SITRANS FCT030 Transmitter Catalog Specification Sheet

© Siemens AG 2016
Flow Measurement
SITRANS F C
Transmitter SITRANS FCT030
• Food & Beverage: dairy products, beer, wine, soft drinks,
°Brix/°Plato, fruit juices and pulps, bottling, CO2 dosing,
CIP/SIP-liquids, mixture recipe control
• Automotive: fuel injection nozzle & pump testing, filling of AC
units, engine consumption
• Oil & Gas: filling of gas bottles, furnace control, test separators
• Hydrocarbon processing: oil refining, derivatives manufacturing, polymerisation
• Water & Waste Water: dosing of chemicals for water treatment
■ Overview
The multiple outputs and bus communication mean that all of the
process information can be read either instantaneously (10 ms
update) or periodically as plant operation requires.
■ Benefits
FCT030 is based on the latest developments within digital signal
processing technology – engineered for high measuring performance, fast response to step changes in flow, fast dosing applications, high immunity against process noise, easy to install
commission and maintain.
The FCT030 transmitter delivers true multi-parameter measurements i.e. massflow, volumeflow, corrected volumeflow, density,
temperature and fraction.
The FCT030 IP67 transmitter can be remote connected or compact mounted with all sensors of type FCS400, sizes DN 15 to
DN 80.
Fraction
The transmitter FCT030 can be set up at works to measure and
report various fraction concentrations of two-part mixtures or
solutions. Where a discrete relationship exists between concentration and density at particular temperatures a calculation is
performed and the percentage concentration by volume or
mass of Part A or Part B (100 % minus Part A) is measured. For
solutions and some mixtures the total mass, or dry weight, is also
available.
In some industries, a selection of standard density scales has
been adopted to represent the density or relative density of the
process fluid.
If "Standard fractions" option is chosen at ordering, the following
fraction or standard density scales can be selected in the setup
menu:
• API number
• Balling
• °Baumé light
• °Baumé heavy
• °Brix
• °Oeschlé°
• Plato
• Specific Gravity
• °Twaddell
• %HFCS42
• %HFCS55
• %HFCS90
• Ethanol-Water 0 % to 20 %
• Ethanol-Water 15 % to 35 %
• Ethanol-Water 30 % to 55 %
• Ethanol-Water 50 % to 100 %
■ Application
SITRANS FC430 mass flowmeters are suitable for applications
within the entire process industry where there is a demand for
accurate flow measurement. The meter is capable of measuring
both liquid and gas flow.
Coriolis flowmeters can be applied in all industries, such as:
• Chemical & Pharma: detergents, bulk chemicals, acids, alkalis, paint mixing systems, solvents and resins, pharmaceuticals, blood products, vaccines, insulin production
Flow calculation and measurement
• Dedicated mass flow calculation with DSP technology
• Fast dosing and flow step response with maximum 10 ms response time.
• 100 Hz update rate to all outputs
• Maximum data age from pickup to output is 20 ms (two update
cycles)
• Independent low flow cut-off settings for mass and volume
flowrates
• Automatic zero-point adjustment on command from discrete
input or host system
• Empty pipe monitoring
Operation and display
• User-configurable operation display
- Full graphical display 240 x 160 pixels with up to 6 programmable views
- Self-explaining alarm handling/log in clear text
- Help text for all parameters appears automatically in the configuration menu
- Keypad can be used for controlling dosing as start/stop/
hold/reset
• SensorFlash technology stores production specific system
documentation and provides removable memory of all flowmeter setups and functions
- Calibration certificates
- Pressure and material test certificates (as ordered)
- Non-volatile memory backup of operational data
- Transfer of user configuration to other flowmeters
Alarms and safety
• Advanced diagnosis and service menu enhances troubleshooting and meter validation
• Configurable upper and lower alarm and warning limits for all
process values
• Alarm handling can be selected between Siemens and
NAMUR standard configurations
• Designed from the ground up and certified for integrated
safety in accordance with IEC 61508 and IEC 61511.
- SIL 2 (single-channel operation)
- SIL 3 (dual-channel operation)
Unlike many systems which are certified in practice, the
SITRANS FC430 system is certified in design, which is a
higher qualification and more robust for secure implementation of safety systems.
Outputs and control
• Built-in dosing controller with compensation and monitoring
comprising 3 built-in totalizers
• Multi-parameter outputs, individually configurable for massflow, volumeflow, corrected volumeflow, density, temperature
or fraction flow such as °Brix or °Plato
Siemens FI 01 · 2016
3/175
3
© Siemens AG 2016
Flow Measurement
SITRANS F C
Transmitter SITRANS FCT030
Up to four I/O channels are configured as follows:
SensorFlash
Channel 1
SensorFlash is a standard, 1 GByte micro SD card with the ability
to be updated by PC. It is supplied with each sensor with the
complete set of certification documents including calibration report. Material, pressure test, factory conformance certificates
are optional at ordering.
Channel 1 is 4 to 20 mA analog output with HART 7.2 which can
be validated and setup for safety critical applications (SIL 2).
The current signal can be configured for massflow, volumeflow
or density.
Channel 2
3
Channel 2 is a signal output which can be freely configured for
any process variable.
• Analog current (0/4 to 20 mA)
• 3 stage analog valve dosing control
• Frequency or pulse
• Discrete one or two-valve dosing control in combination with
channel 3 or 4
• Operational and alarm status
Channels 3 and 4
Channels 3 and 4 can be ordered with signal (freely configured
for any process variable) or relay outputs, or signal input.
Signal
Signal output can be user configured to:
• Analog current (0/4 to 20 mA)
• 3 stage analog valve dosing control
• Frequency or pulse
• Redundant frequency or pulse (linked to Channel 2)
• Discrete one or two-valve dosing control
• Operational and alarm status
Relay
Relay output(s) can be user configured to:
• Discrete one or two-valve dosing control
• Operation status including flow direction
• Alarm status
Signal input
Signal input can be user-configured for
• Dosing control
• Totalizer reset functions
• Force or freeze output(s)
• Inititate automatic zero point adjustment
Signal outputs and inputs are individually ordered as active or
passive.
During service and maintenance all outputs can be forced to a
preset value for simulation, verification or calibration purposes.
Approvals and certificates
The FC430 coriolis flowmeter program was designed from the
ground up to comply with or exceed the requirements of international standards and regulations.
■ Design
The transmitter SITRANS FCT030 is designed in an
IP67/NEMA 4X aluminum enclosure with corrosion resistant
coating. It can be remote connected or compact mounted with
an FCS400 sensor of size DN 15, DN 25, DN 50 or DN 80.
FCT030 is available as standard with one current, HART 7.2 output and can be ordered with additional input/output functions.
The transmitter has a modular design with discrete, replaceable
electronic modules and connection boards to maintain separation between functions and facilitate field service. All modules
are fully traceable and their provenance is included in the transmitter setup.
3/176
Siemens FI 01 · 2016
The Siemens SensorFlash memory unit offers the following features and benefits:
• Automatically program any similar transmitter in seconds to
the operation standard
• Transmitter replacement in less than 5 minutes
• True "plug & play" provided by integrated cross-checking data
consistency and HW/SW version verification
• Permanent database of operational and functional information
from the moment that the flowmeter is switched on
• New firmware updates can be downloaded from the SIEMENS
internet portal for Product Support and placed onto SensorFlash (unmounted from the transmitter and inserted into a PC’s
SD card slot). The firmware is then inserted into the existing
flowmeter and the complete system upgraded.
■ Function
The following functions are available:
• Mass flowrate, volume flowrate, density, process temperature,
fraction flow
• Up to four output/input channels selected at ordering
• Outputs can be individually configured with mass, volume,
density etc.
• Three built-in totalizers which can count positive, negative or
net flows
• Low flow cut-off, adjustable
• Density cut-off or empty pipe cut-off, adjustable
• Flow direction adjustable
• Alarm system consisting of alarm-log, alarm pending menu
• Internal data logger is updated each 10 minutes with operational data such as system health, totalizer values, all configurations and data needed for custody transfer requirements to
OIML R 117 and NTEP
• Display of operating time with real-time clock. Daylight saving
time is not implemented
• Uni/bidirectional flow measurement
• Flowrate outputs are freely configurable between maximum
negative and maximum positive flows according to the sensor
capacity
• Limit switches programmable for flow, density, temperature or
fraction process values. Limit points can be graded as warning and alarm for values both above and below nominal process conditions
• Process noise filter for optimization of measurement performance under non-ideal application conditions. 5-stage pumping filter compensates for flow fluctuations caused by e.g. single acting piston pumps
• Full dosing controller with 5 user-configurable recipes
• Automatic zero adjustment menu, with zero point evaluation
display
• Full service menu for effective and straight forward application
and meter troubleshooting
• Precise temperature measurement ensures optimum accuracy on massflow, density and fraction flow.
• Fraction flow computation is based on a 5th-order algorithm
matching known applications. All standard fraction calculations fit within 0.1% of the true value.
© Siemens AG 2016
Flow Measurement
SITRANS F C
Transmitter SITRANS FCT030
■ Technical specifications
Process media
• Fluid Group 1 (suitable for
dangerous fluids)
• Aggregate state: Paste/light
slurry, liquid and gas
Number of process variables
7
Measurement of
• Mass flow
• Volume flow
Ambient temperature
Operation
• Transmitter
-40 ... +60 °C (-40 ... +140 °F),
(humidity max. 95 %)
• Display
-20 ... +60 °C (-4 ... +140 °F)
Storage
• Transmitter
-40 ... +70 °C (-40 ... +158 °F)
(Humidity max. 95 %)
• Process media temperature
• Display
-20 ... +70 °C (-4 ... +158 °F)
• Corrected volume flow
Communication
HART 7.2
• Reference density
Enclosure
• Density
• Fraction A flow
Material
Aluminum
• Fraction B flow
Rating
IP67/NEMA 4X to IEC 529 and
DIN 40050 (1 mH2O for 30 min.)
Mechanical load
18 ... 400 Hz random,
3.17 g RMS, in all directions
• Fraction A %
• Fraction B %
Current output
Supply voltage
Current
0 ... 20 mA or 4 ... 20 mA
(Channel 1 only 4 ... 20 mA)
Load
< 500  per channel
Time constant
0 ... 100 s adjustable
Digital output1)
Supply
20 ... 27 V DC ± 10%;
100 ... 240 V AC ± 10 %,
47 ... 63 Hz
Fluctuation
No limit
Power consumption
7.5 W/15 VA
Pulse
41.6 µs ... 5 s pulse duration
EMC performance
Frequency
0 ... 10 kHz, 50 % duty cycle,
120 % overscale provision
Emission
EN 55011/CISPR-11 (Class A)
Immunity
EN/IEC 61236-1 (Industry)
Time constant
0 ... 100 s adjustable
NAMUR
Active
0 ... 24 V DC, 110 mA,
short-circuit-protected
Passive
3 ... 30 V DC, max. 110 mA
Within the value limits according
to "General requirements" with
error criteria A in accordance with
NE 21
Relay
Type
Change-over voltage-free relay
contact
Load
30 V AC/100 mA
Functions
Alarm level, alarm number, limit,
flow direction
Environment
Environmental conditions acc. to
IEC/EN/UL 61010-1
• Altitude up to 2000 m
• Pollution degree 2
Maintenance
The flowmeter has a built-in error
log/pending menu which should
be inspected on a regular basis.
Cable glands
Cable gland are available in
Nylon, Nickel plated brass or
stainless steel (316L/W1.4404) in
the following dimensions:
• M20
• ½" NPT
Cable
Standard industrial signal cable
up to 200 m long with 2 x
screened pairs or 4-wire overall
screen can be laid between the
sensor and transmitter. Siemens
offers cables in a selection of precut lengths and prepared for
either gland or plug connection.
Digital input
Voltage
15 ... 30 V DC (2 ... 15 mA)
Functionality
Start/stop/hold/continue dosing,
reset totalizer 1 and 2, force output, freeze output
Galvanic isolation
All inputs and outputs are galvanically isolated, isolation voltage
500 V.
Cut-off
Low-flow
0 ... 9.9 % of maximum flow
Limit function
Mass flow, volume flow, fraction,
density, sensor temperature
Totalizer
Three eight-digit counters for forward, net or reverse flow
Display
• Background illumination with
alphanumerical text, 3  20
characters to indicate flow rate,
totalized values, settings and
faults.
• Time constant as current
output 1
• Reverse flow indicated by
negative sign
Zero point adjustment
Via keypad or remote via digital
input
1)
With 300  internal impedance. For coil switching use the passive output
option.
Siemens FI 01 · 2016
3/177
3
© Siemens AG 2016
Flow Measurement
SITRANS F C
Transmitter SITRANS FCT030
Approvals
Certificates
Hazardous area
• ATEX, IECEx, EAC Ex, FM, CSA,
NEPSI, INMETRO
Safety Integration Level (applies
only to compact versions)
- Zone 1:
Ex d e ia [ia Ga] IIC T6 Gb
- Zone 21:
Ex tb [ia Da] IIIC T85°C Db
CE mark
• Pressure equipment
• Low voltage directive
Pressure equipment
• RoHS
Regional certifications
• C-TICK (Australia and New
Zealand EMC)
• NTEP for US and Canada
• EAC (Belarus, Armenia,
Kazakhstan, Russia)
• PED
• KCC (South Korea)
• CRN
Hygienic applications
• EHEDG for hygienic variant sensors
• 3A for hygienic variant sensors
• External cleanability satisfies
EHEDG and 3A rules
■ Dimensional drawings
200 (7.87)
118 (4.65)
155 (6.1)
250 (9.84)
SITRANS FCT030, compact version, dimensions in mm (inch)
307 (12.09)
216 (8.5)
3
• WEEE
- Class I+II+III, Div. 1 (US only):
Grp. A, B, C, D, E, F, G, H
• OIML R 117 type approval to a
wide variety of liquids other than
water
• SIL 2 for hardware
• SIL 3 for redundant hardware
systems
• FM
Custody transfer
• SIL 3 for software
SITRANS FCT030, remote version, dimensions in mm (inch)
3/178
Siemens FI 01 · 2016
200 (7.87)
© Siemens AG 2016
Flow Measurement
SITRANS F C
Flowmeter - Accessories/Spare parts
Accessories
Description
Article No.
Description
CT plug
Tamper cover for CT locking. Fits over the M12 plug
at both sensor and transmitter ends of the remote system cable (2 pcs.)
A5E31478498
Standard cable (Ex) with
M12 plugs, PO insulation
and PUR sleeve, blue,
-40 ... +80 °C
(-40 ... +176 °F)
Bag of glands (metric) in
black plastic1)
A5E03907414
Bag of glands, (metric) in
gray plastic Ex e/i1)
A5E03907424
Bag of glands (metric) in
AISI 316 SS Ex e/i1)
A5E03907429
Bag of glands (metric) in
Ni-plated brass Ex e/i1)
A5E03907430
Bag of glands (NPT) in
black plastic2)
Bag of glands (NPT) in gray
plastic Ex e/i2)
Article No.
•5m
A5E03914929
• 10 m
A5E03914962
• 25 m
A5E03914995
• 50 m
A5E03915004
• 75 m
A5E03915074
• 150 m
A5E03915088
3
Standard cable (Ex) for termination, PO insulation and
PUR sleeve, blue,
-40 ... +80 °C
(-40 ... +176 °F)
A5E03907435
A5E03907451
Bag of glands (NPT) in
AISI 316 SS Ex e/i2)
A5E03907467
Bag of glands (NPT) in
Ni-plated brass Ex e/i2)
A5E03907473
Standard cable (non-Ex)
with M12 plugs, PO insulation and PUR sleeve, gray,
-40 ... +80 °C
(-40 ... +176 °F)
• 5 m (16.4 ft)
A5E03914805
• 10 m (32.8 ft)
A5E03914850
• 25 m (82 ft)
A5E03914853
• 50 m (164 ft)
A5E03914859
• 75 m (246 ft)
A5E03914861
• 150 m (492 ft)
A5E03914874
•5m
A5E03914945
• 10 m
A5E03914973
• 25 m
A5E03914984
• 50 m
A5E03915015
• 75 m
A5E03915057
• 150 m
A5E03915100
Suitcase for comprehensive sales support and
training for FC430
It comes in a special suitcase with a fan implemented that allows the
flowmeter to demonstrate
airflow.
A5E31467598
Suitcase for comprehensive sales support and
training for FC410.
It comes in a special suitcase with an S7-1200 PLC
and HMI touch-screen display. The operating code is
open-source and can be
copied to customers to
assist with system integration.
A5E33219071
Service toolkit for field maintenance of transmitter and
sensor components. Contains all hand tools necessary for maintenance. Other
tools may be required for
installation.
A5E03722877
Standard cable (non-Ex) for
termination, PO insulation
and PUR sleeve, gray,
-40 ... +80 °C
(-40 ... +176 °F)
• 5 m (16.4 ft)
A5E03914833
• 10 m (32.8 ft)
A5E03914849
• 25 m (82 ft)
A5E03914854
• 50 m (164 ft)
A5E03914856
• 75 m (246 ft)
A5E03914864
• 150 m (492 ft)
A5E03914873
Siemens FI 01 · 2016
3/179
© Siemens AG 2016
Flow Measurement
SITRANS F C
Flowmeter - Accessories/Spare parts
Article No.
Description
Heating Jacket, indoor use,
0 ... 200 °C (32 ... 392 °F)
max. temperature. Complete
with 5 m (16.4 ft) high temperature cable fitted. Dedicated plug connection to
included controller
Description
Dimension
Article No.
DN 10
FDK:085U1016
DN 15
FDK:085U1017
DN 25
FDK:085U1019
DN 32
FDK:085U1020
DN 40
FDK:085U1021
DN 50
FDK:085U1022
DN 65
FDK:085U1023
25 mm
FDK:085U1029
40 mm
FDK:085U1031
50 mm
FDK:085U1032
DN 10
FDK:085U1006
DN 15
FDK:085U1007
DN 25
FDK:085U1009
DN 32
FDK:085U1010
DN 40
FDK:085U1011
DN 50
FDK:085U1012
DN 65
FDK:085U1013
Mating parts for hygienic fittings
DIN 11851
Includes:
• 2 unions
• 2 mating parts (for welding in)
• 2 EPDM gaskets
• 230 V AC
3
- DN 15 electric
A5E33035287
- DN 25 electric
A5E33035324
- DN 50 electric
A5E33035325
- DN 80 electric
A5E33035336
• 115 V AC
- DN 15 electric
A5E32877520
- DN 25 electric
A5E32877556
- DN 50 electric
A5E32877557
- DN 80 electric
A5E32877561
Heating jacket controller,
IP65. Digital display for
0 ... 200 °C (32 .. 392 °F)
control setpoint
• 230 V AC
A5E03839193
• 115 V AC
A5E03839194
1)
2 pcs M20; 1 pce M25 with single and dual cable inserts
2)
2 pcs ½" NPT; 1 pce ½" NPT with single and dual cable inserts
Mating parts for hygienic clamp
ISO 2852
Includes:
• 2 clamps
• 2 mating parts
• 2 EPDM gaskets
2 EPDM gaskets with collar for
mounting set DIN 11851
3/180
Siemens FI 01 · 2016
© Siemens AG 2016
Flow Measurement
SITRANS F C
Flowmeter - Accessories/Spare parts
Spare parts - transmitter FCT030
Article No.
Description
Article No.
Display and keypad assembly with firewire connection
to the transmitter module1)
A5E03548971
Mounting bracket - FCT030;
in painted aluminum for
pipe or wall mounting of
transmitter FCT030 remote
version. Including lock ring,
pressure pads and seal cap
A5E03906091
Sensor interface (Compact).
Front end flow calculator and
process detection. SIL 3
approved1)
A5E03549142
M12 option for sensor housing in stainless steel. Prewired and potted to replace
M12 socket in DSL housing
A5E03906095
A5E03549098
M12 option - remote - in
painted aluminum. Prewired and potted replacement M12 connection for
FCT030 transmitter remote
version
A5E03906104
Sensor interface (Remote);
barrier unit for high speed
digital communication and
Ex ib power supply to
remote front end
DSL module
Remote terminal house M20
A5E03906112
Display lid in painted aluminum with Ex glass plate and
o-ring seal
A5E03549344
Remote terminal house NPT - in painted aluminum
for sensor cable termination
at FCT030 transmitter
remote version. Pre-wired
and potted
A5E03906130
Transmitter cassette (active)
with SIL approved
4 ... 20 mA output and
HART 7.21)
A5E03549357
Transmitter cassette (passive) with SIL approved
4 ... 20 mA output and
HART 7.21)
A5E03549383
Bag of loose spare parts;
including cable strain relief
components, mounting tool,
seals and gasket, assorted
screws and washers, hex
cap nut, blind plugs, and
o-rings
A5E03549396
Power supply
240 V AC, 47 ... 63 Hz
24 ... 90 V DC
A5E03549413
Blind lid in painted aluminum with o-ring seal
A5E03549429
Description
3
Spare parts - sensor FCS400
I/O assembly
Advise Order code
F00 to F97 from Selection
and Ordering data2)
A5E03939114
SensorFlash
(micro SD card)
A5E03915258
Description
Article No.
Blind lid in painted aluminum with o-ring seal
A5E03549295
Frontend cassette
Spare part frontend
cassette for remote version
of FC430 and cassette for
FC4101)
A5E03549191
Sensor housing metric
A5E03549313
Sensor housing NPT in
painted aluminum
A5E03906080
Bag of loose parts for sensor; including cable strain
relief components, washer,
seals, o-rings, and assorted
screws
A5E03549324
1)
The system firmware bundle must be stated in the "Remark" field when
ordering, to ensure compatibility of the system. The FW revision is found
on the product label for FC430 and FC410.
Further for FC430 the firmware bundle can be found in the local display in
the menu items 3.1.10. e.g. "2.02.01-02"
2)
The I/O configuration must be stated in the "Remark" field. The I/O configuration is found in the F option of the ordering code. e.g. code “F40” for
ordering Ch2 Active Current/Freq/Pulse, Ch3 Active Current/Freq/Pulse,
Ch4 Active Input