RSD-40A Diode Module
with Alarms
NEW
The RSD-40A modules can be used to
parallel two power supplies or isolate a single supply using diodes. The parallel version
works with two power supplies rated up to
20A each. The single diode isolation version
is rated up to 40A.
The low-voltage drop Schottky diodes are
mounted on a fan-cooled heatsink. The fan
starts only when the heatsink temperature
exceeds 60 deg. C and features proportional control to extend the operating life. The
temperature of the heatsink is monitored
and an analog output proportional to temperature and a high-temperature alarm output are provided. Terminals are also provided to monitor the presence of input voltage(s) and an output voltage.
Multiple output terminals are provided to
make power distribution easier.
Canada
Mexico
United States
Weidmuller Ltd.
Weidmuller, S.A. de C.V.
Weidmuller Inc.
10 Spy Court
Ave. Ingenieros Civiles #204
821 Southlake Blvd.
Markham, Ontario L3R 5H6
Conjunto Industrial Chachapa
Richmond, Virginia 23236
Telephone: (800) 268-4080
72990 Puebla, Pue. Mexico
Telephone: (800) 849-9343
Facsimile: (905) 475-2798
Telephone: (222) 286 62 47
Facsimile: (804) 379-2593
Email: [email protected]
Facsimile: (222) 286 62 42
Email: [email protected]
Website: www.weidmuller.ca
Website: www.weidmuller.com
RSD-40A Diode Module with Alarms
Specifications:
Input:
Outputs:
Power
Signals
Voltage
Current:
Wire size:
24Vdc nominal
2 x 20A Max. or 1 x 40A max.
22-6 AWG
Connections via screw terminals
Voltage:
Current:
Wire size:
input voltage - 0.4V
40A max.
22-6 AWG
Connections via screw terminals
“AN.1” = input 1 (2x20A version)
“AN.2” = input 2 (2x20A version)
“AN.1” = “AN.2” = input voltage (1x40A version)
“CATH” = output voltage
0-10Vdc = 0-100 deg. C
15Vdc max. output (150 deg. C)
24Vdc under normal operating conditions
0Vdc if heatsink temperature exceeds 90 deg. C
26-14 AWG
Connections via top entry tension clamp terminals
Voltage:
Temperature:
Alarm:
Wire size:
Other
Fan:
Operating temp.:
Mounting:
CSA pending
Approvals:
Catalog number:
2
turns -on when heatsink temperature exceeds 60 deg. C
Proportional control (fan speed increases as heatsink temperature
increases - fully on at 80 deg. C).
0-40 deg. C. ambient
32mm or 35mm DIN rails
2x20A:
1x40A:
7940005219
7940005218
RSD-40A Diode Module with Alarms
2 x 20A
1 x 40A
3
Other New Power Supply and Accessory Products
RS-SNT 1000W
• 360-480V, 3 phase input
• 24Vdc at 40A continuous, 80A for 1 second output
• analog outputs for output voltage, output current and
internal temperature
• 1 form C (SPDT) fault relay rated 1A
• DIN rail or panel mounted
• Catalog number: 7918960324
Diode Module with Voltage Sense
• 2 power supply inputs and 1 output rated 30A total
• low-voltage drop Schottky diodes isolate inputs
• user adjustable voltage sense controls fault relay (relay can
be configured to switch if either input voltage drops below
a 14-24Vdc set-point)
• 1 form C (SPDT) fault relay rated 6A
• mounts on 32mm or 35mm DIN rails
• Catalog number: 9987390000