CP-SNT 1000W Power Supply
The CP-SNT 1000W can deliver 24Vdc @ 40A
and is powered from 3 phase 360-480V. It is
ideally suited for applications where large
numbers of DC powered devices such as
contactors, valves, fans as well as PLCs and
interface devices are used. A high output surge
capability means that highly inductive loads can
be powered from this supply.
NEW
An internal cooling fan allows this power supply
to be mounted on horizontal or vertical 35mm
DIN rail. Like the CP-SNT 300W power supply it
also offers analog outputs representing output
voltage and current and internal temperature. For
redundancy it is possible to operate multiple
power supplies in parallel. It is also possible to
operate 2 units in parallel for increased power.
Features:
• 360-480Vac, 3 phase input for global operation
• 40A continuous output and 80A for 1 second
surge capability
• analog outputs
• parallel operation capability
• 1 form C (SPDT) fault relay
• chassis mountable (hardware included)
Catalog number: 791896 0324
Canada
Mexico
United States
W Interconnections Canada Inc.
W Interconnections, S.A. de C.V.
W Interconnections, Inc.
10 Spy Court
Ave Ingenieros Civiles #204
821 Southlake Blvd.
Markham, Ontario L3R 5H6
Conjunto Industrial Chachapa
Richmond, Virginia 23236
Telephone: (800) 268-4080
72990 Puebla, Pue. Mexico
Telephone: (800) 849-9343
Facsimile: (905) 475-2798
Telephone: (222) 286 62 47
Facsimile: (804) 379-2593
Email: [email protected]
Facsimile: (222) 286 62 42
Email: [email protected]
Website: www.weidmuller.ca
website: www.weidmuller.com.mx
Website: www.weidmuller.com
CP-SNT 1000W Power Supply
Input Voltage
Minimum 342Vac
Typical 480Vac +/- 10%, 50-60Hz, 3 phase
Maximum 528Vac
Input Current
At Minimum Vin 1.9Arms
At Typical Vin 1.4Arms
At Maximum Vin 1.3Arms
Input Protection
External Input Breaker
External Input Fuse
Inrush Current
Overvoltage
Surge Immunity L-L
L-G
6A, 3 pole 480Vac
6A, 480Vac Slow Blow
40A Maximum
Varistor
2KV
4KV
Switching Frequency
65kHz
Output
24Vdc
23-28Vdc
40A
70A
80A
1 second
60 seconds
10,000µF
Voltage Nominal
Voltage Adj. Range
Current nominal
Maximum Start-up Current
Current Surge
Current Surge Time
Surge Cycle Time
Max. Load Capacitance
Efficiency @ Max. Load
90%
Output Ripple
<20mVrms
Regulation
Load (10 - 100% load) 5%
Line 1%
Protection
Short Circuit
Over Voltage
Under Voltage
Over Temperature
Over Current
Hold Time
Auto restart
Vout > 30.5Vdc
Vout < 20Vdc
Vout heatsink temp. > 100 °C
43A typical @ 24V for >1 second
Temperature Range
Storage -40°C to +85°C
Operating -10°C to +50°C (Full Power)
Humidity
Storage 5 to 95%
Operating 20 to 85% non-condensing
Galvanic Isolation
Input to Output 3kVac
Input to Ground 1.5kVac
Output to Ground 500Vac
Wire Size
Dimensions (mm)
Input 22-12AWG (0.08 - 2.5mm2)
Output 22-6AWG (0.5 - 16mm2)
I/O 22-12AWG (0.08 - 2.5mm2)
Length x Width x Depth
8.35lbs (3.8kg)
Weight (kg)
Mounting
TS35 Rail or Chassis (hardware incld.)
Recommended Clearance Leave 4” (10cm) free space on
venting sides
Special Features
Cooling
Load Sharing
Redundancy
Fault Relay
Vout
Tout
Iout
Fan cooled
Maximum 2 units (see Note)
No maximum
Form C contacts (1A @ 30Vdc or 30Vac)
0-10Vdc = 0-30Vdc
0-10V = 0-100°C (internal temp.)
0-10V = 0-50A
CSA 22.2 #950-95, UL 508 Listed,
CE marked
Approvals/Certifications
Miscellaneous
7.2 x 10.6 x 5.3” (182 x 268 x 133mm)
Indicator
Power Factor
Green LED (DC on)
.9 typical @ 380Vac
.87 typical @ 480Vac
Minimum Vin 14ms
Typical Vin 20ms
Maximum Vin 28ms
Note: The output voltages of each power supply should be adjusted
to within 100mV. Use similar sizes and length of cables to
connect the output of each power supply to the load.