
Using the 3 input keys (8) you can parameterize the pressure
transmitter directly at the measuring point. The input buttons can
also be used to control the view of the results, the error messages and the operating modes on the display (9).
The HART modem (7) permits parameterization using a protocol
according to the HART specification.
The pressure transmitters with spans  63 bar measure the input
pressure compared to atmosphere, transmitters with spans
 160 bar compared to vacuum.
1/200
Siemens FI 01 · 2016
6
pe
1
2
3
4
5
6
7
Power
supply
unit
Coupler
11
12
EEPROM
1
6
6
Power supply
10
PROFIBUS DP
3
PROFIBUS-PA
2
EEPROM
1
BusMaster
Measuring cell
Measuring cell sensor
Instrument amplifier
Analog-to-digital converter
Microcontroller
Electrical isolation
One non-volatile memory
each in the measuring cell
and electronics
PROFIBUS-PA interface
8
9
10
11
12
Three input keys
(local operation)
Digital display
Power supply
DP/PA coupler or link
Bus master
pe
Input variable
Function diagram of electronics
The bridge output voltage created by the sensor (1, Figure
"Function diagram of the electronics") is amplified by the measuring amplifier (2) and digitized in the analog-to-digital converter (3). The digital information is evaluated in the microcontroller, its linearity and temperature response corrected, and
provided on the PROFIBUS PA through an electrically isolated
PA interface (7).
The data specific to the measuring cell, the electronics data, and
the parameter data are stored in the two non-volatile memories
(6). The one memory is coupled to the measuring cell, the other
to the electronics. As the result of this modular design, the electronics and the measuring cell can be replaced separately from
each other.
Using the three input buttons (8) you can parameterize the pressure transmitter directly at the measuring point. The input buttons can also be used to control the view of the results, the error
messages and the operating modes on the display (9).
The results with status values and diagnostic values are transferred by cyclic data transmission on the PROFIBUS PA. Parameterization data and error messages are transferred by acyclic
data transmission. Special software such as SIMATIC PDM is required for this.
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 - Technical description
Operation of electronics with FOUNDATION Fieldbus
communication
Mode of operation of the measuring cells
Measuring cell for gauge pressure
9
8
0.0.0.0.0
00
2
3
4
5
5
4
7
FF
interface
μC
EEPROM
6
Foundation Fieldbus
M
3
Power
supply
unit
Coupler
pe
EEPROM
6
Sensor
Measuring cell for gauge pressure, function diagram
pe
Measuring cell
1
2
3
4
5
6
7
Measuring cell sensor
Instrument amplifier
Analog-to-digital converter
Microcontroller
Electrical isolation
One non-volatile memory
each in the measuring cell
and electronics
FF interface
Measuring cell
Process connection
Seal diaphragm
Filling liquid
Silicon pressure sensor
Pressure as input variable
2
Electronics
1
1
2
3
4
5
pe
1
Power supply
10
8
9
10
Three input keys
(local operation)
Digital display
Power supply
pe
Input variable
The pressure pe is applied through the process connection (2,
Figure "Measuring cell for gauge pressure, function diagram) to
the measuring cell (1). This pressure is subsequently transmitted
further through the seal diaphragm (3) and the filling liquid (4) to
the silicon pressure sensor (5) whose measuring diaphragm is
then flexed. This changes the resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit. This change in resistance results in a bridge output voltage proportional to the
differential pressure.
Measuring cell for differential pressure and flow
2
3
4
Function diagram of electronics
The bridge output voltage created by the sensor (1, Figure
"Function diagram of electronics") is amplified by the measuring
amplifier (2) and digitized in the analog-to-digital converter (3).
The digital information is evaluated in the microcontroller, its linearity and temperature response corrected, and provided on the
FOUNDATION Fieldbus through an electrically isolated
FOUNDATION Fieldbus interface (7).
The data specific to the measuring cell, the electronics data, and
the parameter data are stored in the two non-volatile memories
(6). The one memory is coupled to the measuring cell, the other
to the electronics. As the result of this modular design, the electronics and the measuring cell can be replaced separately from
each other.
Using the three input buttons (8) you can parameterize the pressure transmitter directly at the measuring point. The input buttons can also be used to control the view of the results, the error
messages and the operating modes on the display (9).
The results with status values and diagnostic values are transferred by cyclic data transmission on the FOUNDATION
Fieldbus. Parameterization data and error messages are transferred by acyclic data transmission. Special software such as
National Instruments Configurator is required for this.
1
+
-
1
5
7
1
2
3
4
5
6
7
Seal diaphragm
O-ring
Overload diaphragm
Silicon pressure sensor
Process flange
Body of measuring cell
Filling liquid
6
Measuring cell for differential pressure and flow, function diagram
The differential pressure is transmitted through the seal diaphragms (1, Figure "Measuring cell for differential pressure and
flow, function diagram") and the filling liquid (7) to the silicon
pressure sensor (4).
The measuring diaphragm is flexed by the applied differential
pressure. This changes the resistance of the four piezo-resistors
fitted in the diaphragm in a bridge circuit. This change in resistance results in a bridge output voltage proportional to the
differential pressure.
An overload diaphragm is installed to provide protection from
overloads. If the measuring limits are exceeded, the overload diaphragm (3) is flexed until the seal diaphragm rests on the body
of the measuring cell (6), thus protecting the silicon pressure
sensor from overloads.
Siemens FI 01 · 2016
1/201
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 - Technical description
Parameterization SITRANS P410
Depending on the version, there are a range of options for parameterizing the pressure transmitter and for setting or scanning
the parameters.
Parameterization using the input buttons (local operation)
With the input buttons you can easily set the most important parameters without any additional equipment.
Parameterization using HART
Parameterization using HART is performed with a HART Communicator or a PC.
+
230 ... 1100 Ω
SITRANS P
transmitter
Power supply
HART
communicator
Communication between a HART Communicator and a pressure transmitter
When parameterizing with the HART Communicator, the connection is made directly to the 2-wire cable.
+
230 ... 500 Ω
SITRANS P
transmitter
HART
modem
Power supply
PC or
laptop
Diagnostic functions for SITRANS P410 with HART
• Zero correction display
• Event counter
• Limit transmitter
• Saturation alarm
• Slave pointer
• Simulation functions
• Maintenance timer
Available physical units of display for SITRANS P410 with HART
Physical variable
Physical dimensions
Pressure (setting can also be Pa, MPa, kPa, bar, mbar, torr, atm, psi,
g/cm2, kg/cm2, inH2O, inH2O (4 °C),
made in the factory)
mmH2O, ftH2O (20 °C), inHg, mmHg
Level (height data)
m, cm, mm, ft, in
Volume
m3, dm3, hl, yd3, ft3, in3, US gallon, lmp.
gallon, bushel, barrel, barrel liquid
Mass
g, kg, t, lb, Ston, Lton, oz
volume flow
m3/d, m3/h, m3/s, l/min, l/s, ft3/d, ft3/min,
ft3/s, US gallon/min, US gallon/s
Mass flow
t/d, t/h, t/min, kg/d, kg/h, kg/min, kg/s,
g/d, g/h, g/min, g/s, lb/d, lb/h, lb/min, lb/s,
LTon/d, LTon/h, STon/d, STon/h, STon/min
Temperature
K, °C, °F, °R
Miscellaneous
%, mA
Parameterization through PROFIBUS PA interface
Fully digital communication through PROFIBUS PA, profile 3.0, is
particularly user-friendly. Through the PROFIBUS the DS III with
PROFIBUS PA is connected to a process control system, e. g.
SIMATIC PSC 7. Communication is possible even in a potentially
explosive environment.
For parameterization through PROFIBUS you need suitable software, e.g. SIMATIC PDM (Process Device Manager).
USB/RS 232
Parameterization through FOUNDATION Fieldbus interface
HART communication between a PC communicator and a pressure
transmitter
When parameterizing with a PC, the connection is made through
a HART modem.
The signals needed for communication in conformity with the
HART 5.x or 6.x protocols are superimposed on the output current using the Frequency Shift Keying (FSK) method.
Adjustable parameters, SITRANS P410 with HART
Fully digital communication through FOUNDATION Fieldbus is
particularly user-friendly. Through the FOUNDATION Fieldbus
the DS III with FOUNDATION Fieldbus is connected to a process
control system. Communication is possible even in a potentially
explosive environment.
For parameterization through the FOUNDATION Fieldbus you
need suitable software, e.g. National Instruments Configurator.
Adjustable parameters for SITRANS P410 with PROFIBUS PA
and FOUNDATION Fieldbus
Parameters
Input keys
(DS III HART)
HART
communication
Start of scale
Full-scale value
Electrical damping
Start-of-scale value without application of a pressure ("Blind setting")
Full-scale value without application
of a pressure ("Blind setting")
Zero adjustment
current transmitter
Fault current
Disabling of buttons, write protection
Type of dimension and actual
dimension
Characteristic (linear / squarerooted)
Input of characteristic
Freely-programmable LCD
Diagnostic functions
x
x
x
x
x
x
x
x
Parameters
Input
keys
PROFIBUS PA and
FOUNDATION Fieldbus interface
Electrical damping
x
x
x
x
Zero adjustment (correction of position)
x
x
x
x
x
x
x
x
x
x1)
Buttons and/or function disabling
x
x
Source of measured-value display
x
x
Physical dimension of display
x
x
Position of decimal point
x
x
1)
2)
Cancel apart from write protection
Only differential pressure
1/202
Siemens FI 01 · 2016
x
x
Bus address
x
x
x2)
x2)
Adjustment of characteristic
x
x
x
x
x
Input of characteristic
x
Freely-programmable LCD
x
Diagnostics functions
x
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 - Technical description
Diagnostic functions for SITRANS P410 with PROFIBUS PA and
FOUNDATION Fieldbus
• Event counter
• Slave pointer
• Maintenance timer
• Simulation functions
• Display of zero correction
• Limit transmitter
• Saturation alarm
Physical dimensions available for the display
Physical variable
Physical dimensions
Pressure (setting can also be MPa, kPa, Pa, bar, mbar, torr, atm, psi,
g/cm2, kg/cm2, mmH2O, mmH2O (4 °C),
made in the factory)
inH2O, inH20 (4 °C), ftH2O (20 °C),
mmHg, inHg
Level (height data)
m, cm, mm, ft, in, yd
Volume
m3, dm3, hl, yd3, ft3, in3, US gallon, lmp.
gallon, bushel, barrel, barrel liquid
volume flow
m3/s, m3/min, m3/h, m3/d, l/s, l/min, l/h, l/
d, Ml/d, ft3/s, ft3/min, ft3/h, ft3/d, US gallon/s, US gallon/min, US gallon/h, US gallon/d, bbl/s, bbl/min, bbl/h, bbl/d
Mass flow
g/s, g/min, g/h, g/d, kg/s, kg/min, kg/h,
kg/d, t/s, t/min, t/h, /t/d, lb/s, lb/min, lb/h,
lb/d, STon/s, STon/min, STon/h, STon/d,
LTon/s, LTon/min, LTon/h, LTon/d
Total mass flow
t, kg, g, lb, oz, LTon, STon
Temperature
K, °C, °F, °R
Miscellaneous
%
Siemens FI 01 · 2016
1/203
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for gauge pressure
■ Technical specifications
SITRANS P410 for gauge pressure
Input
Measured variable
Gauge pressure
Span (fully adjustable) or measuring range, max. operating
HART
pressure (in accordance with 2014/68/EU Pressure Equipment
Directive) and max. test pressure (pursuant to DIN 16086)
PROFIBUS PA/
FOUNDATION
Fieldbus
Span
Nominal measuring Max. operating pres- Max. perm.
range
sure MAWP (PS)
test pressure
0.01 ... 1 bar
1 ... 100 kPa
0.15 ... 14.5 psi
1 bar
100 kPa
14.5 psi
4 bar
400 kPa
58 psi
6 bar
600 kPa
87 psi
0.04 ... 4 bar
4 ... 400 kPa
0.58 ... 58 psi
4 bar
400 kPa
58 psi
7 bar
0.7 MPa
102 psi
10 bar
1 MPa
145 psi
0.16 ... 16 bar
16 ... 1600 kPa
2.3 ... 232 psi
16 bar
1600 kPa
232 psi
21 bar
2.1 MPa
305 psi
32 bar
3.2 MPa
464 psi
0.63 ... 63 bar
63 ... 6300 kPa
9.1 ... 914 psi
63 bar
6300 kPa
914 psi
67 bar
6.7MPa
972 psi
100 bar
10 MPa
1450 psi
1.6 ... 160 bar
0.16 ... 16 MPa
23 ... 2321 psi
160 bar
16 MPa
2321 psi
167 bar
16.7 MPa
2422 psi
250 bar
2.5 MPa
3626 psi
Lower measuring limit
• Measuring cell with silicone oil filling
30 mbar a/3 kPa a/0.44 psia
Upper measuring limit
100 % of max. span
Output
HART
PROFIBUS PA/FOUNDATION Fieldbus
Output signal
4 ... 20 mA
Digital PROFIBUS PA and FOUNDATION
Fieldbus signal
• Lower limit (infinitely adjustable)
3.55 mA, factory preset to 3.84 mA
-
• Upper limit (infinitely adjustable)
23 mA, factory preset to 20.5 mA or
optionally set to 22.0 mA
-
• Without HART
RB  (UH - 10.5 V)/0.023 A in ,
UH: Power supply in V
-
• With HART
RB = 230 ... 500  (SIMATIC PDM) or
RB = 230 ... 1100  (HART Communicator)
Physical bus
-
Protection against polarity reversal
Protected against short-circuit and polarity reversal. Each connection against the
other with max. supply voltage.
Electrical damping (step width 0.1 s)
Set to 2 s (0 ... 100 s)
Load
1/204
Siemens FI 01 · 2016
IEC 61158-2
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for gauge pressure
SITRANS P410 for gauge pressure
Measuring accuracy
Acc. to IEC 60770-1
Reference conditions
• Increasing characteristic
• Start-of-scale value 0 bar/kPa/psi
• Stainless steel seal diaphragm
• Silicone oil filling
• Room temperature 25 °C (77 °F)
Measuring span ratio r (spread, Turn-Down)
r = max. measuring span/set measuring span or nom. pressure range
Error in measurement at limit setting incl. hysteresis and
reproducibility
• Linear characteristic
- 1 bar/100 kPa/14.5 psi
4 bar/400 kPa/58 psi
16 bar/1.6 MPa/232 psi
63 bar/6.3 MPa/914 psi
160 bar/16 MPa/2321 psi
r5:
5 < r  100 :
 0.04 %
 (0.004  r + 0.045) %
Influence of ambient temperature
(in percent per 28 °C (50 °F))
• 1 bar/100 kPa/14.5 psi
 (0.05  r + 0.1) %
• 4 bar/400 kPa/58 psi
16 bar/1.6 MPa/232 psi
63 bar/6.3 MPa/914 psi
160 bar/16 MPa/2321 psi
 (0.025  r + 0.125) %
Long-term stability (temperature change  30 °C ( 54 °F))
• 1 bar/100 kPa/14.5 psi
4 bar/400 kPa/58 psi
 (0.25  r) % in 5 years
• 16 bar/1.6 MPa/232 psi
63 bar/6.3 MPa/914 psi
160 bar/16 MPa/2321 psi
 (0.125  r) % in 5 years
Effect of mounting position
 0.05 mbar/0.005 kPa/0.000725 psi per 10° inclination
(zero point correction is possible with position error compensation)
Effect of auxiliary power supply
(in percent per change in voltage)
0.005 % per 1 V
Measuring value resolution for PROFIBUS PA and
FOUNDATION Fieldbus
3  10-5 of nominal measuring range
Siemens FI 01 · 2016
1/205
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for gauge pressure
SITRANS P410 for gauge pressure
Rated conditions
Degree of protection (to EN 60529)
IP66 (optional IP66/IP68), NEMA 4X
Temperature of medium
• Measuring cell with silicone oil filling
-40 ... +100 °C (-40 ... +212 °F)
• Measuring cell with inert filling liquid
-20 ... +100 °C (-4 ... +212 °F)
• In conjunction with dust explosion protection
-20 ... +60 °C (-4 ... +140 °F)
Ambient conditions
• Ambient temperature
- Transmitter
-40 ... +85 °C (-40 ... +185 °F)
- Display readable
-30 ... +85 °C (-22 ... +185 °F)
• Storage temperature
-50 ... +85 °C (-58 ... +185 °F)
• Climatic class
- Condensation
Relative humidity 0 ... 100 %
Condensation permissible, suitable for use in the tropics
• Electromagnetic Compatibility
- Emitted interference and interference
immunity
Acc. to IEC 61326 and NAMUR NE 21
Design
Weight (without options)
Die-cast aluminum:  2.0 kg ( 4.4 lb)
Stainless steel precision casting:  4.6 kg ( 10.1 lb)
Enclosure material
Low-copper die-cast aluminum, GD-AlSi 12 or stainless steel precision casting, mat.
no. 1.4408
Wetted parts materials
• Connection shank
Stainless steel, mat. no. 1.4404/316L or Hastelloy C4, mat. no. 2.4602
• Oval flange
Stainless steel, mat. no. 1.4404/316L
• Seal diaphragm
Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819
Measuring cell filling
Silicone oil or inert filling liquid
(maximum value with oxygen measurement pressure 100 bar (1450 psi) at 60 °C
(140 °F))
Process connection
Connection shank G½B to DIN EN 837-1, female thread ½ -14 NPT or oval flange
(PN 160 (MAWP 2320 psi)) to DIN 19213 with mounting thread M10 or 7/16-20 UNF
to EN 61518
Material of mounting bracket
Steel
Sheet-steel, Mat. No. 1.0330, chrome-plated
Stainless steel
Sheet stainless steel, mat. no. 1.4301 (SS 304)
Power supply UH
HART
Terminal voltage on transmitter
10.5 ... 45 V DC
10.5 ... 30 V DC in intrinsically-safe mode
Power supply
Separate 24 V power supply necessary
PROFIBUS PA/ FOUNDATION Fieldbus
Supplied through bus
-
No
• Not Ex
-
9 ... 32 V
• With intrinsically-safe operation
-
9 ... 24 V
• Basic current (max.)
-
12.5 mA
• Start-up current  basic current
-
Yes
• Max. current in event of fault
-
15.5 mA
Fault disconnection electronics (FDE) available
-
Yes
Bus voltage
Current consumption
1/206
Siemens FI 01 · 2016
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for gauge pressure
SITRANS P410 for gauge pressure
Certificates and approvals
Classification according to PED 2014/68/EU
For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of
article 4, paragraph 3 (sound engineering practice)
Explosion protection
• Intrinsic safety "i"
PTB 13 ATEX 2007 X
- Marking
Ex II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +70 °C (-40 ... +158 °F) temperature class T5;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6
- Connection
To certified intrinsically-safe circuits with
peak values:
Ui = 30 V, Ii = 100 mA,
Pi = 750 mW; Ri = 300 
FISCO supply unit:
Uo = 17.5 V, Io = 380 mA, Po = 5.32 W
Linear barrier:
Uo = 24 V, Io = 174 mA, Po = 1 W
- Effective internal inductance/capacitance
L i = 0.4 mH, Ci = 6 nF
L i = 7 H, Ci = 1.1 nF
• Explosion-proof "d"
PTB 99 ATEX 1160
- Marking
Ex II 1/2 G Ex d IIC T4/T6 Gb
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6
- Connection
To circuits with values: UH = 10.5 ... 45 V To circuits with values: UH = 9 ... 32 V DC
DC
• Dust explosion protection for zone 20 (pending)
PTB 01 ATEX 2055
- Marking
Ex II 1 D Ex ta IIIC T120°C Da
Ex II 1/2 D Ex ta/tb IIIC T120°C Da/Db
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F)
- Max. surface temperature
120 °C (248 °F)
- Connection
To certified intrinsically-safe circuits with
peak values:
Ui = 30 V, Ii = 100 mA,
Pi = 750 mW, Ri = 300 
FISCO supply unit:
Uo = 17.5 V, Io = 380 mA, Po = 5.32 W
Linear barrier:
Uo = 24 V, Io = 250 mA, Po = 1 W
- Effective internal inductance/capacitance
L i = 0.4 mH, Ci = 6 nF
L i = 7 H, Ci = 1.1 nF
• Dust explosion protection for zone 21/22 (pending)
PTB 01 ATEX 2055
- Marking
Ex II 2 D Ex tb IIIC T120°C Db
- Connection
To circuits with values:
UH = 10.5 ... 45 V DC; Pmax = 1.2 W
• Type of protection "n" (zone 2)
To circuits with values:
UH = 9 ... 32 V DC; Pmax = 1 W
PTB 13 ATEX 2007 X
- Marking
Ex II 2/3 G Ex nA II T4/T5/T6 Gc
Ex II 2/3 G Ex ic IIC T4/T5/T6 Gc
- Connection (Ex nA)
Um = 45 V
Um = 32 V
- Connections (Ex ic)
To circuits with values:
Ui = 45 V
FISCO supply unit ic:
Uo = 17.5 V, Io = 570 mA
Linear barrier:
Uo = 32 V, Io = 132 mA, Po = 1 W
- Effective internal inductance/capacitance
L i = 0.4 mH, Ci = 6 nF
L i = 7 H, Ci = 1.1 nF
• Explosion protection acc. to FM (pending)
- Identification (XP/DIP) or (IS); (NI)
• Explosion protection to CSA (pending)
- Identification (XP/DIP) or (IS)
Certificate of Compliance 3008490
CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC
T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III
Certificate of Compliance 1153651
CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I,
DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III
Siemens FI 01 · 2016
1/207
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for gauge pressure
HART communication
HART
230 ... 1100 
Protocol
HART Version 5.x
Software for computer
SIMATIC PDM
PROFIBUS PA communication
Simultaneous communication with
master class 2 (max.)
4
The address can be set using
Configuration tool or local operation (standard setting address
126)
Cyclic data usage
• Output byte
5 (one measured value) or
10 (two measured values)
• Input byte
0, 1, or 2 (register operating
mode and reset function for
metering)
Internal preprocessing
FOUNDATION Fieldbus
communication
Function blocks
3 function blocks analog input,
1 function block PID
• Analog input
- Adaptation to customer-specific process variables
Yes, linearly rising or falling
characteristic
- Electrical damping, adjustable
0 ... 100 s
- Simulation function
Output/input (can be locked
within the device with a bridge)
- Failure mode
parameterizable (last good
value, substitute value, incorrect
value)
- Limit monitoring
Yes, one upper and lower warning limit and one alarm limit
respectively
- Square-rooted characteristic
for flow measurement
Yes
Device profile
PROFIBUS PA Profile for Process Control Devices Version
3.0, class B
• PID
Standard FOUNDATION
Fieldbus function block
• Physical block
1 resource block
Function blocks
2
Transducer blocks
- Adaptation to customer-specific process variables
Yes, linearly rising or falling
characteristic
1 transducer block Pressure with
calibration, 1 transducer block
LCD
• Pressure transducer block
- Electrical damping, adjustable
0 ... 100 s
- Simulation function
Input /Output
- Failure mode
parameterizable (last good
value, substitute value, incorrect
value)
- Limit monitoring
Yes, one upper and lower warning limit and one alarm limit
respectively
• Register (totalizer)
Can be reset, preset, optional
direction of counting, simulation
function of register output
• Analog input
- Failure mode
parameterizable (summation
with last good value, continuous
summation, summation with
incorrect value)
- Limit monitoring
One upper and lower warning
limit and one alarm limit respectively
• Physical block
1
Transducer blocks
2
• Pressure transducer block
- Can be calibrated by applying
two pressures
Yes
- Monitoring of sensor limits
Yes
- Specification of a container
characteristic with
Max. 30 nodes
- Square-rooted characteristic
for flow measurement
Yes
- Gradual volume suppression
and implementation point of
square-root extraction
Parameterizable
- Simulation function for measured pressure value and sensor temperature
Constant value or over parameterizable ramp function
1/208
Siemens FI 01 · 2016
- Can be calibrated by applying
two pressures
Yes
- Monitoring of sensor limits
Yes
- Simulation function: Measured
pressure value, sensor temperature and electronics temperature
Constant value or over parameterizable ramp function
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for gauge pressure
Selection and Ordering data
Article No.
Order code
Pressure transmitter for gauge pressure, SITRANS P410 with HART
7MF4033- 7 7 7 7 7 - 7 7 7 7 -Z C41
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
Silicone oil
Measuring cell cleaning
normal
Measuring span (min. ... max.)
0.01 ... 1 bar
(0.15 ... 14.5 psi)
0.04 ... 4 bar
(0.58 ... 58 psi)
0.16 ... 16 bar (2.32 ... 232 psi)
0.63 ... 63 bar (9.14 ... 914 psi)
1.6 ... 160 bar (23.2 ... 2320 psi)
Wetted parts materials
Seal diaphragm
}
}
}
}
}
}
1
B
C
D
E
F
Process connection
Stainless steel
Stainless steel
Hastelloy
Stainless steel
Hastelloy
Hastelloy
Version as diaphragm seal 1) 2) 3) 4)
Process connection
• Connection shank G½B to EN 837-1
• Female thread ½-14 NPT
• Stainless steel oval flange with process connection (Oval flange has no female thread)
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M10 to DIN 19213
- Mounting thread M12 to DIN 19213
• Male thread M20 x 1.5
• Male thread ½ -14 NPT
Non-wetted parts materials
• Housing made of die-cast aluminium
• Housing stainless steel precision casting5)
}
}
Electrical connection / cable entry
• Screwed gland M20 x1 .5
• Screwed gland ½-14 NPT
• Han 7D plug (plastic housing) incl. mating connector11)
• M12 connectors (stainless steel)11)12)
0
1
2
3
4
5
6
}
Version
• Standard version, German plate inscription, setting for pressure unit: bar
• International version, English plate inscription, setting for pressure unit: bar
}
• Chinese version, English plate inscription, setting for pressure unit: Pascal
All versions include DVD with documentation for SITRANS P in German, English, French, Italian and Spanish. Includes Compact operating instructions in various EU languages.
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)"6)
- "Intrinsic safety and flameproof enclosure" (Ex ia + Ex d)"7)
- "Ex nA/ic (Zone 2)"8)
- "Intrinsic safety, explosion-proof enclosure and dust explosion protection
(Ex ia + Ex d + Zone 1D/2D)"7)9) (pending)
• FM + CSA intrinsic safe (is) (pending)10)
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX) + Zone 1D/2D7)9)10) (pending)
• With FM + CSA, Type of protection:
- "Intrinsic Safe and Explosion Proof (is + xp)"6)10) (pending)
A
B
C
Y
0
3
1
2
3
A
}
B
D
P
E
R
F
S
NC
}
B
C
D
F
Siemens FI 01 · 2016
1/209
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for gauge pressure
Article No.
Order code
7MF4033- 7 7 7 7 7 - 7 7 7 7 -Z C41
Selection and Ordering data
Pressure transmitter for gauge pressure, SITRANS P410 with HART
Display
• Without display
• Without visible display
(display concealed, setting: mA)
}
0
1
• With visible display (setting: mA)
6
• with customer-specific display (setting as specified, Order code "Y21" or "Y22" required)
7
} Available ex stock
Power supply units see Chap. 7 "Supplementary Components".
Included in delivery of the device:
• Brief instructions (Leporello)
• DVD with detailed documentation
1)
When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here.
If the acceptance test certificate 3.1.is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective
remote seals.
3) The diaphragm seal is to be specified with a separate order number and must be included with the transmitter order number, for example
7MF403.-..Y..-.... and 7MF4900-1...-.B
4)
The standard measuring cell filling of configurations with remote seals (Y) is silicone oil.
5)
Not in conjunction with Electrical connection "Han7D plug".
6) Without cable gland, with blanking plug
7)
With enclosed cable gland Ex ia and blanking plug
8)
Configurations with HAN and M12 connectors are only available in Ex ic.
9) Only in connection with IP66.
10)
Explosion protection acc. to FM/CSA: suitable for installations according to NEC 500/505.
11)
Only in connection with Ex approval A, B or E.
12) M12 delivered without cable socket
2)
1/210
Siemens FI 01 · 2016
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for gauge pressure
Selection and Ordering data
Article No.
Order code
Pressure transmitter for gauge pressure
SITRANS P410 with PROFIBUS PA (PA)
7MF4034- 7 7 7 7 7 - 7 7 7 7 -Z C41
SITRANS P410 with FOUNDATION Fieldbus (FF)
7MF4035- 7 7 7 7 7 - 7 7 7 7 -Z C41
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
Silicone oil
Measuring cell cleaning
normal
Nominal measuring range
1 bar
(14.5 psi)
4 bar
(58 psi)
16 bar
(232 psi)
63 bar
(914 psi)
160 bar
(2320 psi)
1
B
C
D
E
F
Wetted parts materials
Seal diaphragm
Process connection
Stainless steel
Stainless steel
Hastelloy
Stainless steel
Hastelloy
Hastelloy
Version as diaphragm seal 1) 2) 3) 4)
Process connection
• Connection shank G½B to EN 837-1
• Female thread ½-14 NPT
• Stainless steel oval flange with process connection (Oval flange has no female thread) 5)
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M10 to DIN 19213
- Mounting thread M12 to DIN 19213
• Male thread M20 x 1.5
• Male thread ½ -14 NPT
Non-wetted parts materials
• Housing made of die-cast aluminium
• Housing stainless steel precision casting
Version
• Standard version, German label inscription, setting of pressure unit: bar
• International version, English label inscription, setting of pressure unit: psi
• Chinese version, English label inscription, setting of pressure unit: kPa
All versions incl. DVD with documentation for SITRANS P in German, English, French, Italian and Spanish.
Incl. Compact operating instructions in various EU languages.
A
B
C
Y
0
1
2
3
4
5
6
0
3
1
2
3
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)"6)
- "Intrinsic safety and flameproof enclosure" (Ex ia + Ex d)"7)
- "Ex nA/ic (Zone 2)"8)
- "Intrinsic safety, explosion-proof enclosure and dust explosion protection
(Ex ia + Ex d + Zone 1D/2D)"7) 9) (not for P410 with FOUNDATION Fieldbus) (pending)
• FM + CSA intrinsic safe (is) (pending)10)
A
B
D
P
E
R
F
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX) + Zone 1D/2D7)9)10) (pending)
S
• With FM + CSA, Type of protection:
- "Intrinsic Safe and Explosion Proof (is + xp)"6)10) (pending)
NC
Electrical connection/cable entry
• Screwed gland M20 x 1.5
• Screwed gland ½-14 NPT
• M12 connectors (stainless steel)11) 12)
B
C
F
Siemens FI 01 · 2016
1/211
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for gauge pressure
Selection and Ordering data
Article No.
Order code
Pressure transmitter for gauge pressure
SITRANS P410 with PROFIBUS PA (PA)
7MF4034- 7 7 7 7 7 - 7 7 7 7 -Z C41
SITRANS P410 with FOUNDATION Fieldbus (FF)
7MF4035- 7 7 7 7 7 - 7 7 7 7 -Z C41
77777 - 7777
Display
• Without display
• Without visible display (display concealed,
setting: bar)
• With visible display (setting: bar)
• with customer-specific display (setting as specified, Order code "Y21" required)
0
1
6
7
Included in delivery of the device:
• Brief instructions (Leporello)
• DVD with detailed documentation
1)
When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here.
If the acceptance test certificate 3.1.is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective
remote seals.
3) The diaphragm seal is to be specified with a separate order number and must be included with the transmitter order number, for example
7MF403.-..Y..-.... and 7MF4900-1...-.B
4)
The standard measuring cell filling of configurations with remote seals (Y) is silicone oil.
5)
M10 fastening thread: Max. span 160 bar (2320 psi)
7/16-20 UNF and M12 fastening thread: Max. span 400 bar (5802 psi)
6) Without cable gland, with blanking plug.
7)
With enclosed cable gland Ex ia and blanking plug.
8)
Configurations with HAN and M12 connectors are only available in Ex ic.
9) Only in connection with IP66.
10)
Explosion protection acc. to FM/CSA: suitable for installations according to NEC 500/505.
11)
M12 delivered without cable socket.
12) Only in connection with Ex approval A, B, E or F.
2)
1/212
Siemens FI 01 · 2016
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for gauge pressure
Selection and Ordering data
Order code
Further designs
Add "-Z" to Article No. and specify Order
code.
Pressure transmitter with mounting
bracket (1x fixing angle, 2 x nut,
2 x U-washer or 1 x bracket, 2 x nut,
2 x U-washer) made of:
• Steel
• Stainless steel 304
• Stainless steel 316L
Plug
• Han 7D (metal)
• Han 8D (instead of Han 7D)
• Angled
• Han 8D (metal)
Cable sockets for M12 connectors
(metal (CuZn))
Rating plate inscription
(instead of German)
• English
• French
• Spanish
• Italian
HART PA
A01
A02
A03



A30
A31
A32
A33




A50





FF









Explosion protection "Explosion-proof"
to NEPSI (China)
(only for transmitter 7MF4...-.....-.D..)
E563)



Ex protection "Zone 2" to NEPSI (China)
(only for transmitter 7MF4...-.....-.E..)
E573)



Ex protection „Ex ia“, „Ex d“ and
„Zone 2“ to NEPSI (China)
(only for transmitter 7MF4...-.....-.R..)
E583)



"Intrinsic safety" and "Explosion-proof"
explosion protection acc. to Kosha (Korea)
(pending)
(only for transmitter
7MF4...-.....-.[B, D]..-Z + E11)
E703)



Ex-protection Ex ia according to EAC Ex
(Russia)
E804)



E814)




Ex-protection Ex d according to EAC Ex
(Russia)
E824)




Ex-protection Ex nA/ic (Zone 2) according
to EAC Ex (Russia)
Ex-protection Ex ia + Ex d + Zone 1D/2D
according to EAC Ex (Russia)
E834)



Two coats of lacquer on casing and
cover (PU on epoxy)
G10



Transient protector 6 kV (lightning protection)
J01



Oval flange NAM (ASTAVA)
J06







Quality Inspection Certificate (5-point
characteristic curve test) according to
IEC 60770-21)
C11






B21

E01

English rating plate
Pressure units in inH20 and/or psi

Use in or on zone 1D/2D
(only together with type of protection
"Intrinsic safety" (transmitter
7MF4...-.....-.B.. Ex ia)“ and IP66)
E553)





FF
E24




C12
HART PA
Dual seal




Inspection certificate
Acc. to EN 10204-3.1
Further designs
Add "-Z" to Article No. and specify Order
code.
Explosion-proof "Intrinsic safety" to
NEPSI (China)
(only for transmitter 7MF4...-.....-.B..)
B11
B12
B13
B14
2)
Order code
Selection and Ordering data
Factory certificate
Acc. to EN 10204-2.2
C14
Functional safety (SIL2) (pending)
Devices suitable for use according to
IEC 61508 and IEC 61511. Includes SIL
conformity declaration
C20
Functional safety (SIL2/3)
Devices suitable for use according to
IEC 61508 and IEC 61511. Includes SIL
conformity declaration
C23
Increased measuring accuracy
(mandatory specification for
SITRANS P410)
C41



Device passport Russia
C99



Setting of upper limit of output signal to
22.0 mA
D05

Manufacturer's declaration acc. to NACE
(MR 0103-2012 and MR 0175-2009)
D07



Degree of protection IP66/IP68
(only for M20x1.5 and ½-14 NPT)
D12



Supplied with oval flange
(1 item), PTFE packing and screws in
thread of oval flange
D37



Capri cable gland 4F CrNi and clamping
device (848699 + 810634) included
D59



TAG plate empty (no inscription)
D61





Factor valve block mounting for SITRANS P410 is possible. Depending
on the available P410 variants, please see the configuration options for
SITRANS P DS III (page 1/193).
1)
When the manufacture’s certificate (calibration certificate) has to be
ordered for transmitters with diaphragm seals according to IEC 60770-2, it
is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified
here.
2)
If the acceptance test certificate 3.1.is ordered for the transmitter with
mounted diaphragm seals this certificate must also be ordered with the
respective remote seals.
3)
Option does not include ATEX approval, but instead includes only the
country-specific approval.
4)
Approval pending.
Siemens FI 01 · 2016
1/213
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for gauge pressure
Selection and Ordering data
Order code
Additional data
Please add "-Z" to Article No. and specify
Order code(s) and plain text.
HART PA
FF
Measuring range to be set
Specify in plain text (max. 5 characters):
Y01: ... up to ... mbar, bar, kPa, MPa, psi
 Y01

1)
Stainless steel tag plate and entry in
device variable (measuring point
description)
Max. 16 characters, specify in plain text:
Y15: ...........................................
 Y15



Measuring point text (entry in device
variable)
Max. 27 characters, specify in plain text:
Y16: ...........................................
 Y16



Entry of HART address (TAG)
 Y17

Setting of pressure indication in pres Y21
sure units
Specify in plain text (standard setting: bar):
Y21: mbar, bar, kPa, MPa, psi, ...
Note:
The following pressure units can be
selected:
bar, mbar, mm H2O*), inH2O*), ftH2O*),
mmHG, inHG, psi, Pa, kPa, MPa, g/cm2,
kg/cm2, Torr, ATM or %
*) ref. temperature 20 °C



Setting of pressure indication in
 Y22 +
non-pressure units2)
Y01
Specify in plain text:
Y22: ..... up to ..... l/min, m3/h, m, USgpm, ...
(specification of measuring range in pressure units "Y01" is essential, unit with max.
5 characters)

Max. 8 characters, specify in plain text:
Y17: ...........................................
 = available
Ordering example
Item line:
7MF4033-1EA00-1AA7-Z C41
B line:
A01 + Y01 + Y21
C line:
Y01: 10 ... 20 bar (145 ... 290 psi)
C line:
Y21: bar (psi)
1)
2)
Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are
calculated in the same way as for HART devices.
Preset values can only be changed over SIMATIC PDM.
1/214
Siemens FI 01 · 2016
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for gauge pressure
53 (2.1)
54 (2.13)
27
(1.1)
approx. 96 (3.78)
Ø80 (3.15)
2
17 (0.67)
29 (1.14)
5
84 (3.31)
6
3
4
3
7
72 (2.8)
8
120 (4.72)
68 (2.68)
9
176 (6.93)
237 (9.33)
143 (5.6)
74 (2.9)
50 (1.97)
117 (4.61)
15
(0.6)
1
24
(0.94)
■ Dimensional drawings
Space for rotation
of housing
min. 90 (3.54) 4)
123 (4.84)
1
Ø50 ... 60
(1.97 ... 2.36)
Electronic side, digital display
(longer overall length for cover with window)1)
2
Terminal side1)
3
Electrical connection:
Screwed gland M20 x 1,5 or Screwed gland ½-14 NPT or
Han 7D/Han 8D2) 3) plug
4
Harting adapter
1)
Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing
Not with type of protection "Explosion-proof enclosure"
Not with type of protection "FM + CSA" [IS + XP]"
Minimum distance for rotating
2)
3)
4)
105 (4.13)
5
Protective cover over keys
6
Blanking plug
7
8
Screw cover - safety bracket (only for type of protection
"Explosion-proof enclosure", not shown in the drawing)
Process connection: Connection shank G½B
9
Mounting bracket (option)
SITRANS P410 pressure transmitters for gauge pressure, dimensions in mm (inch)
Siemens FI 01 · 2016
1/215
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for differential pressure and flow
■ Technical specifications
SITRANS P410 for differential pressure and flow
Input
Measured variable
Differential pressure and flow
Span (fully adjustable) or measuring range, max. operating
HART
pressure (in accordance with 2014/68/EU Pressure Equipment
Directive)
PROFIBUS PA/
FOUNDATION
Fieldbus
Span
Nominal measuring Max. operating pressure MAWP (PS)
range
2.5 ... 250 mbar
0.2 ... 25 kPa
1 ... 100 inH2O
250 mbar
25 kPa
100 inH2O
6 ... 600 mbar
0.6 ... 60 kPa
2.4 ... 240 inH2O
600 mbar
60 kPa
240 inH2O
16 ... 1600 mbar
1.6 ...160 kPa
6.4 ... 642 inH2O
1600 mbar
160 kPa
642 inH2O
50 ... 5000 mbar
5 ... 500 kPa
20 ... 2000 inH2O
5000 mbar
500 kPa
2000 inH2O
0.3 ... 30 bar
0.03 ... 3 MPa
4.35 ... 435 psi
30 bar
3 MPa
435 psi
6 ... 600 mbar
0.6 ... 60 kPa
2.4 ... 240 inH2O
600 mbar
60 kPa
240 inH2O
16 ... 1600 mbar
1.6 ...160 kPa
6.4 ... 642 inH2O
1600 mbar
160 kPa
642 inH2O
50 ... 5000 mbar
5 ... 500 kPa
20 ... 2000 inH2O
5000 mbar
500 kPa
2000 inH2O
0.3 ... 30 bar
0.03 ... 3 MPa
4.35 ... 435 psi
30 bar
3 MPa
435 psi
160 bar
16 MPa
2320 psi
420 bar
42 MPa
6091 psi
Lower measuring limit
• Measuring cell with silicone oil filling
-100 % of max. span (-33 % with measuring cell 30 bar/3 MPa/435 psi)
or 30 mbar a/3 kPa a/0.44 psi a
Upper measuring limit
100 % of max. span
Start of scale value
Between the measuring limits (fully adjustable)
Output
HART
PROFIBUS PA/ FOUNDATION Fieldbus
Output signal
4 ... 20 mA
Digital PROFIBUS PA and
FOUNDATION Fieldbus signal
• Lower limit (infinitely adjustable)
3.55 mA, factory preset to 3.84 mA
-
• Upper limit (infinitely adjustable)
23 mA, factory preset to 20.5 mA or
optionally set to 22.0 mA
-
• Without HART
RB  (UH - 10.5 V)/0.023 A in ,
UH: Power supply in V
-
• With HART
RB = 230 ... 500  (SIMATIC PDM) or
RB = 230 ... 1100  (HART Communicator)
Physical bus
-
Protection against polarity reversal
Protected against short-circuit and polarity reversal.
Each connection against the other with max. supply voltage.
Electrical damping (step width 0.1 s)
Set to 2 s (0 ... 100 s)
Load
1/216
Siemens FI 01 · 2016
IEC 61158-2
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for differential pressure and flow
SITRANS P410 for differential pressure and flow
Measuring accuracy
Acc. to IEC 60770-1
Reference conditions
• Increasing characteristic
• Start-of-scale value 0 bar/kPa/psi
• Stainless steel seal diaphragm
• Silicone oil filling
• Room temperature 25 °C (77 °F)
Measuring span ratio r (spread, Turn-Down)
r = max. measuring span/set measuring span or nom. pressure range
Error in measurement at limit setting incl.
hysteresis and reproducibility
• Linear characteristic
- 250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.7 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kpa/72.5 psi
30 bar/3 MPa/435 psi
r5:
5 < r  100 :
 0.04 %
 (0.004  r + 0.045) %
r5:
5 < r  100 :
 0.04 %
 (0.004  r + 0.045) %
r5:
5 < r  100 :
 0.08 %
 (0.008  r + 0.09) %
• Square-rooted characteristic (flow > 50 %)
- 250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.7 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kpa/72.5 psi
30 bar/3 MPa/435 psi
• Square-rooted characteristic
(flow > 25 ... 50 %)
- 250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.7 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kpa/72.5 psi
30 bar/3 MPa/435 psi
Influence of ambient temperature
(in percent per 28 °C (50 °F))
• 250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.7 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kpa/72.5 psi
30 bar/3 MPa/435 psi
 (0.025  r + 0.125) %
Influence of static pressure
• on the zero point (PKN)
- 250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.7 psi
1600 mbar/160 kPa/23.21 psi
 (0.1  r) % per 70 bar
(zero-point correction is possible with position error adjustment)
- 5 bar/500 kpa/72.5 psi
30 bar/3 MPa/435 psi
 (0.2  r) % per 70 bar
(zero-point correction is possible with position error adjustment)
• on the span (PKS)
- 250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.7 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kpa/72.5 psi
30 bar/3 MPa/435 psi
 0.14 % per 70 bar
Long-term stability
(temperature change ± 30 °C (± 54 °F))
Static pressure max. 70 bar/7 MPa/1015 psi
• 250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.7 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kpa/72.5 psi
 (0.125  r) % in 5 years
• 30 bar/3 MPa/435 psi
 (0.25  r) % in 5 years
Effect of mounting position (in pressure per change in angle)
 0.7 mbar/0.07 kPa/0.028 inH2O per 10° inclination
(zero-point correction is possible with position error adjustment)
Effect of auxiliary power supply
(in percent per change in voltage)
0.005 % per 1 V
Measuring value resolution for PROFIBUS PA and
FOUNDATION Fieldbus
3  10-5 of nominal measuring range
Siemens FI 01 · 2016
1/217
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for differential pressure and flow
SITRANS P410 for differential pressure and flow
Rated conditions
Degree of protection (to EN 60529)
IP66 (optional IP66/IP68), NEMA 4X
Temperature of medium
• Measuring cell with silicone oil filling
-40 ... +100 °C (-40 ... +212 °F)
-20 ... +100 °C (-4 ... +212 °F) with 30 bar measuring cell
• In conjunction with dust explosion protection
-20 ... +60 °C (-4 ... +140 °F)
Ambient conditions
• Ambient temperature
- Transmitter
-40 ... +85 °C (-40 ... +185 °F)
- Display readable
-30 ... +85 °C (-22 ... +185 °F)
• Storage temperature
-50 ... +85 °C (-58 ... +185 °F)
• Climatic class
- Condensation
Relative humidity 0 ... 100 %
Condensation permissible, suitable for use in the tropics
• Electromagnetic Compatibility
- Emitted interference and interference
immunity
Acc. to IEC 61326 and NAMUR NE 21
Design
Weight (without options)
Die-cast aluminum:  4.5 kg ( 9.9 lb)
Stainless steel precision casting:  7.1 kg ( 15.6 lb)
Enclosure material
Low-copper die-cast aluminum, GD-AlSi12 or stainless steel precision casting, mat.
no. 1.4408
Wetted parts materials
• Seal diaphragm
Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819
• Process flanges and sealing screw
Stainless steel, mat. no. 1.4408, Hastelloy C4, mat. no. 2.4602
• O-Ring
FPM (Viton) or optionally: PTFE, FEP, FEPM and NBR
Measuring cell filling
Silicone oil or inert filling liquid
(maximum value with oxygen measurement pressure 100 bar (1450 psi) at 60 °C
(140 °F))
Process connection
Female thread ¼-18 NPT and flange connection with mounting thread M10 to
DIN 19213 or 7/16-20 UNF to IEC 61518
Material of mounting bracket
• Steel
Sheet-steel, Mat. No. 1.0330, chrome-plated
• Stainless steel
Sheet stainless steel, mat. no. 1.4301 (SS 304)
Power supply UH
HART
Terminal voltage on transmitter
10.5 ... 45 V DC
10.5 ... 30 V DC in intrinsically-safe mode
Power supply
Separate 24 V power supply necessary
PROFIBUS PA/ FOUNDATION Fieldbus
Supplied through bus
-
No
• Not Ex
-
9 ... 32 V
• With intrinsically-safe operation
-
9 ... 24 V
• Basic current (max.)
-
12.5 mA
• Start-up current  basic current
-
Yes
• Max. current in event of fault
-
15.5 mA
Fault disconnection electronics (FDE) available
-
Yes
Bus voltage
Current consumption
1/218
Siemens FI 01 · 2016
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for differential pressure and flow
SITRANS P410 for differential pressure and flow
Certificates and approvals
HART
Classification according to PED 2014/68/EU
For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of
article 4, paragraph 3 (sound engineering practice)
PROFIBUS PA/ FOUNDATION Fieldbus
Explosion protection
• Intrinsic safety "i"
PTB 13 ATEX 2007 X
- Marking
Ex II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +70 °C (-40 ... +158 °F) temperature class T5;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6
- Connection
To certified intrinsically-safe circuits with
peak values:
Ui = 30 V, Ii = 100 mA, Pi = 750 mW;
Ri = 300 
FISCO supply unit:
Uo = 17.5 V, Io = 380 mA, Po = 5.32 W
Linear barrier:
Uo = 24 V, Io = 250 mA, Po = 1.2 W
- Effective internal inductance/capacitance
L i = 0.4 mH, Ci = 6 nF
L i = 7 H, Ci = 1.1 nF
• Explosion-proof "d"
PTB 99 ATEX 1160
- Marking
Ex II 1/2 G Ex d IIC T4/T6 Gb
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6
- Connection
To circuits with values: UH = 10.5 ... 45 V To circuits with values: UH = 9 ... 32 V DC
DC
• Dust explosion protection for zone 20 (pending)
PTB 01 ATEX 2055
- Marking
Ex II 1 D Ex ta IIIC T120°C Da
Ex II 1/2 D Ex ta/tb IIIC T120°C Da/Db
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F)
- Max. surface temperature
120 °C (248 °F)
- Connection
To certified intrinsically-safe circuits with
peak values:
Ui = 30 V, Ii = 100 mA,
Pi = 750 mW, Ri = 300 
FISCO supply unit:
Uo = 17.5 V, Io = 380 mA, Po = 5.32 W
Linear barrier:
Uo = 24 V, Io = 250 mA, Po = 1 W
- Effective internal inductance/capacitance
L i = 0.4 mH, Ci = 6 nF
L i = 7 H, Ci = 1.1 nF
• Dust explosion protection for zone 21/22 (pending)
PTB 01 ATEX 2055
- Marking
Ex II 2 D Ex tb IIIC T120°C Db
- Connection
To circuits with values: UH = 10.5 ... 45 V To circuits with values: UH = 9 ... 32 V
DC; Pmax = 1.2 W
DC;
Pmax = 1 W
• Type of protection "n" (zone 2)
PTB 13 ATEX 2007 X
- Marking
Ex II 2/3 G Ex nA IIC T4/T5/T6 Gc
Ex II 2/3 G Ex ic IIC T4/T5/T6 Gc
- Connection (Ex nA)
Um = 45 V
Um = 32 V
- Connection (Ex ic)
To circuits with values:
Ui = 45 V
FISCO supply unit ic:
Uo = 17.5 V, Io = 570 mA
Linear barrier:
Uo = 32 V, Io = 132 mA, Po = 1 W
- Effective internal inductance/capacitance
L i = 0.4 mH, Ci = 6 nF
L i = 7 H, Ci = 1.1 nF
• Explosion protection acc. to FM (pending)
- Identification (XP/DIP) or (IS); (NI)
• Explosion protection to CSA (pending)
- Identification (XP/DIP) or (IS)
Certificate of Compliance 3008490
CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC
T4...T6;
CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III
Certificate of Compliance 1153651
CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I,
DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III
Siemens FI 01 · 2016
1/219
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for differential pressure and flow
HART communication
HART
230 ... 1100 
Protocol
HART Version 5.x
Software for PC
SIMATIC PDM
PROFIBUS PA communication
Simultaneous communication with
master class 2 (max.)
4
The address can be set using
Configuration tool or local operation (standard setting
address 126)
Cyclic data usage
• Output byte
5 (one measured value) or
10 (two measured values)
• Input byte
0, 1, or 2 (register operating
mode and reset function for
metering)
Internal preprocessing
FOUNDATION Fieldbus
communication
Function blocks
3 function blocks analog input,
1 function block PID
• Analog input
- Adaptation to customerspecific process variables
Yes, linearly rising or falling
characteristic
- Electrical damping, adjustable
0 ... 100 s
- Simulation function
Output/input (can be locked
within the device with a bridge)
- Failure mode
parameterizable (last good
value, substitute value, incorrect
value)
- Limit monitoring
Yes, one upper and lower warning limit and one alarm limit
respectively
- Square-rooted characteristic
for flow measurement
Yes
Device profile
PROFIBUS PA Profile for Process Control Devices Version
3.0, class B
• PID
Standard FOUNDATION Fieldbus function block
• Physical block
1 resource block
Function blocks
2
Transducer blocks
- Adaptation to customer-specific process variables
Yes, linearly rising or falling
characteristic
1 transducer block Pressure with
calibration, 1 transducer block
LCD
• Pressure transducer block
- Electrical damping, adjustable
0 ... 100 s
- Simulation function
Input /Output
- Failure mode
parameterizable (last good
value, substitute value, incorrect
value)
- Limit monitoring
Yes, one upper and lower warning limit and one alarm limit
respectively
• Register (totalizer)
Can be reset, preset, optional
direction of counting, simulation
function of register output
• Analog input
- Failure mode
parameterizable (summation
with last good value, continuous
summation, summation with
incorrect value)
- Limit monitoring
One upper and lower warning
limit and one alarm limit respectively
• Physical block
1
Transducer blocks
2
• Pressure transducer block
- Can be calibrated by applying
two pressures
Yes
- Monitoring of sensor limits
Yes
- Specification of a container
characteristic with
Max. 30 nodes
- Square-rooted characteristic
for flow measurement
Yes
- Gradual volume suppression
and implementation point of
square-root extraction
Parameterizable
- Simulation function for measured pressure value and sensor temperature
Constant value or over parameterizable ramp function
1/220
Siemens FI 01 · 2016
- Can be calibrated by applying
two pressures
Yes
- Monitoring of sensor limits
Yes
- Simulation function: Measured
pressure value, sensor temperature and electronics temperature
Constant value or over parameterizable ramp function
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for differential pressure and flow
Selection and Ordering data
Article No.
Order Code
SITRANS P410 with HART pressure transmitters for differential pressure and flow,
PN 160 (MAWP 2320 psi)
7MF4433- 7 7 7 7 7 - 7 7 7 7 -Z C41
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
Silicone oil
Measuring cell cleaning
normal
Measuring span (min. ... max.)
2.5 ... 250 mbar
(1.004 ... 100.4 inH2O)
6 ... 600 mbar
(2.409 ... 240.9 inH2O)
16 ... 1600 mbar
(6.424 ... 642.4 inH2O)
50 ... 5000 mbar
(20.08 ... 2008 inH2O)
0.3 ... 30 bar
(4.35 ... 435 psi)
}
}
}
}
}
}
1
D
E
F
G
H
Wetted parts materials
(stainless steel process flanges)
Seal diaphragm
Parts of measuring cell
Stainless steel
Stainless steel
Hastelloy
Stainless steel
Hastelloy
Hastelloy
Version for diaphragm seal1) 2) 3) 4)
Process connection
Female thread ¼-18 NPT with flange connection
• Sealing screw opposite process connection
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M10 to DIN 19213 (only for replacement requirement)
• Vent on side of process flange5)
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M10 to DIN 19213 (only for replacement requirement)
}
}
A
B
C
Y
2
0
6
4
Non-wetted parts materials
process flange screws
Electronics housing
Stainless steel
Stainless steel
Die-cast aluminum
Stainless steel precision casting6)
Version
• Standard version, German plate inscription, setting for pressure unit: bar
• International version, English plate inscription, setting for pressure unit: bar
• Chinese version, English plate inscription, setting for pressure unit: Pascal
All versions include DVD with documentation for SITRANS P in German, English, French, Italian and
Spanish. Includes Compact operating instructions in various EU languages.
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)"7)
- "Intrinsic safety and flameproof enclosure" (Ex ia + Ex d)"8)
- "Ex nA/ic (Zone 2)"9)
- "Intrinsic safety, explosion-proof enclosure and dust explosion protection
(Ex ia+ Ex d + Zone 1D/2D)"8)10) (pending)
• FM + CSA intrinsic safe (is) (pending)11)
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX) + Zone 1D/2D8)10)11) (pending)
• With FM + CSA, Type of protection:
- "Intrinsic Safe and Explosion Proof (is + xp)"7)11) (pending)
}
}
}
2
3
1
2
3
A
}
B
D
P
E
R
F
S
NC
Siemens FI 01 · 2016
1/221
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for differential pressure and flow
Article No.
Order Code
7MF4433- 7 7 7 7 7 - 7 7 7 7 -Z C41
Selection and Ordering data
SITRANS P410 with HART pressure transmitters for differential pressure and flow,
PN 160 (MAWP 2320 psi)
Electrical connection/cable entry
• Screwed gland M20 x 1.5
• Screwed gland ½-14 NPT
• Han 7D plug (plastic housing) incl. mating connector12)13)
• M12 connectors (stainless steel)14)15)
Display
• Without display
• Without visible display (display concealed, setting: mA)
• With visible display (setting: mA)
• with customer-specific display (setting as specified, Order code "Y21" or "Y22" required)
}
B
C
D
F
}
0
1
6
7
} Available ex stock
Power supply units see Chap. 7 "Supplementary Components".
Included in delivery of the device:
• Brief instructions (Leporello)
• DVD with detailed documentation
• Sealing plug(s) or sealing screw(s) for the process flanges(s)
1)
When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here.
2)
If the acceptance test certificate 3.1.is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective
remote seals.
3)
The diaphragm seal is to be specified with a separate order number and must be included wiht the transmitter order number, for example
7MF443.-..Y..-.... and 7MF4900-1...-.B
4)
The standard measuring cell filling for configurations with remote seals (Y) is silicone oil.
5)
Not suitable for connection of remote seal. Position of the top vent valve in the process flange (see dimensional drawing).
6)
Not in conjunction with Electrical connection "Han7D plug".
7)
Without cable gland, with blanking plug
8)
With enclosed cable gland Ex ia and blanking plug
9)
Configurations with HAN and M12 connectors are only available in Ex ic.
10)
Only in connection with IP66.
11)
Explosion protection acc. to FM/CSA: suitable for installations according to NEC 500/505.
Only in connection with Ex approval A, B or E.
13)
Permissible only for crimp-contact of conductor cross-section 1 mm2
12)
14)
Only in connection with Ex approval A, B, E or F.
15)
M12 delivered without cable socket.
1/222
Siemens FI 01 · 2016
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for differential pressure and flow
Article No.
Selection and Ordering data
Order code
Pressure transmitters for differential pressure and flow PN 160 (MAWP 2320 psi)
SITRANS P410 with PROFIBUS PA (PA)
7MF4434- 7 7 7 7 7 - 7 7 7 7 -Z C41
SITRANS P410 with FOUNDATION Fieldbus (FF)
7MF4435- 7 7 7 7 7 - 7 7 7 7 -Z C41
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
Silicone oil
Measuring cell
cleaning
normal
1
Nominal measuring range
250 mbar (100.4 inH2O)
600 mbar (240.9 inH2O)
1600 mbar (642.4 inH2O)
5 bar
(2008 inH2O)
30 bar
(435 psi)
D
E
F
G
H
Wetted parts materials
(stainless steel process flanges)
Seal diaphragm
Parts of measuring cell
A
B
C
Y
Stainless steel
Stainless steel
Hastelloy
Stainless steel
Hastelloy
Hastelloy
Version as diaphragm seal 1) 2) 3) 4)
Process connection
Female thread ¼-18 NPT with flange connection
• Sealing screw opposite process connection
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M10 to DIN 19213 (only for replacement requirement)
• Venting on side of process flanges 5)
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M10 to DIN 19213 (only for replacement requirement)
2
0
6
4
Non-wetted parts materials
process flange screws
Electronics housing
Stainless steel
Stainless steel
2
3
Die-cast aluminum
Stainless steel precision casting
Version
• Standard version, German plate inscription, setting for pressure unit: bar
• International version, English plate inscription, setting for pressure unit: bar
• Chinese version, English plate inscription, setting for pressure unit: Pascal
All versions include DVD with documentation for SITRANS P in German, English, French, Italian and
Spanish. Includes Compact operating instructions in various EU languages.
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)"6)
- "Intrinsic safety and flameproof enclosure" (Ex ia + Ex d)"7)
- "Ex nA/ic (Zone 2)" 8)
- "Intrinsic safety, explosion-proof enclosure and dust explosion protection
(Ex ia + Ex d + Zone 1D/2D)"7) 9)(not for DS III FF) (pending)
• FM + CSA intrinsic safe (is) (pending)10)
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX) + Zone 1D/2D7)9)10) (pending)
• With FM + CSA, Type of protection:
- "Intrinsic Safe and Explosion Proof (is + xp)"8)10) (pending)
Electrical connection/cable entry
• Screwed gland M20 x 1.5
• Screwed gland ½-14 NPT
• M12 connectors (stainless steel)11) 12)
}
}
1
2
3
A
B
D
P
E
R
F
S
NC
B
C
F
Siemens FI 01 · 2016
1/223
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for differential pressure and flow
Selection and Ordering data
Article No.
Order code
Pressure transmitters for differential pressure and flow PN 160 (MAWP 2320 psi)
SITRANS P410 with PROFIBUS PA (PA)
7MF4434- 7 7 7 7 7 - 7 7 7 7 -Z C41
SITRANS P410 with FOUNDATION Fieldbus (FF)
7MF4435- 7 7 7 7 7 - 7 7 7 7 -Z C41
Display
• Without display
• Without visible display (display concealed, setting: bar)
• With visible display (setting: bar)
• With customer-specific display (setting as specified, Order code "Y21" required)
0
1
6
7
Included in delivery of the device:
• Brief instructions (Leporello)
• DVD with detailed documentation
• Sealing plug(s) or sealing screw(s) for the process flanges(s)
1)
2)
3)
4)
5)
6)
7)
When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here.
If the acceptance test certificate 3.1.is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective
remote seals.
The diaphragm seal is to be specified with a separate order number and must be included wiht the transmitter order number, for example
7MF443.-..Y..-.... and 7MF4900-1...-.B
The standard measuring cell filling for configurations with remote seals (Y) is silicone oil.
Not suitable for connection of remote seal. Position of the top vent valve in the process flange (see dimensional drawing).
Without cable gland, with blanking plug.
With enclosed cable gland Ex ia and blanking plug.
8)
Configurations with HAN and M12 connectors are only available in Ex ic.
Only in connection with IP66.
Explosion protection acc. to FM/CSA: suitable for installations according to NEC 500/505.
11)
Only in connection with Ex approval A, B, E or F.
12)
M12 delivered without cable socket
9)
10)
1/224
Siemens FI 01 · 2016
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for differential pressure and flow
Selection and Ordering data
Order code
Further designs
Add "-Z" to Article No. and specify Order
code.
Pressure transmitter with mounting
bracket (1x fixing angle, 2 x nut,
2 x U-washer or 1 x bracket, 2 x nut,
2 x U-washer) made of:
• Steel
• Stainless steel 304
• Stainless steel 316L
O-rings for process flanges
(instead of FPM (Viton))
• PTFE (Teflon)
• FEP (with silicone core, approved for food)
• FFPM (Kalrez, compound 4079),
for measured medium temperatures
-15 ... 100 °C (5 ... 212 °F)
• NBR (Buna N)
Plug
• Han 7D (metal)
• Han 8D (instead of Han 7D)
• Angled
• Han 8D (metal)
Order code
Selection and Ordering data
HART PA
FF
A01
A02
A03









A20
A21
A22









A23



Further designs
Add "-Z" to Article No. and specify Order
code.
HART PA
FF
Setting of upper limit of
output signal to 22.0 mA
D05

Manufacturer's declaration acc. to NACE
(MR 0103-2012 and MR 0175-2009)
(only together with seal diaphragm made of
Hastelloy and stainless steel)
D07



Degree of protection IP66/IP68
(only for M20 x 1.5 and ½-14 NPT)
D12



Supplied with oval flange set
(2 items), PTFE packings and screws in
thread of process flanges
D37



Capri cable gland 4F CrNi and clamping
device (848699 + 810634) included
D59



TAG plate empty (no inscription)
D61



Use in or on zone 1D/2D
(only together with type of protection
"Intrinsic safety" (transmitter
7MF4...-.....-.B.. Ex ia)“and IP66)
E01



A30
A31
A32
A33




Dual seal
E24



Sealing screws (2 units)
¼-18 NPT, with valve in mat. of process
flanges
A40



Explosion-proof "Intrinsic safety" to
NEPSI (China)
(only for transmitter 7MF4...-.....-.B..)
E553)



Cable sockets for M12 connectors
(metal (CuZn))
A50



Explosion protection "Explosion-proof"
to NEPSI (China)
(only for transmitter 7MF4...-.....-.D..)
E563)



Explosion-proof "Zone 2" to NEPSI
(China)
(only for transmitter 7MF4...-.....-.E..)
E573)



Ex protection „Ex ia“, „Ex d“ and „Zone
2“ to NEPSI (China)
(only for transmitter 7MF4...-.....-.R..)
E583)



"Intrinsic safety" and "Explosion-proof"
explosion protection acc. to Kosha (Korea)
(pending)
(only for transmitter
7MF4...-.....-.[B, D]..-Z + E11)
E703)



Ex-protection Ex ia according to EAC Ex
(Russia)
E804)



Ex-protection Ex d according to EAC Ex
(Russia)
E814)



Ex-protection Ex nA/ic (Zone 2) according
to EAC Ex (Russia)
E824)



Ex-protection Ex ia + Ex d + Zone 1D/2D
according to EAC Ex (Russia)
E834)



Two coats of lacquer on casing and
cover (PU on epoxy)
G10



Interchanging of process connection
side
H01



Vent on side for gas measurements
H02



Stainless steel process flanges for vertical differential pressure lines
(not together with K01, K02 and K04)5)
H03



Rating plate inscription
(instead of German)
• English
• French
• Spanish
• Italian
B11
B12
B13
B14












English rating plate
Pressure units in inH2O and/or psi
B21



Quality Inspection Certificate (5-point
characteristic curve test) according to
IEC 60770-21)
C11



Inspection certificate2) to EN 10204-3.1
C12



Factory certificate to EN 10204-2.2
C14



Functional safety (SIL2) (pending)
Devices suitable for use according to
IEC 61508 and IEC 61511. Includes SIL
conformity declaration
C20

Functional safety (SIL2/3)
Devices suitable for use according to
IEC 61508 and IEC 61511. Includes SIL
conformity declaration
C23

Increased measuring accuracy
(mandatory specification for
SITRANS P410)
C41

Device passport Russia
C99





Siemens FI 01 · 2016
1/225
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for differential pressure and flow
Selection and Ordering data
Order code
Further designs
Add "-Z" to Article No. and specify Order
code.
Order code
Selection and Ordering data
HART PA
FF
Additional data
Please add "-Z" to Article No. and specify
Order code(s) and plain text.
Measuring range to be set
Specify in plain text:
• in the case of linear characteristic curve  Y01
(max. 5 characters):
Y01: ... up to ... mbar, bar, kPa, MPa, psi
• in the case of square rooted characteristic  Y02
(max. 5 characters):
Y02: ... up to ... mbar, bar, kPa, MPa, psi
Transient protector 6 kV (lightning protection)
J01



Chambered graphite gasket for process
flange
J02



Chambered PTFE graphite gasket
J03



EPDM O-rings for process flange with
approval (WRC/WRAS)
J05



Vent valve or blanking plug of process
flange welded-in (orientation: on right
when viewing the display)6)
J08



Vent valve or blanking plug of process
flange welded-in (orientation: on left
when viewing the display)6)
J09



Factor valve block mounting for SITRANS P410 is possible. Depending
on the available P410 variants, please see the configuration options for
SITRANS P DS III (page 1/193).
 = available
1)
When the manufacture’s certificate (calibration certificate) has to be ordered
for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The
measuring accuracy of the total combination is certified here.
2)
If the acceptance test certificate 3.1.is ordered for the transmitter with
mounted diaphragm seals this certificate must also be ordered with the
respective remote seals.
3)
Option does not include ATEX approval, but instead includes only the
country-specific approval.
4)
Approval pending.
5)
Not suitable for connection of remote seal.
6)
Blanking plug is standard configuration. Order option A40 if a vent valve is
required instead of a blanking plug.
HART PA

FF
1)

Stainless steel tag plate and entry in
device variable (measuring point
description)
Max. 16 characters, specify in plain text:
Y15: ...........................................
 Y15



Measuring point text (entry in device
variable)
Max. 27 char., specify in plain text: Y16:
.......
 Y16



 Y17
Entry of HART address (TAG)
Max. 8 char., specify in plain text: Y17: .......

 Y21
Setting of pressure indicator in
pressure units
Specify in plain text (standard setting: bar):
Y21: mbar, bar, kPa, MPa, psi, ...
Note: The following pressure units can be
selected:
bar, mbar, mm H2O*), inH2O*), ftH2O*),
mmHG, inHG, psi, Pa, kPa, MPa, g/cm2,
kg/cm2, Torr, ATM or %
*) ref. temperature 20 °C




Setting of pressure indicator in nonpressure units2)
Specify in plain text:
Y22: ..... up to ..... l/min, m3/h, m, USgpm, ...
(specification of measuring range in pressure units "Y01" or "Y02" is essential, unit
with max. 5 characters)
Y223)
+
Y01 or
Y02

Preset bus address
possible between 1 and 126
Specify in plain text: Y25: .....................
Y25


Damping adjustment in seconds
(0 ... 100 s)
Y30



Only Y01, Y15, Y16, Y17, Y21, Y22, Y25 and D05 can be factory preset
 = available
1)
2)
3)
1/226
Siemens FI 01 · 2016
Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are
calculated in the same way as for HART devices.
Preset values can only be changed over SIMATIC PDM.
Not in conjunction with over-filling safety device for flammable and nonflammable liquids (Order code "E08")
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for differential pressure and flow
Selection and Ordering data
Article No.
Order code
SITRANS P DS III with HART pressure transmitters for differential pressure and flow,
PN 420 (MAWP 6092 psi)
7MF4533- 7 7 7 7 7 - 7 7 7 7 -Z C41
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
Silicone oil
Measuring cell cleaning
normal
Measuring span (min. ... max.)
6 ... 600 mbar
(2.4 ... 240 inH2O)
16 ... 1600 mbar
(6.4 ... 642 inH2O)
50 ... 5000 mbar
(20 ... 2000 inH2O)
0.3 ... 30 bar
(4.35 ... 435 psi)
1
E
F
G
H
Wetted parts materials
(stainless steel process flanges)
Seal diaphragm
Parts of measuring cell
Stainless steel
Stainless steel
Hastelloy
Stainless steel
Version for diaphragm seal 1) 2) 3) 4)
Process connection
Female thread ¼-18 NPT with flange connection
• Sealing screw opposite process connection
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M12 to DIN 19213 (only for replacement requirement)
• Venting on side of process flanges, location of vent valve at top of process flanges
(see dimensional drawing)
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M12 to DIN 19213 (only for replacement requirement)
A
B
Y
3
1
7
5
Non-wetted parts materials
process flange screws Electronics housing
Stainless steel
Stainless steel
Die-cast aluminum
Stainless steel precision casting5)
Version
• Standard version, German plate inscription, setting for pressure unit: bar
• International version, English plate inscription, setting for pressure unit: bar
• Chinese version, English plate inscription, setting for pressure unit: Pascal
All versions include DVD with documentation for SITRANS P in German, English, French, Italian and Spanish. Includes Compact operating instructions in various EU languages.
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)"6)
- "Intrinsic safety and flameproof enclosure" (Ex ia + Ex d)"7)
- "Ex nA/ic (Zone 2)"8)
- "Intrinsic safety, explosion-proof enclosure and dust explosion protection
(Ex ia+ Ex d + Zone 1D/2D)"7)9) (pending)
• FM + CSA intrinsic safe (is) (pending)10)
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX) + Zone 1D/2D7)9)10) (pending)
• With FM + CSA, Type of protection:
- "Intrinsic safety and explosion-proof (is + xp)" 6)10), max PN 360 (pending)
Electrical connection/cable entry
• Screwed gland M20x1.5
• Screwed gland ½-14 NPT
• Han 7D plug (plastic housing) incl. mating connector11) 12)
• M12 connectors (stainless steel)13)14)
2
3
1
2
3
A
B
D
P
E
R
F
S
NC
B
C
D
F
Siemens FI 01 · 2016
1/227
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for differential pressure and flow
Selection and Ordering data
SITRANS P DS III with HART pressure transmitters for differential pressure and flow,
PN 420 (MAWP 6092 psi)
Display
• Without display
• Without visible display (display concealed, setting: mA)
• With visible display (setting: mA)
• with customer-specific display (setting as specified, Order code "Y21" or "Y22" required)
Article No.
Order code
7MF4533- 7 7 7 7 7 - 7 7 7 7 -Z C41
0
1
6
7
Power supply units see Chap. 7 "Supplementary Components".
Scope of delivery: Pressure transmitter as ordered (Instruction Manual is extra ordering item)
1)
When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here.
2) If the acceptance test certificate 3.1.is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective
remote seals.
3)
The diaphragm seal is to be specified with a separate order number and must be included wiht the transmitter order number, for example
7MF453.-..Y..-.... and 7MF4900-1....-.B
4)
The standard measuring cell filling for configurations with remote seals (Y) is silicone oil.
5) Not in conjunction with Electrical connection "Han7D plug".
6)
Without cable gland, with blanking plug
7)
With enclosed cable gland Ex ia and blanking plug
8) Configurations with HAN and M12 connectors are only available in Ex ic.
9)
Only in connection with IP66.
10)
Explosion protection acc. to FM/CSA: suitable for installations according to NEC 500/505.
11) Only in connection with Ex approval A, B or E.
12)
Permissible only for crimp-contact of conductor cross-section 1 mm2
13)
Only in connection with Ex approval A, B, E or F.
14) M12 delivered without cable socket.
1/228
Siemens FI 01 · 2016
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for differential pressure and flow
Selection and Ordering data
Article No.
Order Code
Pressure transmitters for differential pressure and flow, PN 420 (MAWP 6092 psi)
SITRANS P410 with PROFIBUS PA (PA)
7MF4534- 7 7 7 7 7 - 7 7 7 7 -Z C41
SITRANS P410 with FOUNDATION Fieldbus (FF)
7MF4535- 7 7 7 7 7 - 7 7 7 7 -Z C41
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
Silicone oil
Measuring cell cleaning
normal
Nominal measuring range
600 mbar
(240 inH2O)
1600 mbar
(642 inH2O)
5 bar
(2000 inH2O)
30 bar
(435 psi)
1
E
F
G
H
Wetted parts materials
(stainless steel process flanges)
Seal diaphragm
Parts of measuring cell
Stainless steel
Stainless steel
Hastelloy
Stainless steel
Version for diaphragm seal 1) 2) 3) 4)
Process connection
Female thread ¼-18 NPT with flange connection
• Sealing screw opposite process connection
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M12 to DIN 19213 (only for replacement requirement)
• Venting on side of process flanges, location of vent valve at top of process flanges
(see dimensional drawing).
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M12 to DIN 19213 (only for replacement requirement)
A
B
Y
3
1
7
5
Non-wetted parts materials
Process flange screws Electronics housing
Stainless steel
Stainless steel
Die-cast aluminum
Stainless steel precision casting
Version
• Standard version, German plate inscription, setting for pressure unit: bar
• International version, English plate inscription, setting for pressure unit: bar
• Chinese version, English plate inscription, setting for pressure unit: Pascal
All versions include DVD with documentation for SITRANS P in German, English, French, Italian and Spanish. Includes Compact operating instructions in various EU languages.
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)"5)
- "Intrinsic safety and flameproof enclosure" (Ex ia + Ex d)"6)
- "Ex nA/ic (Zone 2)" 7)
- "Intrinsic safety, explosion-proof enclosure and dust explosion protection
(Ex ia + Ex d + Zone 1D/2D)"6)8) (not for P410 with FOUNDATION Fieldbus) (pending)
• FM + CSA intrinsic safe (is) (pending)9)
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX) + Zone 1D/2D6)7)9) (pending)
• With FM + CSA, Type of protection:
- "Intrinsic safety and explosion-proof (is + xp)"6)9), max PN 360 (pending)
Electrical connection/cable entry
• Screwed gland M20 x 1.5
• Screwed gland ½-14 NPT
• M12 connectors (stainless steel) 10) 11)
2
3
1
2
3
A
B
D
P
E
R
F
S
NC
B
C
F
Siemens FI 01 · 2016
1/229
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for differential pressure and flow
Selection and Ordering data
Article No.
Order Code
Pressure transmitters for differential pressure and flow, PN 420 (MAWP 6092 psi)
SITRANS P410 with PROFIBUS PA (PA)
7MF4534- 7 7 7 7 7 - 7 7 7 7 -Z C41
SITRANS P410 with FOUNDATION Fieldbus (FF)
7MF4535- 7 7 7 7 7 - 7 7 7 7 -Z C41
1 7777 - 7777
Display
• Without (display hidden)
• Without visible display (display concealed, setting: bar)
• With visible display (setting: bar)
• With customer-specific display (setting as specified, Order code "Y21" required)
0
1
6
7
Included in delivery of the device:
• Brief instructions (Leporello)
• DVD with detailed documentation
• Sealing plug(s) or sealing screw(s) for the process flanges(s)
1)
When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here.
If the acceptance test certificate 3.1.is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective
remote seals.
3) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example
7MF453.-..Y..-.... and 7MF4900-1....-.B
4)
The standard measuring cell filling for configurations with remote seals (Y) is silicone oil.
5)
Without cable gland, with blanking plug.
6) With enclosed cable gland Ex ia and blanking plug.
7)
Configurations with HAN and M12 connectors are only available in Ex ic.
8)
Only in connection with IP66.
9) Explosion protection acc. to FM/CSA: suitable for installations according to NEC 500/505.
10)
Only in connection with Ex approval A, B, E or F.
11)
M12 delivered without cable socket
2)
1/230
Siemens FI 01 · 2016
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for differential pressure and flow
Selection and Ordering data
Order code
Further designs
Add "-Z" to Article No. and specify Order code.
Pressure transmitter with mounting
bracket (1x fixing angle, 2 x nut, 2 x Uwasher or 1 x bracket, 2 x nut, 2 x Uwasher) made of:
• Steel
• Stainless steel 304
• Stainless steel 316L
HART PA
FF
A01
A02
A03









A20
A21
A22









A23



A30
A31
A32
A33




Sealing screws (2 units)
A40
¼-18 NPT, with valve in mat. of process flanges



Cable sockets for M12 connection
(metal (CuZn))
A50



B11
B12
B13
B14












B21



Quality Inspection Certificate (5-point char- C11
acteristic curve test) according to
IEC 60770-2



Inspection certificate
Acc. to EN 10204-3.1
C12



Factory certificate
Acc. to EN 10204-2.2
C14



Functional safety (SIL2) (pending)
C20
Devices suitable for use according to
IEC 61508 and IEC 61511. Includes SIL conformity declaration

Functional safety (SIL2/3)
C23
Devices suitable for use according to
IEC 61508 and IEC 61511. Includes SIL conformity declaration

Increased measuring accuracy
C41
(mandatory specification for SITRANS P410)



Device passport Russia
C99



Setting of upper limit of output signal to
22.0 mA
D05

Manufacturer's declaration acc. to NACE
(MR 0103-2012 and MR 0175-2009)
(only together with seal diaphragm made of
Hastelloy and stainless steel)
D07



Degree of protection IP66/IP68
(only for M20 x 1.5 and ½-14 NPT)
D12



Capri cable gland 4F CrNi and clamping
device (848699 + 810634) included
D59



TAG plate empty (no inscription)
D61



O-rings for process flanges
(instead of FPM (Viton))
• PTFE (Teflon)
• FEP (with silicone core, approved for food)
• FFPM (Kalrez, compound 4079),
for measured medium temperatures
-15 ... 100 °C (5 ... 212 °F)
• NBR (Buna N)
Plug
• Han 7D (metal)
• Han 8D (instead of Han 7D)
• Angled
• Han 8D (metal)
Rating plate inscription (instead of German)
• English
• French
• Spanish
• Italian
English rating plate
Pressure units in inH2O and/or psi
Order code
Selection and Ordering data
Further designs
Add "-Z" to Article No. and specify Order code.
HART PA
FF
Use in or on zone 1D/2D
(only together with type of protection
"Intrinsic safety" (transmitter
7MF4...-.....-.B.. Ex ia)“and IP66)
E01



Dual seal
E24



Explosion-proof "Intrinsic safety"
to NEPSI (China)
(only for transmitter 7MF4...-.....-.B..)
E551)



Ex prot. "Explosion-proof" to NEPSI (China) E561)
(only for transmitter 7MF4...-.....-.D..)



Explosion-proof "Zone 2" to NEPSI (China) E571)
(only for transmitter 7MF4...-.....-.E..)



Ex protection „Ex ia“, „Ex d“ and „Zone 2“ E581)
to NEPSI (China)
(only for transmitter 7MF4...-.....-.R..)



"Intrinsic safety" and "Explosion-proof"
explosion protection acc. to Kosha (Korea)
(pending)
(only for transmitter
7MF4...-.....-.[B, D]..-Z + E11)
E701)



Ex-protection Ex ia according to EAC Ex
(Russia)
E802)



Ex-protection Ex d according to EAC Ex
(Russia)
E812)



Ex-protection Ex nA/ic (Zone 2) according to E822)
EAC Ex (Russia)



Ex-protection Ex ia + Ex d + Zone 1D/2D
according to EAC Ex (Russia)
E832)



Two coats of lacquer on casing and cover
(PU on epoxy)
G10



Interchanging of process connection side
H01



Vent on side for gas measurements
H02



Stainless steel process flanges for vertical H03
differential pressure lines



Transient protector 6 kV (lightning protec- J01
tion)



Chambered graphite gasket for process
flange
J02



Chambered PTFE graphite gasket
J03



EPDM O-rings for process flange with
approval (WRC/WRAS)
J05



Vent valve or blanking plug of process
flange welded-in (orientation: on right
when viewing the display)3)
J08



Vent valve or blanking plug of process
J09
flange welded-in (orientation: on left when
viewing the display)3)



Factor valve block mounting for SITRANS P410 is possible. Depending
on the available P410 variants, please see the configuration options for
SITRANS P DS III (page 1/193).
1)
Option does not include ATEX approval, but instead includes only the
country-specific approval.
2) Approval pending.
3)
Blanking plug is standard configuration. Order option A40 if a vent valve is
required instead of a blanking plug.
Siemens FI 01 · 2016
1/231
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 for differential pressure and flow
Selection and Ordering data
Order code
Additional data
HART PA
FF
Please add "-Z" to Article No. and specify
Order code(s) and plain text.
Measuring range to be set
Specify in plain text:
• in the case of linear characteristic curve
(max. 5 characters):
Y01: ... up to ... mbar, bar, kPa, MPa, psi
• in the case of square rooted characteristic
(max. 5 characters):
Y02: ... up to ... mbar, bar, kPa, MPa, psi
1)
Y01

Y02

Y15



Measuring point text (entry in device vari- Y16
able)
Max. 27 char., specify in plain text: Y16: .......



Entry of HART address (TAG)
Y17
Max. 8 char., specify in plain text: Y17: .........

Setting of pressure indication in pressure Y21
units
Specify in plain text (standard setting: bar):
Y21: mbar, bar, kPa, MPa, psi, ...
Note:
The following pressure units can be selected:
bar, mbar, mm H2O*), inH2O*), ftH2O*),
mmHG, inHG, psi, Pa, kPa, MPa, g/cm2,
kg/cm2, Torr, ATM or %
*) ref. temperature 20 °C



Setting of pressure indication in
Y22 +
non-pressure units2)
Y01 or
Y02
Specify in plain text:
3
Y22: ..... up to ..... l/min, m /h, m, USgpm, ...
(specification of measuring range in pressure
units "Y01" or "Y02" is essential, unit with
max. 5 characters)





Stainless steel tag plate and entry in
device variable (measuring point description)
Max. 16 characters, specify in plain text:
Y15: ...........................................
Preset bus address
possible between 1 and 126
Specify in plain text: Y25: .....................
Y25
Damping adjustment in seconds
(0 ... 100 s)
Y30

Only Y01, Y15, Y16, Y17, Y21, Y22, Y25 and D05 can be factory preset.
 = available
1)
Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are
calculated in the same way as for HART devices.
2) Preset values can only be changed over SIMATIC PDM.
1/232
Siemens FI 01 · 2016
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 for differential pressure and flow
■ Dimensional drawings
143 (5.6)
Ø80 (3.15)
1
5
2
29
(1.14)
84 (3.31)
6
3
7
8
166 (6.54)
53 (2.1)
24
(0.94)
69 (2.7)
50 (1.97)
128 (5.04)
15
(0.6)
12
10
11
52 (2.05)
3
17 (0.67)
4
72 (2.83)
68 (2.7)
105 (4.1)
Electronic side, digital display
(longer overall length for cover with window)1)
2
Terminal side1)
3
Electrical connection:
Screwed gland M20 x 1,5 or Screwed gland ½-14 NPT or
Han 7D/ Han 8D2) 3) plug
4
Harting adapter
5
Protective cover over keys
1)
Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing
Not with type of protection "Explosion-proof enclosure"
Not with type of protection "FM + CSA" [IS + XP]"
92 mm (3.62 inch) for minimum distance to permit rotation with indicator
2)
3)
4)
96 (3.8)
134 (5.28)
Space for rotation
of housing
9
approx. 96 (3.78)
1
262 (10.3)
min. 90 (3.54) 4)
120 (4.7)
6
Blanking plug
7
Screw cover - safety bracket (only for type of protection
"Explosion-proof enclosure", not shown in the drawing)
8
Lateral venting for liquid measurement (Standard)
9
Lateral venting for gas measurement (suffix H02)
10 Mounting bracket (option)
11 Sealing screw with valve (option)
12 Process connection: ¼-18 NPT (IEC 61518)
SITRANS P410 pressure transmitters for differential pressure and flow, dimensions in mm (inch)
Siemens FI 01 · 2016
1/233
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
143 (5.6)
53 (2.1)
17 (0.67)
5
29 (1.14)
84 (3.31)
50 (1.97)
1
approx. 96 (3.78)
6
3
4
3
7
2
min. 90 (3.54) 4)
approx. 85 (3.35) 6)
Space for rotation
of housing
8
60 (2.36) 5)
8
128 (5.04)
approx. 217 (8.54) 7)
15
(0.6)
24
(0.94)
SITRANS P410 for differential pressure and flow
Ø80 (3.15)
1
9
approx. 87 (3.43)
65 (2.56)
Electronic side, digital display
(longer overall length for cover with window)1)
5
Protective cover over keys
6
Blanking plug
2
Terminal side1)
7
3
Electrical connection:
Screwed gland M20 x 1,5 or Screwed gland ½-14 NPT or
Han 7D/ Han 8D2) 3) plug
Screw cover - safety bracket (only for type of protection
"Explosion-proof enclosure", not shown in the drawing)
8
Sealing screw with valve (option)
9
Process connection: ¼-18 NPT (IEC 61518)
1
4
Harting adapter
1)
Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing
Not with type of protection "Explosion-proof enclosure"
Not with type of protection "FM + CSA" [IS + XP]"
92 mm (3.6 inch) for minimum distance to permit rotation with indicator
74 mm (2.9 inch) for PN ≥ 420 (MAWP ≥ 6092 psi)
91 mm (3.6 inch) for PN ≥ 420 (MAWP ≥ 6092 psi)
219 mm (8.62 inch) for PN ≥ 420 (MAWP ≥ 6092 psi)
2)
3)
4)
5)
6)
7)
SITRANS P410 pressure transmitters for differential pressure and flow, with process covers for vertical differential pressure lines, optional "H03" ,
dimensional drawing, dimensions in mm (inch)
SITRANS P410 pressure transmitters for differential pressure and flow,
with process covers for vertical differential pressure lines
1/234
Siemens FI 01 · 2016
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 - Accessories/Spare parts
Selection and Ordering data
Article No.
Article No.
Selection and Ordering data
Accessories/Spare parts
Mounting screws
Mounting bracket and fastening parts
for pressure transmitters
SITRANS P410 with HART, P410 with
PROFIBUS PA and P410 with FOUNDATION
Fieldbus (7MF403.-.....-..C.)
• made of steel
• made of stainless steel 304/1.4301
• made of stainless steel 316L/1.4404
For measuring point label, grounding and connection terminals or for display (50 units)
7MF4997-1AB
7MF4997-1AH
7MF4997-1AP
Mounting bracket and fastening parts
for pressure transmitters
SITRANS P410 with HART, P410 with
PROFIBUS PA and P10with FOUNDATION
Fieldbus (7MF403-.....-..A., -..B., ..D. and ..F.)
• made of steel
7MF4997-1AC
• made of stainless steel 304/1.4301
} 7MF4997-1AJ
• made of stainless steel 316L/1.4404
7MF4997-1AQ
Mounting and fastening brackets
For differential pressure transmitters with
flange thread M10
SITRANS P410 with HART, P410 with
PROFIBUS PA and P410 with FOUNDATION
Fieldbus (7MF443.-...)
• made of steel
• made of stainless steel 304/1.4301
• made of stainless steel 316L/1.4404
7MF4997-1AD
} 7MF4997-1AK
7MF4997-1AR
Mounting and fastening brackets
For differential pressure transmitters with
flange thread M12
SITRANS P410 with HART, P410 with
PROFIBUS PA and P410 with FOUNDATION
Fieldbus (7MF453.-...)
• made of steel
• made of stainless steel 304/1.4301
• made of stainless steel 316L/1.4404
7MF4997-1AE
7MF4997-1AL
7MF4997-1AS
Mounting and fastening brackets
For differential pressure transmitters with
flange thread 7/16 -20 UNF
SITRANS P410 with HART, P410 with
PROFIBUS PA and P410 with FOUNDATION
Fieldbus (7MF443.-... and 7MF453.-...)
• made of steel
• made of stainless steel 304/1.4301
• made of stainless steel 316L/1.4404
7MF4997-1AF
7MF4997-1AM
7MF4997-1AT
Sealing screws
(1 set = 2 units) for process flange
• made of stainless steel
• made of Hastelloy
7MF4997-1CD
7MF4997-1CG
7MF4997-1CH
Sealing screws with vent valve
Complete (1 set = 2 units)
• made of stainless steel
• made of Hastelloy
} 7MF4997-1CP
7MF4997-1CQ
Connection board
• for SITRANS P410
• for SITRANS P410 with PROFIBUS PA and
P410 with FOUNDATION Fieldbus
7MF4997-1DN
7MF4997-1DP
O-rings for process flanges made of:
• FPM (Viton)
• PTFE (Teflon)
• FEP (with silicone core, approved for food)
• FFPM (Kalrez, compound 4079)
• NBR (Buna N)
7MF4997-2DA
7MF4997-2DB
7MF4997-2DC
7MF4997-2DD
7MF4997-2DE
Sealing ring for process connection
see "Fittings"
} Available ex stock
Cover
Made of die-cast aluminum, including gasket,
for SITRANS P410 with HART, P410 with
PROFIBUS PA and P410 with FOUNDATION
Fieldbus.
Compatible for Ex and non-Ex transmitters
• without window
7MF4997-1BB
• with window
} 7MF4997-1BE
Cover
Made of stainless steel, including gasket,
or SITRANS P410 with HART, P410 with
PROFIBUS PA and P410 with FOUNDATION
Fieldbus.
Compatible for Ex and non-Ex transmitters
• without window
• with window
Digital indicator
Including mounting material, for SITRANS
P410 with HART, P410 with PROFIBUS PA and
P410 with FOUNDATION Fieldbus
Measuring point label
• without inscription (5 units)
• Printed (1 unit)
Data according to Y01 or Y02, Y15, Y16 and
Y99 (see "Pressure transmitters")
7MF4997-1BC
7MF4997-1BF
7MF4997-1BR
7MF4997-1CA
7MF4997-1CB-Z
Y..: ......................
Siemens FI 01 · 2016
1/235
1
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
1
SITRANS P410 - Accessories/Spare parts
Selection and Ordering data
Article No.
Documentation
The entire documentation is available for
download free-of-charge in various languages
at: http://www.siemens.com/processinstrumentation/documentation
Compact operating instructions
SITRANS P DS III/P410
• English, German, Spanish, French, Italian,
Dutch
• Estonian, Latvian, Lithuanian, Polish,
Romanian, Croatian
• Bulgarian, Czech, Finnish, Slovakian,
Slovenian
• Danish, Greek, Portuguese, Swedish,
Hungarian
The compact operating instructions are available on the DVD supplied with each transmitter.
DVD with documentation
The DVD contains detailed documentation for
all device versions
Certificates (order only via SAP)
instead of Internet download
• hard copy (to order)
• on DVD (to order)
HART modem
with USB interface
A5E03434626
A5E03434631
A5E03434645
A5E03434656
A5E00090345
A5E03252406
A5E03252407
} 7MF4997-1DB
} Available ex stock
Power supply units see Chap. 7 "Supplementary Components".
1/236
Siemens FI 01 · 2016
© Siemens AG 2016
Pressure Measurement
Transmitters for applications with advanced requirements (Advanced)
SITRANS P410 - Accessories/Spare parts
■ Dimensional drawings
60
30
25
12,5
25
30
Ø9
6
60
R30
12,5
3
134
21
105
120
52,5
72
16,5
R30
3
115
Ø11
72
Mounting bracket for SITRANS P410 gauge pressure-transmitters, dimensions in mm
mounting bracket material: Sheet-steel Mat. No. 1.0330, chrome-plated, or stainless steel Mat. No. 1.4301 (304)
38
27
54
20,65
R30
41,3
27
20,65
R6,5
Ø20
3
41,3
54
134
21
105
120
52,5
72
16,5
R30
3
115
Ø11
72
Mounting bracket for SITRANS P410 differential pressure transmitter, dimensions in mm
mounting bracket material: Sheet-steel Mat. No. 1.0330, chrome-plated, or stainless steel Mat. No. 1.4301 (304)
Siemens FI 01 · 2016