NX-series System Unit NX-PD/PF/PC/TBX CSM_NX-PD_PF_PC_TBX_DS_E_3_5 Power Supply Unit, Power Connection Unit, and FG Terminal Expansion Unit for NX-series • Provide stabilised power to the internal circuits of NX I/O Units. • Feed additional power to I/O circuits of NX I/O Units. • Provide extra terminals for sensor/actuator power and termination of shielded cabling. Features • • • • • • • • Units to feed in additional Unit power and I/O power to an NX-series remote I/O terminal. Screwless clamp terminal block significantly reduces wiring work. Space-saving 12 mm wide units. The NX Unit Power Supply Unit allows expansion of the I/O configuration beyond the maximum power supply capacity of the EtherCAT Coupler The I/O Power Supply Unit is used when the total allowed I/O current per feed terminal is exceeded, or to split I/O power into groups. The I/O Power Connection Unit can be used as an additional power supply terminal for connected sensors and actuators. The FG Terminal Expansion Unit can be used as ground terminal for wire shields. The screwless terminal block is detachable for easy commissioning and maintenance. System Configuration Sysmac Studio Support Software EtherCAT master* NJ-series CPU Unit Connection to peripheral USB port or built-in EtherNet/IP port on NJ-series CPU Unit Built-in EtherCAT port Sysmac Studio Support Software ●EtherCAT Slave Terminal Communications cable Ethernet cables Peripheral USB port. NX Series EtherCAT Coupler Unit NX-ECC@@@ Connection to peripheral USB port on EtherCAT Coupler Unit NX Units End Cover * OMRON CJ1W-NC@81/@82 Position Control Units cannot be connected to the EtherCAT Slave Terminal even though they support EtherCAT. Sysmac® is a trademark or registered trademark of OMRON Corporation in Japan and other countries for OMRON factory automation products. EtherCAT® is a registered trademark of Beckhoff Automation GmbH for their patented technology. Other company names and product names in this document are the trademarks or registered trademarks of their respective companies. 1 NX-PD/PF/PC/TBX Power Supply Systems Communications Coupler Unit Unit power supply terminals NX Unit NX Unit Additional NX Unit power supply Power Supply Unit NX Unit power supply Internal power supply circuit The I/O power supply is separated. The I/O power supply is not separated. NX bus I/O power supply To external devices I/O power supply terminals Unit power supply (24 VDC) To external devices External External input input device device Additional I/O I/O Power To external power Supply devices supply Unit End Cover I/O power supply (Supply from external source) Note: Supply the Unit power and the I/O power from different power supplies. If you supply power from the same power supply the galvanic separation between the bus system and the I/O circuits is no longer effective. Noise generated in the I/O circuits may cause malfunctions in the internal circuits of the units. 2 NX-PD/PF/PC/TBX Ordering Information International Standards • The standards are abbreviated as follows: U: UL, U1: UL(Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, CE: EC Directives, and KC: KC Registration. • Contact your OMRON representative for further details and applicable conditions for these standards. Additional NX Unit Power Supply Unit Unit type Product Name Power supply voltage NX Bus power supply capacity NX Unit power consumption Model Standards Additional NX Unit Power Supply Unit NX Series System Unit 24 VDC (20.4 to 28.8 VDC) 10 W max. 0.45 W max. NX-PD1000 UC1, N, L, CE, KC Additional I/O Power Supply Unit Unit type Product Name Power supply voltage Additional I/O Power Supply Unit NX Series System Unit I/O power feed maximum current NX Unit power consumption 4A 5 to 24 VDC (4.5 to 28.8 VDC) Model Standards NX-PF0630 UC1, N, L, CE, KC 0.45 W max. 10 A NX-PF0730 I/O Power Supply Connection Unit Unit type Product Name I/O Power Supply Connection Unit NX Series System Unit Number of I/O power terminals Current capacity of I/O power terminal NX Unit power consumption Model Standards IOG: 16 terminals 4 A/terminal max. 0.45 W max. NX-PC0010 UC1, N, L, CE, KC IOV: 16 terminals 4 A/terminal max. 0.45 W max. NX-PC0020 UC1, N, L, CE, KC IOV:8 terminals IOG:8 terminals 4 A/terminal max. 0.45 W max. NX-PC0030 UC1, N, L, CE, KC Shield Connection Unit Unit type Product Name Number of shield terminals NX Unit power consumption Model Standards Shield Connection Unit NX Series System Unit 14 terminals (The following two terminals are functional ground terminals.) 0.45 W max. NX-TBX01 UC1, N, L, CE, KC 3 NX-PD/PF/PC/TBX Optional Products Product Name Unit/Terminal Block Coding Pins Specification Model For 10 Units (Terminal Block: 30 pins, Unit: 30 pins) Standards − NX-AUX02 Specification Product Name No. of terminals Terminal number indications 8 Terminal Block A/B 16 Ground terminal mark Terminal current capacity Model None NX-TBA082 Provided NX-TBC082 None 10 A Provided Standards NX-TBA162 --- NX-TBC162 Accessories There are no accessories. General Specification Item Specification Enclosure Mounted in a panel Grounding method Ground to 100 Ω or less Ambient operating temperature 0 to 55°C Ambient operating humidity 10% to 95% (with no condensation or icing) Atmosphere Must be free from corrosive gases. Ambient storage temperature −25 to 70°C (with no condensation or icing) Altitude 2,000 m max. Pollution degree 2 or less: Conforms to JIS B3502 and IEC 61131-2. Operating Noise immunity environment Overvoltage category 2 kV on power supply line (Conforms to IEC61000-4-4.) Category II: Conforms to JIS B3502 and IEC 61131-2. EMC immunity level Zone B Vibration resistance Conforms to IEC 60068-2-6. 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s2, 100 min each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) Shock resistance Conforms to IEC 60068-2-27. 147 m/s2, 3 times each in X, Y, and Z directions Applicable standards cULus: Listed UL508 and ANSI/ISA 12.12.01 EC: EN 61131-2 and C-Tick, KC Registration, NK, LR 4 NX-PD/PF/PC/TBX Specification Additional NX Unit Power Supply Unit NX-PD1000 Unit name Additional NX Unit Power Supply Unit Model NX-PD1000 External connection terminals Screwless push-in terminal block (8 terminals) Power supply voltage 24 VDC (20.4 to 28.8 VDC) NX Bus power supply capacity 10 W max. (Refer to Installation orientation and restrictions for details.) NX Unit power supply efficiency 70% Unwired terminal current capacity 4 A max. (Including the current of through-wiring) Dimensions 12 (W) × 100 (H) 71 × (D) Isolation method No-isolation Insulation resistance 20 MΩ min. between isolated circuits (at 100 VDC) Dielectric strength 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. NX Unit power consumption 0.45 W max. I/O current consumption No consumption Weight 65 g max. + + Terminal block − (Functional ground terminal) − (Functional ground terminal) Circuit layout No-isolation power supply circuit UNIT PWR LED NX Unit power supply + NX Unit power supply + Internal circuits NX bus connector (left) NX Unit power supply - NX Unit power supply − I/O power supply + I/O power supply + I/O power supply - I/O power supply - NX bus connector (right) DIN Track contact plate (Unit track surface) 5 NX-PD/PF/PC/TBX Installation orientation: Possible in 6 orientations. Restrictions: • For upright installation For 10 W output, 40ºC Output power (W) 12 10 For 8.5 W output, 55ºC 8 6 4 2 0 0 Installation orientation and restrictions 10 20 30 40 45 50 55 60 Ambient operating temparature (ºC) • For any installation other than upright For 10 W output, 40ºC Output power (W) 12 10 8 For 6.0 W output, 55ºC 6 4 2 0 0 10 20 30 40 45 50 55 60 Ambient operating temperature (ºC) Additional NX Unit Power Supply Unit NX-PD1000 A1 24 VDC Unit power supply Terminal connection diagram Through-wiring for surplus terminals*1 B1 UV UV UG UG NC*2 NC*2 Ground of 100 Ω or less A8 B8 *1. You can use the unwired terminals of the Unit power supply terminals (UV/UG) for through-wiring of the Additional NX Unit Power Supply Unit or the Unit power supply terminals on the EtherCAT Coupler Unit. *2. The NC terminal is not connected to the internal circuit. 6 NX-PD/PF/PC/TBX Additional I/O Power Supply Units NX-PF0@30 Unit name Additional I/O Power Supply Unit Model NX-PF0630 External connection terminals Screwless push-in terminal block (8 terminals) Power supply voltage 5 to 24 VDC (4.5 to 28.8 VDC)* I/O power supply maximum current 4A 10 A Current capacity of I/O power supply terminal 4 A max. 10 A max. Dimensions 12 (W) × 100 (H) 71 × (D) Isolation method No-isolation Insulation resistance 20 MΩ min. between isolated circuits (at 100 VDC) Dielectric strength 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. NX Unit power consumption 0.45 W max. I/O current consumption 10 mA max. Weight 65 g max. IOV IOV … NX-PF0730 IOV IOG IOG … Terminal block IOG Circuit layout NX Unit power supply + NX Unit power supply + Internal circuits NX bus connector (left) NX Unit power supply - NX Unit power supply - I/O power supply + I/O power supply + I/O power supply - I/O power supply - NX bus connector (right) IO PWR Indicator Installation orientation and restrictions Installation orientation: Possible in 6 orientations. Restrictions: No restrictions Additional I/O Power Supply Unit NX-PF0630 A1 B1 IOV DC Input Unit A1 IOV 24 VDC Terminal connection diagram IOG A8 Overload/low voltage detection IOG IOV IOV IOG IOG B8 A8 B1 0 1 IOV IOV IOG IOG 2 3 IOV IOV IOG IOG Two-wire type Three-wire type B8 Not supported Protective function Not supported. * Use an output voltage that is appropriate for the I/O circuits of the NX Units and the connected external devices. 7 NX-PD/PF/PC/TBX I/O Power Supply Connection Unit IOG terminal type NX-PC0010 Unit name I/O Power Supply Connection Unit Model NX-PC0010 External connection terminals Screwless push-in terminal block (16 terminals) Number of I/O power supply terminals IOG: 16 terminals Current capacity of I/O power supply terminal 4 A/terminal max. Dimensions 12 (W) × 100 (H) 71 ×(D) Isolation method No-isolation Insulation resistance 20 MΩ min. between isolated circuits (at 100 VDC) Dielectric strength 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. NX Unit power consumption 0.45 W max. I/O current consumption No consumption Weight 65 g max. IOG IOG … Terminal block IOG Circuit layout NX Unit power supply + NX Unit power supply + Internal circuits NX bus NX Unit power supply − connector (left) I/O power supply + NX Unit power supply − NX bus connector (right) I/O power supply + I/O power supply − Installation orientation and restrictions I/O power supply − Installation orientation: Possible in 6 orientations. Restrictions: No restrictions I/O Power Supply Connection Unit NX-PC0010 B1 A1 IOG IOG Terminal connection diagram A8 DC Input Unit or Transistor Output Unit A1 B1 0 1 IOV IOV IOG IOG IOG IOG 2 3 IOG IOG IOV IOV IOG IOG 4 5 IOG IOG IOV IOV IOG IOG 6 7 IOG IOG IOV IOV B8 A8 Three-wire type B8 8 NX-PD/PF/PC/TBX I/O Power Supply Connection Unit IOV terminal type NX-PC0020 Unit name I/O Power Supply Connection Unit Model NX-PC0020 External connection terminals Screwless push-in terminal block (16 terminals) Number of I/O power supply terminals IOV: 16 terminals Current capacity of I/O power supply terminal 4 A/terminal max. Dimensions 12 (W) × 100 (H) 71 × (D) Isolation method No-isolation Isolation resistance 20 MΩ min. between isolated circuits (at 100 VDC) Dielectric strength 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. NX Unit power consumption 0.45 W max. I/O current consumption No consumption Weight 65 g max. … Terminal block IOV IOV IOV NX Unit power supply + Circuit layout NX bus connector (left) Installation orientation and restrictions NX Unit power supply + Internal circuits NX Unit power supply − I/O power supply + NX Unit power supply − NX bus connector I/O power supply + (right) I/O power supply − I/O power supply − Installation orientation: Possible in 6 orientations. Restrictions: No restrictions I/O Power Supply Connection Unit A1 NX-PC0020 B1 IOV IOV Terminal connection diagram A8 DC Input Unit or Transistor Output Unit A1 B1 0 1 IOV IOV IOG IOG IOV IOV 2 3 IOV IOV IOG IOG IOV IOV 4 5 IOV IOV IOG IOG IOV IOV 6 7 IOV IOV IOG IOG B8 A8 Three-wire type B8 9 NX-PD/PF/PC/TBX I/O Power Supply Connection Unit IOV/IOG terminal type NX-PC00300 Unit name I/O Power Supply Connection Unit Model NX-PC0030 External connection terminals Screwless push-in terminal block (16 terminals) Number of I/O power supply terminals IOV: 8 terminals IOG: 8 terminals Current capacity of I/O power supply terminal 4 A/terminal max. Dimensions 12 (W) × 100 (H) 71 × (D) Isolation method No-isolation Insulation resistance 20 MΩ min. between isolated circuits (at 100 VDC) Dielectric strength 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. NX Unit power consumption 0.45 W max. I/O current consumption No consumption Weight 65 g max. … IOV IOV IOV Terminal block Circuit layout … IOG IOG IOG NX Unit power supply + NX Unit power supply + Internal circuits NX bus NX Unit power supply − connector (left) I/O power supply + NX Unit power supply − I/O power supply + I/O power supply − Installation orientation and restrictions NX bus connector (right) I/O power supply − Installation orientation: Possible in 6 orientations. Restrictions: No restrictions I/O Power Supply Connection Unit NX-PC0030 A1 Terminal connection diagram A8 B1 DC Input Unit or Transistor Output Unit A1 IOV IOV 0 1 IOG IOG 2 3 IOV IOV 4 5 IOG IOG 6 7 IOV IOV 8 9 IOG IOG 10 11 IOV IOV 12 13 IOG IOG 14 15 B8 A8 Three-wire type B1 B8 10 NX-PD/PF/PC/TBX Shield Connection Unit NX-TBX01 Shield Connection Unit Model NX-TBX01 External connection terminals Screwless push-in terminal block (16 terminals) Number of shield terminals 14 terminals (The following two terminals are functional ground terminals.) Dimensions 12 (W) × 100 (H) 71 × (D) Isolation method Isolation between the SHLD functional ground terminal, and internal circuit: No-isolation Insulation resistance 20 MΩ min. between isolated circuits (at 100 VDC) Dielectric strength 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. NX Unit power consumption 0.45 W max. I/O current consumption No consumption Weight 65 g max. SHLD terminal SHLD terminal Terminal block … Unit name SHLD terminal (Functional ground terminal) (Functional ground terminal) NX Unit power supply + Circuit layout NX bus connector (left) NX Unit power supply + Internal circuits NX Unit power supply − NX Unit power supply − I/O power supply + I/O power supply + I/O power supply − I/O power supply − NX bus connector (right) DIN Track contact plate (Unit back surface) Installation orientation and restrictions Installation orientation: Possible in 6 orientations. Restrictions: No restrictions Shield Connection Unit NX-TBX01 A1 Terminal connection diagram Incremental Encoder Input Unit (Open collector input) B1 A1 A8 SHLD A B SHLD SHLD Z NC SHLD SHLD IOV IOV SHLD SHLD IOG IOG SHLD SHLD I0 I1 SHLD SHLD B8 A8 Rotary Encoder B1 SHLD SHLD SHLD Shield I2 NC IOV IOV IOG IOG B8 Ground of 100 Ω or less 11 NX-PD/PF/PC/TBX Version Information NX Units Model Corresponding unit versions/versions * Unit Version EtherCAT Coupler Units NX-ECC20@ NJ/NX-series CPU Units NX-PD1000 Ver.1.06 or higher NX-PF0630 Ver.1.08 or higher NX-PF0730 NX-PC0020 NX-PC0010 NX-PC0030 Sysmac Studio Ver.1.0 Ver.1.0 or later Ver.1.05 or later Ver.1.06 or higher NX-TBX01 * Some Units do not have all of the versions given in the above table. If a Unit does not have the specified version, support is provided by the oldest available version after the specified version. Refer to the user’s manuals for the specific Units for the relation between models and versions. 12 NX-PD/PF/PC/TBX External Interface Additional NX Unit Power Supply Unit, Additional I/O Power Supply Unit, I/O Power Supply Connection Unit, and Shield Connection Unit NX-PD1000/NX-PF0@30/NX-PC00@0/NX-TBX01 (B) (C) (A) Symbol Name Function (A) NX bus connector This connector is used to connect each Unit. (B) Indicators The indicators show the current operating status of the Unit. (C) Terminal block The terminal block is used to connect external devices. The number of terminals depends on the type of Unit. Terminal Blocks (A) (B) A1 B1 A1 B1 A2 B2 A2 B2 A3 B3 A3 B3 A4 B4 A4 B4 A5 B5 A5 B5 A6 B6 A6 B6 A7 B7 A7 B7 A8 B8 A8 B8 (C) 8-terminal type Symbol 16-terminal type Name Function Terminal numbers for which A and B indicate the column, and 1 to 8 indicate the line are displayed. The terminal number is a combination of column and line, so A1 to A8 and B1 to B8 are displayed. The terminal number indications are the same regardless of the number of terminals on the terminal block. {A) Terminal number indications (B) Release holes Insert a flat-blade screwdriver into these holes to connect and remove the wires. (C) Terminal holes The wires are inserted into these holes. 13 NX-PD/PF/PC/TBX Applicable Terminal Blocks for Each Unit Model Unit model NX-PD1000 NX-PF0630 NX-PF0730 NX-PC@@@@ NX-TBX01 Model NX-TBC082 NX-TBA082 NX-TBA082 NX-TBA162 NX-TBC162 No. of terminals 8 8 8 16 16 Terminal Blocks Terminal number indications A/B A/B A/B A/B A/B Ground terminal mark Provided None None None Provided Terminal current capacity 10 A 10 A 10 A 10 A 10 A Applicable Wires Using Ferrules If you use ferrules, attach the twisted wires to them. Observe the application instructions for your ferrules for the wire stripping length when attaching ferrules. Always use plated one-pin ferrules. Do not use unplated ferrules or two-pin ferrules. The applicable ferrules, wires, and crimping tool are given in the following table. Terminal types Manufacturer Ferrule model Terminals other than ground terminals Applicable wire (mm2 (AWG)) 0.34 (#22) 0.5 (#20) Crimping tool Phoenix Contact AI0,34-8 Phoenix Contact (The figure in parentheses is the applicable wire size.) AI0,5-8 CRIMPFOX 6 (0.25 to 6 mm2, AWG 24 to 10) AI0,5-10 AI0,75-8 0.75 (#18) AI0,75-10 AI1,0-8 1.0 (#18) AI1,0-10 AI1,5-8 1.5 (#16) AI1,5-10 Ground terminals AI2,5-10 2.0 *1 Terminals other Weidmuller H0.14/12 0.14 (#26) Weidmueller (The figure in parentheses is the applicable wire size.) than ground PZ6 Roto (0.14 to 6 mm2, AWG 26 to 10) H0.25/12 0.25 (#24) terminals H0.34/12 0.34 (#22) H0.5/14 0.5 (#20) H0.5/16 H0.75/14 0.75 (#18) H0.75/16 H1.0/14 1.0 (#18) H1.0/16 H1.5/14 1.5 (#16) H1.5/16 *1. Some AWG 14 wires exceed 2.0 mm2 and cannot be used in the screwless clamping terminal block. When you use any ferrules other than those in the above table, crimp them to the twisted wires so that the following processed dimensions are achieved. 8 to 10 mm 1.6 mm max. (Terminals other than ground terminals) 2.4 mm max. (Terminals other than ground terminals) 2.7 mm max. (Ground terminals) 2.0 mm max. (Ground terminals) Using Twisted Wires/Solid Wires If you use the twisted wires or the solid wires, use the following table to determine the correct wire specifications. Wire type Conductor length Twisted wires Solid wire Wire size (stripping length) Classification Current capacity Plated Unplated Plated Unplated 2 A max. Possible Possible Possible Possible Greater than All terminals except 0.08 to 1.5 mm2 8 to 10 mm Possible *1 Not Not 2 A and 4 A or less AWG28 to 16 ground terminals Possible Possible Possible *1 Not Possible Greater than 4 A Ground terminals --Possible Possible Possible *2 Possible *2 2.0 mm2 9 to 10 mm *1. Secure wires to the screwless clamping terminal block. Refer to the Securing Wires in the USER'S MANUAL for how to secure wires. *2. With the NX-TB@@@1 Terminal Block, use twisted wires to connect the ground terminal. Do not use a solid wire. Terminals Conductor length (stripping length) <Additional Information> If more than 2 A will flow on the wires, use plated wires or use ferrules. 14 NX-PD/PF/PC/TBX Dimensions (Unit: mm) Additional NX Unit Power Supply Unit, Additional I/O Power Supply Unit, I/O Power Supply Connection Unit, and Shield Connection Unit NX-PD1000/NX-PF0@30/NX-PC00@0/NX-TBX01 ● Unit Only 14.1 12.0 0.55 1.5 104.5 100 1.5 65.2 71 80.1 ● With Cables Connected 100 71 Related Manuals Man. No W523 Model NX-PD1 @@@ NX-PF0 @@@ NX-PC0 @@@ NX-TBX @@@ Manual NX-series System Unit User’s Manual Application Learning how to use NXseries System Units Description The hardware and functions of the NX-series System Units are described. 15 Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions. 2016.4 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ (c)Copyright OMRON Corporation 2016 All Right Reserved.