CLS500 Catalog Sheet

© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
■ Overview
■ Configuration
Installation
4
Pointek CLS500 is an inverse frequency shift capacitance level
and material detection switch ideal for detecting interfaces,
solids, liquids, toxic, and aggressive chemicals in critical conditions of high temperature and pressure. CLS500 also has the
ability to tune out buildup on the probe.
Keep unit out of path of falling material, or protect probe from
falling material.
■ Benefits
• Active-Shield technology so measurement is unaffected by
material buildup in active shield section
• 2-wire loop powered with solid-state switch or 4 to 20/20 to
4 mA output
• Simple push-button calibration and integrated local display
• Full function diagnostics
• HART communications for remote commissioning and
inspection
Build up of material in active shield area does not affect
switch operation.
■ Application
Active-Shield technology ensures that measurement is unaffected by vapors, product deposits, dust, and condensation.
The unique mechanical probe design coupled with a high performance transmitter gives superior performance in a wide
range of level detection applications.
Pointek CLS500’s microprocessor-based electronics provide
one-point calibration, making setup possible without shutting
down your production process.
• Key Applications: foam or liquid/foam level, glycol regenerators, high-pressure coalescers, LNG applications
50 (2)
Install probe at least 50 (2) from tank wall.
Pointek CLS500 installation, dimensions in mm (inch)
Siemens FI 01 · 2016
4/63
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
■ Technical specifications
Design
Input
Measuring range
0 ... 330 pF
Span
Min. 1 pF
Material
• Wetted parts material
- Standard rod
• Probe isolation (rod)
Output
Solid-state switch
• Output
• Protection
• Max. switching voltage
• Max. load current
• Voltage drop
• Time delay
(pre or post switching)
4
Galvanically isolated
Against reversed polarity (bipolar)
• 30 V (DC)
• 30 V peak (AC)
82 mA
< 1 V, typical at 50 mA
1 ... 60 s
Probe diameter
• Standard rod version (PFA)
• High temperature rod version
(Stainless steel)
Probe length
• Standard rod version (PFA)
• High temperature rod version
(Stainless steel)
4 ... 20 mA/20 ... 4 mA
Current loop
Accuracy (transmitter)
Temperature stability
0.15 pF (0 pF) or < 0.25 % (typical
< 0.1 %) of actual measurement
value, whichever is greater over the
full temperature range
Non-linearity and repeatability
0.1 % of full scale and actual measurement respectively
Accuracy
Deviation < 0.1 % of measured value
Rated operating conditions1)
Installation conditions
• Location
Ambient conditions
• Ambient temperature (transmitter)
• Installation category
• Pollution degree
Medium conditions
• Relative dielectric constant r
• Process temperature
- Standard (PFA)
- High temperature stainless steel
version with thermal isolator
- Cryogenic version3)
Process pressure
Indoor/outdoor
-40 ... +85 °C (-40 ... +185
I
4
°F)2)
Min. 1.5
Temperature ratings are pressure
dependent. See Pressure/Temperature curves on page 4/71.
-50 ... +200 °C (-58 ... +392 °F)
-60 ... +400 °C (-76 ... +752 °F)
-200 ... +200 °C (-328 ... +392 °F)
Pressure rating of process seal is
temperature dependent.
See Pressure/Temperature curves on
page 4/71.
-1 ... +150 bar g
• Standard (PFA)
(-14.6 ... +2 175 psi g)
• High temperature version (Stainless -1 ... +35 bar g
(-14.6 ... +507.6 psi g)
steel)
Process connection of probe
• Threaded mounting
• Flange mounting
Enclosure
• Material
316L stainless steel
PFA
16 mm (0.63 inch)
19 mm (0.75 inch)
Max. 1 000 mm (39.4 inch) with
16 mm (0.63 inch) diameter probe
Max. measuring length 1 000 mm
(39.4 inch) with 19 mm (0.75 inch)
diameter probe
NPT [(Taper), ANSI/ASME B1.20.1]
R [(BSPT), EN 10226/PT (JIS-T),
JIS B 0203]
G [(BSPP), EN ISO 228-1/PF (JIS-P),
JIS B 0202]
ASME, EN 1092-1
• Cable inlet
• Degree of protection
Aluminum, epoxy-coated (stainless
steel option available3))
2 x ½" NPT
Type 4X/NEMA4X/IP65, IP68
Power supply
Max. 33 V DC
Features
Measurement current signaling
NAMUR NE 43
Safety
• Inputs/outputs fully galvanically
isolated
• Polarity-insensitive current loop
• Fully potted
• Integrated safety barrier
Primary variable (PV) out of limits,
system failure in measurement circuit,
deviation between A/D and D/A converter, check sum, watch dog and
self-checking facility
Positions 0 ... 9, A ... F
Conforming to HART Communication
Foundation (HCF)
• Diagnostics with fault alarm when:
• Function rotary switch
• SMART communication
Certificates and approvals
General Purpose
Non incendive/Non sparking
Dust Ignition Proof
Explosion Proof
Marine
1)
CE, CSA/FM, RCM
CSA/FM Class I, Div. 2, Groups A, B,
C, D T4
ATEX II 3G 2D EEx n A [ib] IIC T6 ...
T4 T100 °C
CSA/FM Class II and III, Div. 1,
Groups E, F, G T4
ATEX II 1/2 GD EEx d [ia] T6 ... T1
T100 °C
FM Class I, Div. 1, Groups A, B, C, D
T4
ATEX II 1/2 GD EEx d [ia] IIC T6 ... T1
T100 °C
Lloyds Register of Shipping, Categories ENV1, ENV2, ENV3, ENV5,
Bureau Veritas
When operation is in areas classified as hazardous, observe restrictions
according to relevant certificate. See also Pressure/Temperature curves on
page 4/71.
2)
Thermal isolator is used if process connection temperature exceeds 85 °C
(185 °F)
3)
Customers interested in a custom designed device should consult a local
sales person. For more information, please visit http://
www.automation.siemens.com/aspa_app.
4/64
Siemens FI 01 · 2016
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
Pointek CLS500 probe version
Standard
HT Series
Process connection types
Standard (PFA)
(7ML5601, 7ML5602, 7ML5603)
High Temperature (Stainless steel) (7ML5604)
Threaded
Available as standard
–
Flange
Available as standard
Available as standard
Available as standard
Available as standard
None
–
HT Stainless: available as standard
PFA
Available as standard
–
1 000 mm (40 inch)
1 000 mm (40 inch)
Max. process pressure
150 bar g (2 175 psi g)
Stainless steel2): 35 bar g (507 psi g)
Max. process temperature
200 °C (392 °F)
400 °C (752 °F)
Process connection materials
316L stainless steel
Probe insulation
Length parameters
Max. rod length
Process condtitions1)
4
1)
When operation is in areas classified as hazardous, observe restrictions according to relevant certificate. See also Pressure/Temperature curves on
page 4/71. Pressure rating of process seal is temperature dependent. See Pressure/Temperature curves on page 4/71.
2)
Pressure rating of process seal is temperature dependent. See Pressure/Temperature curves on page 4/71.
– Not available as standard
Siemens FI 01 · 2016
4/65
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
Selection and Ordering data
Article No.
Selection and Ordering data
Pointek CLS500, threaded
Inverse frequency shift capacitance level and
material detection switch for detecting interfaces,
solids, liquids, toxic and aggressive chemicals in
critical conditions of extreme temperature and
pressure. CLS500 also has the ability to tune out
buildup on the probe.
7ML5601-
Further designs
77 7 77 - 77 A 0
Please add "-Z" to Article No. and specify Order
code(s).
Total insertion length: enter the total insertion length
in plain text description
4
Y01
Note: The difference between Y01 and Y02 must be
a minimum of 150 mm
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Electronic transmitter
No transmitter supplied
MSP 2002-1 (330 pF)
Order code
0
1
Active Shield length - minimum length is 50 mm
Y02: to mm1)
Y02
Stainless steel tag [69 x 50 mm (2.71 x 1.97 inch)]:
Measuring-point number/identification
(max. 27 characters) specify in plain text
Y15
Process connection
¾"
1"
1¼"
A
B
C
Manufacturer's test certificate: M to DIN 55350,
Part 18 and to ISO 9000
C11
Inspection Certificate Type 3.1 per EN 10204
C12
1½"
2"
D
E
Operating Instructions
Threaded connection and rating
NPT [(Taper), ANSI/ASME B1.20.1]
R [(BSPT), EN 10226/PT (JIS-T) JIS B 0203]
G [(BSPP), EN ISO 228-1/PF (JIS-P), JIS B 0202]
Probe insulation/material of process connection
PFA insulation/316L stainless steel
A
B
D
1
1
2
ATEX II 1/2 GD EEx d [ia] IIC T6 ... T1 T100 °C
FM Class I, Div. 1, Groups A, B, C, D T4
4
6
Thermal isolator/remote version
Rigid thermal isolator [for process connection
temperature over 85 °C (185 °F)]
No thermal isolator
1)
Add Order code Y01 and Y02 in plain text:
"Insertion/active shield length to mm"
4/66
Siemens FI 01 · 2016
See page 4/70
Pointek Specials
See page 4/79
1)
Approvals
General Purpose: CE, CSA/FM, RCM
CSA/FM Class I, Div. 2, Groups A, B, C, D T4;
ATEX II 3GD 2D EEx nA [ib] IIC T6 ... T4 T100 °C;
CSA/FM Class II and III Div. 1, Groups E, F, G T4
Probe/electrode diameter
16 mm (0.63 inch) rigid rod, minimum insertion
length 200 mm (7.9 inch), maximum insertion
length 1 000 mm (39.4 inch)1)
Note: The Operating Instructions should be
ordered as a separate line on the order.
This device is shipped with the Siemens Level and
Weighing manual DVD containing the ATEX Quick
Start and manual library.
1
A
B
See dimension drawings on page 4/76 for further explanation of Y02
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
Selection and Ordering data
Article No.
Selection and Ordering data
Pointek CLS500, welded flange
Inverse frequency shift capacitance level and
material detection switch for detecting interfaces,
solids, liquids, toxic and aggressive chemicals in
critical conditions of extreme temperature and
pressure. CLS500 also has the ability to tune out
buildup on the probe.
7ML5602-
Further designs
Please add "-Z" to Article No. and specify Order
code(s).
77 7 77 - 77 A 0
Order code
Total insertion length: enter the total insertion length
in plain text description
Y01
Active Shield length - minimum length is 50 mm.
Y02: to mm1)
Y02
Stainless steel tag [69 x 50 mm (2.71 x 1.97 inch)]:
Measuring-point number/identification
(max. 27 characters) specify in plain text
Y15
Manufacturer's test certificate: M to DIN 55350,
Part 18 and to ISO 9000
C11
AA
AB
BA
BB
Inspection Certificate Type 3.1 per EN 10204
C12
4" ASME, 150 lb1)
4" ASME, 300 lb1)
6" ASME, 150 lb1)
6" ASME, 300 lb1)
Welded flange, 316L stainless steel,
Type A flat faced
DN 50 PN 16
DN 50 PN 40
DN 80 PN 16
CA
CB
DA
DB
This device is shipped with the Siemens Level and
Weighing manual DVD containing the ATEX Quick Start
and manual library.
DN 80 PN 40
DN 100 PN 161)
DN 125 PN 161)
(Note: Flange bolting patterns and facings
dimensionally correspond to the applicable
ASME B16.5 or EN 1092-1 standard.)
FD
GC
HC
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Electronic transmitter
MSP 2002-1 (330 pF)
Process connection and pressure rating
Welded flange, 316L stainless steel, raised face
2" ASME, 150 lb
2" ASME, 300 lb
3" ASME, 150 lb
3" ASME, 300 lb1)
Probe insulation/material of process connection
PFA insulation/316L stainless steel
Approvals
General Purpose
CSA/FM Class I, Div. 2, Groups A, B, C, D T4;
ATEX II 3GD 2D EEx nA [ib] IIC T6 ... T4 T100 °C;
CSA/FM Class II and III Div. 1, Groups E, F, G T4
ATEX II 1/2 GD EEx d [ia] IIC T6 ... T1 T100 °C
FM Class I, Div. 1, Groups A, B, C, D T4
Probe/electrode diameter
16 mm (0.63 inch) rigid rod, min. length 200 mm
(7.9 inch), max. length 1 000 mm (39.4 inch)
Thermal isolator
Rigid thermal isolator
[for process temperature over 85 °C (185 °F)]
No thermal isolator
1)
1
Operating Instructions
Note: The Operating Instructions should be
ordered as a separate line on the order.
Pointek Specials
1)
See page 4/70
See page 4/79
See dimensional drawings on page 4/77 for further explanation of Y02
EC
ED
FC
1
1
2
4
6
1
A
B
Custom shipping methods required. Contact factory for more details.
Siemens FI 01 · 2016
4/67
4
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
Selection and Ordering data
Pointek CLS500, single piece flange
Inverse frequency shift capacitance level and
material detection switch for detecting interfaces,
solids, liquids, toxic and aggressive chemicals in
critical conditions of extreme temperature and
pressure. CLS500 also has the ability to tune out
buildup on the probe.
Article No.
Selection and Ordering data
7ML560377 7 77 - 77 A 0
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Electronic transmitter
MSP 2002-1 (330 pF)
4
1
Process connection and pressure rating
Single piece flange, 316L stainless steel,
raised face
2" ASME, 150 lb
2" ASME, 300 lb
AA
AB
3" ASME, 150 lb
3" ASME, 300 lb1)
BA
BB
4" ASME, 150 lb1)
4" ASME, 300 lb1)
CA
CB
6" ASME, 150 lb1)
6" ASME, 300 lb1)
Single piece flange, 316L stainless steel,
Type B1 raised faced
DA
DB
DN 50 PN 16
DN 50 PN 25
EC
ED
DN 80 PN 16
DN 80 PN 25
FC
FD
DN 100 PN 161)
DN 100 PN 251)
GC
GD
DN 125 PN 161)
DN 125 PN 251)
HC
HD
Probe insulation/material of process connection
PFA insulation/316L stainless steel
1
ATEX II 1/2 GD EEx d [ia] IIC T6 ... T1 T100 °C
FM Class I, Div. 1, Groups A, B, C, D T4
4
6
1
Thermal isolator
Rigid thermal isolator [for process connection
temperature over 85 °C (185 °F)]
No thermal isolator
Custom shipping methods required. Contact factory for more details
4/68
Siemens FI 01 · 2016
Y01
Active Shield length - minimum length is 50 mm.
Y02: to mm1)
Y02
Stainless steel tag [69 x 50 mm (2.71 x 1.97 inch)]:
Measuring-point number/identification
(max. 27 characters) specify in plain text
Y15
Manufacturer's test certificate: M to DIN 55350,
Part 18 and to ISO 9000
C11
Inspection Certificate Type 3.1 per EN 10204
C12
Note: The Operating Instructions should be
ordered as a separate line on the order.
This device is shipped with the Siemens Level and
Weighing manual DVD containing the ATEX Quick
Start and manual library.
See page 4/70
Accessories
See page 4/79
1)
1
2
1)
Total insertion length: enter the total insertion length
in plain text description
Operating Instructions
Approvals
General Purpose: CE, CSA/FM, RCM
CSA/FM Class I, Div. 2, Groups A, B, C, D T4;
ATEX II 3GD 2D EEx nA [ib] IIC T6 ... T4 T100 °C;
CSA/FM Class II and III Div. 1, Groups E, F, G T4
Probe/electrode diameter
16 mm (0.63 inch) rigid rod,
maximum length 1 000 mm (39.4 inch) (Y01)
Order code
Further designs
Please add "-Z" to Article No. and specify Order
code(s).
A
B
See dimensional drawings on page 4/77 for further explanation of Y02
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
Selection and Ordering data
Article No.
Selection and Ordering data
Article No.
Pointek CLS500 High temperature
Inverse frequency shift capacitance level and
material detection switch for detecting interfaces,
solids, liquids, toxic and aggressive chemicals in
critical conditions of extreme temperature and
pressure. CLS500 also has the ability to tune out
buildup on the probe.
7ML5604-
Pointek CLS500 High temperature
Inverse frequency shift capacitance level and
material detection switch for detecting interfaces,
solids, liquids, toxic and aggressive chemicals in
critical conditions of extreme temperature and
pressure. CLS500 also has the ability to tune out
buildup on the probe.
7ML5604-
7A 7 77 - 7777
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Electronic transmitter
None5)
MSP 2002-1 (330 pF)
Probe material of process connection
No insulation/316L stainless steel3)4)
1
Stilling well
No stilling well
0
1
Process connection and pressure rating
316L stainless steel, raised face1)
2" ASME, 150 lb
2" ASME, 300 lb
2" ASME, 600 lb
2" ASME, 900 lb
A1
A2
A3
A4
3" ASME, 150 lb
3" ASME, 300 lb2)
3" ASME, 600 lb2)
3" ASME, 900 lb2)
B1
B2
B3
B4
4" ASME, 150 lb2)
4" ASME, 300 lb2)
4" ASME, 600 lb2)
4" ASME, 900 lb2)
C1
C2
C3
C4
lb2)
7 A 7 77 - 7777
6" ASME, 150
6" ASME, 300 lb2)
6" ASME, 600 lb2)
6" ASME, 900 lb2)
316L stainless steel, Type B1 flat faced
D1
D2
D3
D4
DN 50 PN 16
DN 50 PN 25
DN 50 PN 40
DN 50 PN 63
E1
E2
E3
E4
DN 80 PN 16
DN 80 PN 25
DN 80 PN 402)
DN 80 PN 632)
F
F
F
F
DN 100 PN 162)
DN 100 PN 252)
DN 100 PN 402)
DN 100 PN 642)
G1
G2
G3
G4
DN 125 PN 162)
DN 125 PN 252)
DN 125 PN 402)
DN 125 PN 642)
(Note: Flange bolting patterns and facings
dimensionally correspond to the applicable
ASME B16.5 or EN 1092-1 standard.)
H1
H2
H3
H4
0
Approvals
General Purpose
CSA/FM Class I, Div. 2, Groups A, B, C, D T4;
ATEX II 3GD 2D EEx nA [ib] IIC T6 ... T4 T100 °C;
CSA/FM Class II and III Div. 1, Groups E, F, G T4
A
B
ATEX II 1/2 GD EEx d [ia] IIC T6 ... T1 T100 °C
FM Class I, Div. 1, Groups A, B, C, D T4
D
F
Probe/electrode diameter
Maximum length 1 000 mm (39.37 inch)4)
Thermal isolator
Rigid thermal isolator [for process connection
temperature over 85 °C (185 °F)]
4
A
1
1)
Welded flange for no insulation option only
2)
Custom shipping methods required
3)
Non-conductive material only, stainless steel non-insulated probe diameter
19 mm (0.75 inch)
4)
Add Order code Y01 and Y02 in plain text: "Insertion/active shield length
to mm"
Minimum insertion length depends on probe version selected.
See dimensional drawings on page 4/76 for more details
5)
Only available with Approvals option A
1
2
3
4
Siemens FI 01 · 2016
4/69
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
Selection and Ordering data
Order code
Further designs
Please add "-Z" to Article No. and specify Order
code(s).
4
Total insertion length: enter the total insertion length
in plain text description
Y01
Active Shield length - minimum length is 50 mm.
Y02: to mm1)
Y02
Stainless steel tag [69 x 50 mm (2.71 x 1.97 inch)]:
Measuring-point number/identification
(max. 27 characters) specify in plain text
Y15
Manufacturer's test certificate: M to DIN 55350,
Part 18 and to ISO 9000
C11
Inspection Certificate Type 3.1 per EN 10204
C12
Operating Instructions
Article No.
English
7ML1998-5GG03
German
7ML1998-5GG32
Note: The Operating Instructions should be
ordered as a separate line on the order.
All literature is available to download for free, in a range
of languages, at http://www.siemens.com/
processinstrumentation/documentation
This device is shipped with the Siemens Level and
Weighing manual DVD containing the ATEX Quick Start
and Operating Instructions library.
Accessories
General Purpose
1/2" NPT General Purpose Cable Entry IP68/IP69K
NEMA6, -40 ... +100 °C (-40 ... +212 °F), cable size
6 ... 12 mm (0.236 ... 0.472 inch)
7ML1830-1JA
M20 x 1.5 General Purpose Cable Entry IP68/IP69K
NEMA6, -40 ... +100 °C (-40 ... +212 °F), cable size
7 ... 12 mm (0.275 ... 0.472 inch)
7ML1830-1JC
Transmitter, MSP 2002-1, 330 PF
7ML1830-1JP
Hazardous Locations
1/2" NPT EMC rated Cable Gland: Dust Ignition Proof, 7ML1830-1JB
Flameproof Exd, and Increased Safety ATEX II 2 GD
ExtD A21 (Zone 1, Zone 2, Zone 21, Zone 22, and in
Gas Groups IIA,IIB, and IIC) -60 ... +80 °C IP66, IP67,
IP68, NEMA4X, cable sizes 5.5 ... 12 mm
(0.216 ... 0.472 inch)
M20 EMC rated Cable Gland: Dust Ignition Proof,
Flameproof Exd, and Increased Safety ATEX II 2 GD
ExtD A21 (Zone 1, Zone 2, Zone 21, Zone 22, and in
Gas Groups IIA,IIB and IIC) -60 ... +80 °C IP66, IP67,
IP68, NEMA4X, cable sizes 5.5 ... 12 mm
(0.216 ... 0.472 inch)
7ML1830-1JD
Pointek Specials
See page 4/79
1)
See dimensional drawings on page 4/77 for further explanation of Y02
4/70
Siemens FI 01 · 2016
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
■ Characteristic curves
Pressure/temperature curve
CLS500 rod probes
Threaded process connections
(7ML5601)
Permitted operating pressures P
150 bar (2.175 psi)
140 bar (2.030 psi)
130 bar (1.885 psi)
4
120 bar (1.740 psi)
110 bar (1.595 psi)
100 bar (1.450 psi)
90 bar (1.305 psi)
80 bar (1.160 psi)
70 bar (1.015 psi)
60 bar (870 psi)
50 bar (725 psi)
40 bar (580 psi)
30 bar (435 psi)
20 bar (290 psi)
Atmospheric
10 bar (145 psi)
-40 ºF 14 ºF
(-40 ºC)(-10 ºC)
-1 bar (-14.5 psi)
-150 ºC
(-238 ºF)
-100 ºC -50 ºC
(-148 ºF) (-58 ºF)
100 ºF
(38 ºC)
0 ºC RT 50 ºC
(32 ºF)
(122 ºF)
200 ºF
(93 ºC)
100 ºC
(212 ºF)
-29 ºC
(-20 ºF)
300 ºF
(149 ºC)
150 ºC
(302 ºF)
400 ºF
(204 ºC)
200 ºC
(392 ºF)
500 ºF
(260 ºC)
250 ºC
(482 ºF)
600 ºF
(315 ºC)
300 ºC
(572 ºF)
700 ºF
(371 ºC)
350 ºC
400 ºC
(662 ºF) (752 ºF)
Permitted operating temperature T
Example:
Permitted operating pressure = 137 bar (1988 psi) at 75 °C
Pointek CLS500 process pressure/temperature derating curves (7ML5601)
Siemens FI 01 · 2016
4/71
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
Pressure/temperature curve
CLS500 rod probes
ASME flanged process connections
(7ML5602 and 7ML5603)
Permitted operating pressures P
150 bar (2.175 psi)
140 bar (2.030 psi)
130 bar (1.885 psi)
120 bar (1.740 psi)
4
110 bar (1.595 psi)
100 bar (1.450 psi)
90 bar (1.305 psi)
80 bar (1.160 psi)
70 bar (1.015 psi)
60 bar (870 psi)
50 bar (725 psi)
40 bar (580 psi)
30 bar (435 psi)
ASME 300 lb1)
20 bar (290 psi)
-40 ºF 14 ºF
(-40 ºC)(-10 ºC)
-1 bar (-14.5 psi)
-150 ºC
(-238 ºF)
ASME 150 lb1)
10 bar (145 psi)
Atmospheric
-100 ºC -50 ºC
(-148 ºF) (-58 ºF)
100 ºF
(38 ºC)
0 ºC RT 50 ºC
(32 ºF)
(122 ºF)
200 ºF
(93 ºC)
100 ºC
(212 ºF)
300 ºF
(149 ºC)
150 ºC
(302 ºF)
-29 ºC
(-20 ºF)
1)
The curve denotes the minimum allowable flange class for the shaded area below.
Pointek CLS500 process pressure/temperature derating curves (7ML5602 and 7ML5603)
4/72
Siemens FI 01 · 2016
400 ºF
(204 ºC)
200 ºC
(392 ºF)
500 ºF
(260 ºC)
250 ºC
(482 ºF)
600 ºF
(315 ºC)
300 ºC
(572 ºF)
700 ºF
(371 ºC)
350 ºC
400 ºC
(662 ºF) (752 ºF)
Permitted operating temperature T
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
Pressure/temperature curve
CLS500 rod probes
EN flanged process connections
(7ML5602 and 7ML5603)
Permitted operating pressures P
150 bar (2.175 psi)
140 bar (2.030 psi)
130 bar (1.885 psi)
120 bar (1.740 psi)
4
110 bar (1.595 psi)
100 bar (1.450 psi)
90 bar (1.305 psi)
80 bar (1.160 psi)
70 bar (1.015 psi)
60 bar (870 psi)
50 bar (725 psi)
40 bar (580 psi)
30 bar (435 psi)
20 bar (290 psi)
PN 251)
Atmospheric
-40 ºF 14 ºF
(-40 ºC)(-10 ºC)
-1 bar (-14.5 psi)
-150 ºC
(-238 ºF)
PN 161)
10 bar (145 psi)
-100 ºC -50 ºC
(-148 ºF) (-58 ºF)
100 ºF
(38 ºC)
0 ºC RT 50 ºC
(32 ºF)
(122 ºF)
200 ºF
(93 ºC)
100 ºC
(212 ºF)
300 ºF
(149 ºC)
150 ºC
(302 ºF)
-29 ºC
(-20 ºF)
1)
400 ºF
(204 ºC)
200 ºC
(392 ºF)
500 ºF
(260 ºC)
250 ºC
(482 ºF)
600 ºF
(315 ºC)
300 ºC
(572 ºF)
700 ºF
(371 ºC)
350 ºC
400 ºC
(662 ºF) (752 ºF)
Permitted operating temperature T
The curve denotes the minimum allowable flange class for the shaded area below.
Pointek CLS500 process pressure/temperature derating curves (7ML5602 and 7ML5603)
Siemens FI 01 · 2016
4/73
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
Pressure/temperature curve
CLS500 high temperature (no insulation)
ASME flanged process connections
(7ML5604)
Permitted operating pressures P
90 bar (1.305 psi)
80 bar (1.160 psi)
70 bar (1.015 psi)
4
60 bar (870 psi)
ASME 600 lb1)
50 bar (725 psi)
40 bar (580 psi)
30 bar (435 psi)
ASME 300 lb1)
20 bar (290 psi)
ASME 150 lb1)
10 bar (145 psi)
Atmospheric
-40 ºF 14 ºF
(-40 ºC) (-10 ºC)
-1 bar (-14.5 psi)
-150 ºC
(-238 ºF)
-100 ºC -50 ºC
(-148 ºF) (-58 ºF)
100 ºF
(38 ºC)
0 ºC RT 50 ºC
(32 ºF)
(122 ºF)
200 ºF
(93 ºC)
100 ºC
(212 ºF)
300 ºF
(149 ºC)
150 ºC
(302 ºF)
-29 ºC
(-20 ºF)
1)
The curve denotes the minimum allowable flange class for the shaded area below.
Pointek CLS500 process pressure/temperature derating curves (7ML5604)
4/74
Siemens FI 01 · 2016
400 ºF
(204 ºC)
200 ºC
(392 ºF)
500 ºF
(260 ºC)
250 ºC
(482 ºF)
600 ºF
(315 ºC)
300 ºC
(572 ºF)
700 ºF
(371 ºC)
350 ºC
400 ºC
(662 ºF) (752 ºF)
Permitted operating temperature T
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
Pressure/temperature curve
CLS500 high temperature (no insulation)
EN flanged process connections
(7ML5604)
Permitted operating pressures P
40 bar (580 psi)
30 bar (435 psi)
PN 401)
20 bar (290 psi)
PN 251)
Atmospheric
10 bar (145 psi)
-40 ºF 14 ºF
(-40 ºC) (-10 ºC)
-1 bar (-14.5 psi)
-150 ºC
(-238 ºF)
-100 ºC -50 ºC
(-148 ºF) (-58 ºF)
PN 161)
100 ºF
(38 ºC)
0 ºC RT 50 ºC
(32 ºF)
(122 ºF)
200 ºF
(93 ºC)
100 ºC
(212 ºF)
300 ºF
(149 ºC)
150 ºC
(302 ºF)
-29 ºC
(-20 ºF)
1)
400 ºF
(204 ºC)
200 ºC
(392 ºF)
500 ºF
(260 ºC)
250 ºC
(482 ºF)
600 ºF
(315 ºC)
300 ºC
(572 ºF)
700 ºF
(371 ºC)
350 ºC
400 ºC
(662 ºF) (752 ºF)
Permitted operating temperature T
The curve denotes the minimum allowable flange class for the shaded area below.
Pointek CLS500 process pressure/temperature derating curves (7ML5604)
Siemens FI 01 · 2016
4/75
4
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
■ Dimensional drawings
Standard rod version
Threaded (7ML5601)
205 (8.1)
Standard configuration
(7ML5601)
Transmitter/
electronics
Inactive tip
Ø16 (0.63)
Pointek CLS500 threaded process connections, dimensions in mm (inch)
4/76
Siemens FI 01 · 2016
With thermal isolator option
(all versions)
270 (10.6)
With explosion-proof seal option
(all versions)
Thermal
isolator
430 (16.9)
30 (1.18)
PFA insulated
probe
1/2" NPT:
230 (9.1)
Measuring length
4
Y02
Y01 (insertion length)
min. = 200 (7.87) / max. = 1 000 (39.37)
20 (0.79)
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
Standard Rod version
Welded Flange (7ML5602)
Single Piece Flange (7ML5603)
205 (8.1)
Standard configuration
(7ML5602, 7ML5603)
Transmitter/
electronics
With thermal isolator option
(all versions)
4
430 (16.9)
270 (10.6)
With explosion-proof seal option
(all versions)
Measuring length1)
30 (1.18)
PFA insulated
probe
Y021)
Y01 (insertion length)
min. = 200 (7.87)/max. = 1 000 (39.37)
½" NPT:
230 (9.1)
Thermal
isolator
Inactive tip
Ø16 (0.63)
High temperature rod version
Welded Flange (7ML5604), Stainless steel rod 4)
Flange Facing (raised face)
Flange Class
Thermal
isolator
Facing thickness
ASME 150/300
2 (0.08)
ASME 600/900
7 (0.28)
PN16/25/40/64
2 (0.08)
Notes:
1)
Min. Y02 (active shield length) = 50 (1.96)
Min. Y02 (active shield length) = 138 (5.43)
3)
Min. Y02 (active shield length) = 100 (3.94)
4)
Non conductive materials only
Stainless steel
probe
Measuring
Y02 2)
length2)
Y01 (insertion length)
min. = 244 (9.61)/max. = 1 000 (39.37)
2)
Insertion length does not include any raised
face/gasket face dimension (see Flange
Facing Table above)
Ø19 (0.75)
Pointek CLS500 flanged process connections, dimensions in mm (inch)
Siemens FI 01 · 2016
4/77
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS500
■ Schematics
Ground lug
Protective
label
Solid state
switch relay
(any polarity)
Instrument
system
ground
Measuring
signal
(minicoaxial
cable)
Type:
Ser.:
Date:
Rev.:
Tampering voids warranty
4
Ground connection
point for instrument
system
Pointek CLS500 connections
4/78
Siemens FI 01 · 2016
4 ... 20 mA
current loop
connection
(any polarity)
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS Specials
■ Selection and ordering data
Pointek Specials1)
Pointek Specials1)
Article No.
Article No.
Kit, sensor for cable units, PPS, digital,
FKM
A5E01163678
Kit, sensor for cable units, PPS, standard,
FFKM
A5E01163679
Kit, sensor for cable units, PPS, digital,
FFKM
A5E01163680
Kit, sensor for cable units, PVDF, standard,
FKM
A5E01163681
Kit, sensor for cable units, PVDF, digital,
FKM
A5E01163682
CLS100 Miscellaneous Parts
Custom length of cable is available only for
7ML5501-xxx1x and 7ML5501-xxx5x2)
Kit, sensor for cable units, PVDF, standard,
FFKM
A5E01163683
CLS200 Gasket (IP65), Synprene
Kit, sensor for cable units, PVDF, digital,
FFKM
A5E01163684
CLS100 Polycarbonate Lid and Gasket, FKM
Kit, Lid and gasket,
CLS100 enclosure version
A5E01163671
CLS200 Mounting Bracket,
316L stainless steel
Spare gasket, enclosure version
(IP65 versions only)
A5E01163672
CLS200 Gasket (IP68), Silicone
Spare mounting bracket
A5E01163685
CLS200 PROFIBUS Connector (IP65)
Spare gasket, enclosure version
(IP68 versions)
A5E01163673
Spare, PROFIBUS connector
(IP65 versions only)
CLS200 Blind Lid
A5E01163686
CLS200 Miscellaneous Parts
CLS200 with FFKM O-rings (any version)2)
CLS200 Electronics
Spare aluminum blind lid
(for standard versions only)
A5E01163674
CLS200 Lid with window
Test magnet, digital version
7ML1830-1JE
Amplifier/power supply kit, standard version
A5E03251681
Amplifier/power supply, digital version
7ML1830-1JF
LCD display, digital version
7ML1830-1JK
CLS300 Cable Extensions,
316L stainless steel
Spare aluminum lid with window
A5E01163676
CLS200 Sensor Kit for cable units
Kit, sensor for cable units, PPS, Standard, FKM
A5E01163677
Kit, stainless steel cable extension, 1 m,
adjustable by customer
A5E01163688
Kit, stainless steel cable extension, 3 m,
adjustable by customer
A5E01163689
Kit, stainless steel cable extension, 5 m,
adjustable by customer
A5E01163690
Kit, stainless steel cable extension, 10 m,
adjustable by customer
A5E01163691
Kit, stainless steel cable extension, 15 m,
adjustable by customer
A5E01163693
Kit, stainless steel cable extension, 20 m,
adjustable by customer
A5E01163695
Siemens FI 01 · 2016
4/79
4
© Siemens AG 2016
Level Measurement
Point level measurement - RF Capacitance switches
Pointek CLS Specials
Pointek Specials1)
Pointek Specials1)
Article No.
CLS300 Cable Extensions,
316 stainless steel with PFA coating
4
Article No.
CLS300 Electronics Kits with drivers
(for rod or cable versions)
Kit, PFA cable extension, 1 m,
adjustable by customer
A5E01163697
Kit, PFA cable extension, 3 m,
adjustable by customer
A5E01163698
Kit, PFA cable extension, 5 m,
adjustable by customer
A5E01163699
Kit, PFA cable extension, 10 m,
adjustable by customer
A5E01163700
Kit, PFA cable extension, 15 m,
adjustable by customer
A5E01163701
Kit, PFA cable extension, 20 m,
adjustable by customer
A5E01163702
CLS300 Rod Kits, 316L stainless steel
Kit, electronics with driver, standard CLS300.
To be used in rod or cable versions with
length less than 5 m.3)4)
A5E01163723
Kit, electronics with driver, digital CLS300.
To be used in rod or cable versions with
length less than 5 m.3)4)
A5E01163725
CLS300 Electronics Kits with drivers
(for cable versions)
Kit, electronics with driver, standard CLS300.
To be used in cable versions with
length greater than 5 m.3)4)
A5E01163724
Kit, electronics with driver, digital CLS300.
To be used in cable versions with
length greater than 5 m.3)4)
A5E01163726
CLS300 Electronics
Kit, stainless steel rod 180 mm (7.09 inch) to
be used with CLS300 units only (with standard
active shield). Insertion length after installation
is 350 mm (13.78 inch).
A5E01163719
Kit, stainless steel rod 330 mm (12.99 inch) to
be used with CLS300 units only (with standard
active shield). Insertion length after installation
is 500 mm (19.69 inch).
A5E01163720
Kit, stainless steel rod 580 mm (22.83 inch) to
be used with CLS300 units only (with standard
active shield). Insertion length after installation
is 750 mm (29.53 inch).
A5E01163721
Kit, stainless steel rod 830 mm (32.68 inch) to
be used with CLS300 units only (with standard
active shield). Insertion length after installation
is 1 000 mm (39.37 inch).
A5E01163722
Kit, stainless steel rod 1 330 mm (52.36 inch) to
be used with CLS300 units only (with standard
active shield). Insertion length after installation
is 1 500 mm (59.06 inch).2)
Kit, stainless steel rod 1 830 mm (72.05 inch) to
be used with CLS300 units only (with standard
active shield). Insertion length after installation
is 2 000 mm (78.74 inch).2)
Test magnet, digital version
7ML1830-1JE
Amplifier/power supply kit, standard version
A5E03251683
Amplifier/power supply, digital version
7ML1830-1JF
LCD display, digital version
7ML1830-1JK
CLS300 Weight Kit, 316L stainless steel
Kit, spare stainless steel weight. To be used in
any cable version of CLS300
A5E01163727
CLS500 Gasket (IP65), Silicone
Spare gasket, CLS500 enclosure version, IP65
A5E01163728
CLS500 Blind Lid
Spare CLS500 aluminum blind lid
A5E01163729
Kit, stainless steel rod customized length
up to 1 m2)
CLS500 Electronics Kit
Kit, stainless steel rod customized length
up to 2 m2)
1)
Special flange sizes and facings are available. Please consult a local sales
person for details.
2)
Please consult a local sales person for part number and pricing
3)
For General Purpose approvals only
4)
To maintain approvals, qualified trained Siemens personnel
required for part replacement
Transmitter, MSP 2002-1, 330 PF
7ML1830-1JP
Customers interested in a custom designed device should consult a local
sales person. For more information, please visit
http://www.automation.siemens.com/aspa_app.
4/80
Siemens FI 01 · 2016