SITRANS RD500 Catalog Sheet

© Siemens AG 2016
Supplementary Components
Remote Data Manager
SITRANS RD500
■ Overview
■ Benefits
The SITRANS RD500 is a remote data manager providing remote monitoring through integrated web access, alarm event
handling, and data capture for instrumentation and other devices.
• RD500 supports report and alarm events via email, SMS, and
FTP transfer
• Web provides worldwide access to instrument data and
RD500 configuration and setup
• Simple configuration using a standard web browser, no
programming or additional software required.
• Offers scalability with optional I/O modules for current
(4 to 20 mA), voltage (0 to 10 V), thermocouple (TC), resistance temperature detector (RTD), and digital input, output
and counter
• 10 base-TI 100 Base-TX Ethernet and support for GSM,
GPRS, 3G, and PSTN provide flexible remote communications
options
• Supports up to 128 devices with the flexible I/O modules and
supports addressing for Modbus serial devices via RS 232
and RS 485 serial ports
• Integrated FTP server and client support FTP data synchronization to central servers
• Compact flash slot supports up to 2 gigabytes of expandable
memory for data capture and storage, 1 gigabyte industrial
compact flash card included
• Log files formats are CSV (comma separated values) for data
files and HTML for report files
• Supports Modbus TCP via Ethernet and GPRS for easy
integration into control systems
• Optional 3G Modem offers VPN support
■ Application
7
The RD500 is an easy-to-use remote data monitoring solution,
using a web-based application and hardware modules. The
unique modular approach allows a variety of process signals to
be monitored, while the serial ports allow data to be collected
from Modbus RTU devices.
The RD500 comprises a master communications module, and
up to 16 slave modules. Various module types are available, allowing up to a maximum of 128 conventional inputs and outputs.
The RD500’s serial ports can support addressing for up
Modbus RTU slave devices including field instruments.
The RD500's built-in web server, FTP, and email client allows the
process to be monitored remotely. Alarm notifications are com-
municated through email and SMS text messages to one or more
recipients to ensure that appropriate actions are taken by personnel.
The RD500 supports modems, providing flexibility for applications in which cellular or landline connectivity is desired.
The RD500 is configured via a web-based interface - a standard
browser is all the software you need to configure your system.
• Key Applications: remote monitoring of inventory, process,
and maintenance applications, with web access to field instrumentation
WWW
With SITRANS RD500, monitor inventory levels, process, environmental, and remote maintenance
applications, and get web access to most types of field instrumentation, including flow, level, pressure,
temperature measurement, and weighing.
7/20
Siemens FI 01 · 2016
© Siemens AG 2016
Supplementary Components
Remote Data Manager
SITRANS RD500
■ Dimensional drawings
Mode of operation
Measuring principle
Remote data monitor
Measuring points
• Up to 128 standard inputs (conventional IO, see optional IO modules)
• Addressing for Modbus serial
devices (Modbus RTU and Modbus
TCP)
Input
See table on page 7/22
Output
See table on page 7/22
Accuracy
See table on page 7/22
Dimensions
78.5 (3.09)
Rated operating conditions
Storage temperature range
-30 … +70 ºC (-22 … +158 ºF)
Operating temperature
0 … 50 ºC (32 … 122 ºF)
Operating and storage humidity
80 % max relative humidity, non-condensing, from 0 … 50 °C
(32 … 122 °F)
105.4 (4.15)
134.7 (5.30)
■ Technical specifications
Design
Material (enclosure)
High impact plastic and stainless
steel
Installation category
I
Pollution degree
2
Weight
456.4 g (15.1 oz)
Mounting
Snaps onto standard DIN style top
hat (T) profile mounting rails according to EN 50022 – 35 x 7.5 and
– 35 x 15
Power
Mounting
Depress
24.5 (1) min.
clearance
3
4
24 V DC ± 10 %
400 mA min. (1 module)
DIN rail
3.5 amps max. (16 modules)
Must use Class 2 or SELV-rated
power supply
7
4
Display
Status LEDs
• STS - status LED indicates condition
of master
• TX/RX - transmit/receive LEDs show
serial activity
• Ethernet - link and activity LEDs
• CF - CompactFlash LED indicates
card status and read/write activity
24.5 (1) min.
clearance
SITRANS RD500, dimensions in mm (inch)
Memory
On-board user memory
4 MB of non-volatile Flash memory
On-board SDRAM
2 MB
Memory card
CompactFlash Type II slot for Type I
and Type II cards; 1 GB (optional
2 GB)
Certificates and approvals
Safety
• UL listed to U.S. and Canadian safety standards for use in Class I, II,
and III, Division 1 and 2 hazardous
locations
• CE, RCM
Communication
USB/PG port
Adheres to USB specifications 1.1.
Device only using Type B connection.
Serial ports
Format and baud rates for each port
are individually software programmable up to 115, 200 baud
RS232/PG port
RS 232 port via RJ12
Comms ports
RS 422/485 port via RJ45 and RS 232
port via RJ12
Ethernet port
10 BASE-T/100 BASE-TX; RJ45 jack
is wired as a NIC (Network Interface
Card)
Siemens FI 01 · 2016
7/21
© Siemens AG 2016
Supplementary Components
Remote Data Manager
SITRANS RD500
SITRANS RD500 Module Specifications
7
8 inputs, 6 solid
state outputs
8 inputs, 6 relay
outputs
8 channel,
4 … 20 mA
8 channel ± 10 V
6 channel, RTD
8 channel thermocouple module
Order number
7ML1930-1ES
7ML1930-1ER
7ML1930-1EP
7ML1930-1EQ
7ML1930-1ET
7ML1930-1EU
Application
8 inputs, 6 outputs
8 inputs, 6 outputs
16 bit analog input
used to monitor con- used to monitor con- module provides high
tact or sensor inputs tact or sensor inputs density signal measurement for data
monitoring applications and accepts
0/4 to 20 mA process signals
16 bit analog input
module provides high
density signal measurement for data
monitoring applications and accepts
± 10 V process
signals
16 bit analog input
module provides
high-density signal
measurement for
data acquisition
applications and
accepts various RTD
inputs
16 bit thermocouple
input module provides high density
signal measurement
for data acquisition
applications and
accepts wide range
of thermocouple
types
Accuracy
Not applicable
± 0.1 % of span
± (0.2 % of span,
1 °C) 0 … 50 °C
(32 … 122 °F);
± (0.1 % of span,
1 °C) 18 … 28 °C
(64 … 82 °F);
includes NIST conformity, A/D conversion
errors, temperature
coefficient and linearization conformity at
23 °C after
20 minutes warm-up
± (0.3 % of span,
1 °C); includes NIST
conformity, cold junction effect, A/D conversion errors,
temperature coefficient and linearization conformity at
23 °C after 20 minute
warm-up
Not applicable
± 0.1 % of span
Mounting
Snaps onto standard DIN style top hat (T) profile mounting rails according to EN 50022 – 35 x 7.5 and - 35 x 15
Inputs
Dip switch selectable for sink or
source
• Dip switch select- • 8 single-ended
• 8 single-ended
• 6 single-ended
• 8 single-ended
able for sink or
ranges: 0 … 20 mA
ranges:
resolution: full 16-bit resolution: full 16-bit
source
or 4 … 20 mA
0 … 10 V DC or
• Sample time:
• Sample time:
max. voltage:
resolution: full 16-bit ± 10 V DC
67 … 400 ms
50 … 400 ms
30 V DC, reverse
• Sample time:
resolution: full 16-bit depending on
depending on
polarity protected
50 … 400 ms
• Sample time:
number of enabled
number of enabled
Off voltage: < 1.2 V
depending on
50 … 400 ms
inputs
inputs
On voltage: > 3.8 V number of enabled
depending on
• Input frequency:
inputs
number of enabled
- Filter switch on:
inputs
50 Hz
- Filter switch off:
300 Hz
Outputs
Solid state output,
switched DC, contact rating 1 A DC
max.
Form A, NO
Not applicable
pairs share common
terminals:
1&, 3&4, 5&6
Current rating by
pair: 3 Amps at
30 V DC/125 V AC
resistive
1/10 HP at 125 V AC
Note:
For the secure operation of Siemens products and solutions, it is
necessary to take suitable preventive action (e.g. cell protection
concept) and integrate each component into a holistic, state-ofthe-art industrial security concept. Third-party products that may
be in use should also be considered.
For more information about industrial security, visit
http://www.siemens.com/industrialsecurity.
7/22
Siemens FI 01 · 2016
Not applicable
Not applicable
Not applicable
© Siemens AG 2016
Supplementary Components
Remote Data Manager
SITRANS RD500
Selection and Ordering data
Article No.
Selection and Ordering data
SITRANS RD500
The SITRANS RD500 is a remote data manager
providing integrated web access, alarm event handling and data capture for instrumentation.
7ML5750-
Additional Operating Instructions
77 A 0 0 - 0
RD500 Remote Data Manager manual, English:
web access, alarm event handling, and data capture
7ML1998-5MK01
RD500 Remote Data Manager manual, German:
web access, alarm event handling, and data capture
7ML1998-5MK31
RD500 8 channel 0 (4) ... 20 mA input module
manual, English
7ML1998-5MB01
RD500 8 channel 0 (4) ... 20 mA input module
manual, German
7ML1998-5MB31
RD500 8 channel ± 10 V input module manual,
English
7ML1998-5MC01
RD500 8 channel ± 10 V input module manual,
German
7ML1998-5MC31
RD500 8 inputs, 6 relay outputs module manual,
English
7ML1998-5MD01
RD500,8 inputs, 6 relay outputs module manual,
German
7ML1998-5MD31
RD500 8 inputs, 6 solid state outputs module
manual, English
7ML1998-5ME01
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Communications Connection
Ethernet1)
 1
Digital Communications to Instruments
RS 485 Modbus RTU and Modbus TCP

A
1)
Configuration limited to 16 modules.
 We can offer shorter delivery times for configurations designated with the
Quick Ship Symbol . For details see page 9/5 in the appendix.
Selection and Ordering data
Article No.
Input configuration modules
Note: one RD500 supports 16 input modules
maximum
Article No.
RD500 8 channel 0 (4) ... 20 mA input module
 7ML1930-1EP
RD500 8 channel ± 10 V input module
 7ML1930-1EQ
RD500 8 digital inputs/pulse counters, 6 relay
outputs module
 7ML1930-1ER
RD500 8 inputs, 6 solid state outputs module
manual, German
7ML1998-5ME31
RD500 8 digital inputs/pulse counters, 6 solid state  7ML1930-1ES
outputs module1)
RD500 6 channel input, RTD module manual,
English
7ML1998-5MF01
RD500 6 channel input, RTD module
 7ML1930-1ET
7ML1998-5MF31
RD500 8 channel thermocouple module
 7ML1930-1EU
RD500 6 channel input, RTD module manual,
German
RD500 8 channel thermocouple module manual,
English
7ML1998-5MJ01
RD500, 8 channel thermocouple module manual,
German
7ML1998-5MJ31
Optional equipment
External cellular modem
7ML1930-1GJ
Multitech cellular modem, internal (including
antennae)
7ML1930-1EY
Industrial CompactFlash card, 2 GB
7ML1930-1FB
Industrial CompactFlash card, 1 GB
7ML1930-1FC
RJ11 serial to terminal block RS 232
7ML1930-1FD
RJ45 serial to terminal block RS 485
7ML1930-1FE
GPRS Spare modem antenna
7ML1930-1FF
RD500 Spare Module base
7ML1930-1FG
RD500 Spare End terminator
7ML1930-1FH
Ethernet Cat 5e Red X/O cable for configuration,
1.52 m (5 ft)
7ML1930-1FM
USB cable type A/B
7ML1930-1FN
Remote mount external antenna 17 ft (5 m)
7ML1930-1FY
Accessories
SITRANS RD100, loop powered display - see
page 7/10
7ML5741-...
SITRANS RD200, universal input display with
Modbus conversion - see page 7/12
7ML5740-...
SITRANS RD300, dual line display with totalizer
and linearization curve and Modbus conversion see page 7/16
7ML5744-...
1)
Configuration limited to 16 modules
 We can offer shorter delivery times for configurations designated with the
Quick Ship Symbol . For details see page 9/5 in the appendix.
Operating Instructions
Application manual, English
7ML1998-5MA01
Application manual, German
Note: Operating Instructions should be ordered as a
separate line item.
All literature is available to download for free, in a
range of languages, at http://www.siemens.com/
processinstrumentation/documentation
This device is shipped with the Siemens Level and
Weighing manual DVD containing Quick Starts and
Operating Instructions.
7ML1998-5MA31
Siemens FI 01 · 2016
7/23
7
© Siemens AG 2016
Supplementary Components
Remote Data Manager
SITRANS RD500
■ Schematics
RD500 port pin outs
RS232
Power connection
RS 422/485
4-wire connections
1 COMMON
2 24 VDC ± 10 %
3 N/C
CTS (PIN 1)
Rx
COMM
COMM
Tx
RTS (PIN 6)
RS 485
2-wire connections
5V
5V
Power connector
7
130K
1
8
130K
2
USB/PG
130K
RS485
5V
130K
4 RxB
Rx
CTS (PIN 1)
Rx
COMM
COMM
Tx
RTS (PIN 6)
COMMS PORT
RS232
130K
6 GND
YELLOW
LED
ETHERNET (NIC)
Communication ports
Configuration ports
RS 232
MILLTRONICS BW500
RS232
USB/PG
A
M
RUN
PAR
ZERO
SPAN
ALT
DISP
RESET
TOTAL
CLEAR
ENTER
green/
amber LED
yellow LED
or
Ethernet (crossover)
RS 485
TxA
TxB
COMM
RxB
RxA
TxA
TxB
RS485
7
Ethernet connection (Port 3)
green/
amber LED
yellow LED
SITRANS RD500 connections
7/24
Siemens FI 01 · 2016
TxA
2
5 TxEN
(OC)
6 GND
Expansion
port
GREEN/
AMBER
LED
RTS
Tx
COMM
COMM
Rx
CTS
8
TxA
3 RxA
Common +24 V DC
TxB
1
5 TxEN
(OC)
TxB (PIN 1)
TxA
RxA
RxB
TxEN
COMM
TxB
TxA (PIN 8)
COMMS PORT
7
Tx/Rx
Tx
RS232/PG PORT
COMM
+24
N/C
130K
TxB
Standard ethernet cable