SITRANS I Supply Units, Isolators, Displays - Supplementary Components

7
© Siemens AG 2015
Supplementary Components
7/2
Product overview
7/4
7/7
Isolating power supplies and
Output isolators
SITRANS I100
SITRANS I200
7/10
7/12
7/16
Displays
SITRANS RD100
SITRANS RD200
SITRANS RD300
7/19
Remote data manager
SITRANS RD500
7/24
7/30
7/34
WirelessHART products
SITRANS AW200 - WirelessHART adapter
SITRANS AW210 - WirelessHART adapter
IE/WSN-PA LINK
You can download all instructions, catalogs and certificates for Supplementary
Components free of charge at
www.usa.siemens.com/level
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Supplementary Components
Product overview
■ Overview
Application
Description
Catalog Programming
page
Software
Isolating power supplies and Output isolators
Isolating power supply for
SITRANS I100
supplying 2- and 3-wire
Isolating power supply with HART for rail mounting,
transmitters and for connect- with intrinsically-safe input.
ing mA sources in the hazardous area
7/4
-
Output isolator for controlSITRANS I200
ling valve positioners,
Output isolator with HART for rail mounting, with
i/p converters or indicators in intrinsically-safe output
the hazardous area
7/7
-
Displays
7
2-wire loop powered,
NEMA 4X enclosed remote
digital display for process
instrumentation and for hazardous locations
SITRANS RD100
7/10
• Versatile loop-powered meter that displays process
variables in level, flow, pressure, temperature and
weighing applications
• FM and CSA approved device that can be installed
in a range of environments, including hazardous areas
• Large, easy-to-read display
• Easy to install and set up using quick two-step process
-
Universal input, panel mount
remote digital display for process instrumentation. Supports RTD, TC, current and
voltage inputs, and supporting software allows for
remote configuration and
data logging
SITRANS RD200
7/12
• Universal remote display that accepts various inputs, making it an ideal fit for use with most field instruments
• Standard panel mount display with optional enclosures
• Two optional relays for alarm indication or process
control applications
• Meter Copy feature to reduce setup time, cost and
errors
• RD Software supporting remote configuration,
monitoring and logging for up to 100 displays
-
A panel mount remote digital
display for process instrumentation and acts as a
multi-purpose, easy to use,
rate/totalizer ideal for flow
rate, total and control applications
SITRANS RD300
7/16
• A remote display for level, flow, pressure, weighing,
and other process instruments
• Acts as a multi-purpose, easy to use, rate/totalizer
ideal for flow rate, total, and control applications
• Data can be remotely collected, logged and presented on your local computer using the free downloadable RD software.
• Accepts a single or dual input of current and voltage
-
Remote data monitoring
providing integrated web
access, alarm event
handling, and data capture
for instrumentation
SITRANS RD500
7/19
• Supports up to 128 devices with the flexible I/O
modules and Modbus serial devices, including field
instruments
• Out- of-the-box operation, no software required,
works with standard web browser
• Support Ethernet, cellular and PSTN communication
• Data and alarming through FTP, Email, SMS,
HTML and Modbus TPC
• Up to 2 GB of data logging memory
-
Remote data manager
7/2
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Supplementary Components
Product overview
Application
Description
Catalog Programming
page
Software
WirelessHART products
WirelessHART adapter to
SITRANS AW200 - WirelessHART adapter
enable standard 4 ... 20 mA • Makes isolated information in
or HART devices to wireless
HART field instruments airborne
communication
• Permits predictive instead of preventive
maintenance strategies
• Enables 4 ... 20 mA or HART devices to
wireless communication
• Up to 4 HART devices can be connected
• Power up one connected field instrument
7/24
SIMATIC PDM
• Local with HART
modem
• Wireless via
WirelessHART
Explosion protected WireSITRANS AW210 - WirelessHART adapter
lessHART adapter to enable • Wireless transfer of the process variable of a
standard 4 ... 20 mA or HART
4 to 20 mA device via direct connection
devices to wireless commu• Wireless communication with up to 8 HART field
nication
devices in multidrop mode
• Suitable for use in explosion-protected areas
• Loop-powered or external power supply
• Supports burst mode and event notification for
adapters and connected devices
7/30
SIMATIC PDM
• Local with HART
modem
• Wireless via
WirelessHART
Gateway for the connection
of WirelessHART field
devices (HART V7.1) to
Industrial Ethernet.
IE/WSN-PA LINK
7/34
• Connection of up to 100 WirelessHART devices
• Approved for operation in hazardous areas in
Zone 2
• Open TCP/IP communication and Modbus TCP via
the Ethernet interface
• Can be used with HART-OPC servers of the
HART Communication Foundation
-
7
Siemens FI 01 · 2015 US Edition
7/3
© Siemens AG 2015
Supplementary Components
Isolating power supplies and Output isolators
SITRANS I100
■ Overview
Analog
input
SITRANS I100 isolating power supply, function block diagram
■ Technical specifications
SITRANS I100 Isolating Power Supplies with HART
Ex i input
Analog input 0/4 to 20 mA
The isolating power supplies are used for the intrinsically safe
operation of 2- and 3-wire transmitters and for connecting to intrinsically safe mA sources.
0/4 ... 20 mA with HART
Functional range
0 ... 24 mA
Max. input current for mA sources
50 mA
Transmitter supply voltage
 16 V at 20 mA (for 2-, 3-wire)
Supply voltage residual ripple
 25 mVeff
The 2- and 3-wire transmitters are supplied with auxiliary power
from the transmitter supply unit.
No-load voltage
 26 V
Short-circuit current
 35 mA
For 2-wire transmitters the isolators transfer the HART communication signal bidirectionally.
Input resistance (AC impedance
HART)
 500 
Input resistance for mA sources
30 
Communication signal (on 2-wire
transmitters)
Bidirectional HART transmission,
0.5 ... 30 kHz
■ Benefits
7
Input signal
• Active output 0/4 to 20 mA
• Suitable for 2-, 3-wire transmitters, 2-wire HART transmitters
and mA sources
• Intrinsically safe input [Ex ia] IIC
• Galvanic isolation between input, output and auxiliary power
• Open-circuit and short-circuit monitoring and messaging for
input and output (can be switched off)
• Installation possible in Zone 2 and Div. 2
• Can be used up to SIL 2 (IEC 61508)
Zones
Ex i interfaces
Installation in
0
1
2
20
21
22
X
X
X
X
X
X
X
X
■ Design
The HART isolating power supply is comprised of a compact
plastic enclosure (IP30) and is equipped with push-in screw
terminals.
Output
Output signal
0/4 ... 20 mA with HART
Load resistance RL
0 ... 600 W (terminal 1+/2-)
0 ... 379 W (terminal 3+/2-)
(with internal 221  resistance for
HART)
Residual ripple
 40 Aeff
No-load voltage
 15.5 V
Communication signal
Bidirectional HART transmission,
0.5 kHz ... 30 kHz
Response time (10 % ... 90 %)
 25 ms
Transfer behavior
Input/Output
1:1
(0 ... 20 mA --> 0 ... 20 mA,
4 ... 20 mA --> 4 ... 20 mA)
Measuring accuracy
Accuracy, typical data expressed
as % of calibrated span at UN,
23 °C
Linearity error
 0.1 %
On the front are a green LED for indicating the power supply
status and a red LED for signaling errors.
Offset error
 0.1 %
Temperature influence
 0.1 %/10 K
The auxiliary power supply can be connected individually using
push-in screw terminals or jointly for up to 40 units using pacBus.
Power supply effect within voltage
range
 0.01 %
Load resistance effect
 0.02 %
7/4
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Supplementary Components
Isolating power supplies and Output isolators
SITRANS I100
Error detection Ex i input
Rated conditions
Degree of protection of enclosure
IP30
• Open circuit
< 2 mA
Degree of protection of terminals
IP20
• Short-circuit
> 22 mA
• Output behavior
= Input signal
• Output current at Iin = 0
Iout = 0 mA
Ambient conditions
• Ambient temperature
-20 ... +60 °C/+70 °C
(-4 ... +140 °F/+158 °F)
(see "Operating instructions")
• Storage temperature
-40 ... +80 °C (-40 ... +176 °F)
• Relative humidity
(no condensation)
 95 %
Electromagnetic compatibility
Tested under the following standards and regulations:
EN 61326-1 Use in the industrial
environment
Error detection output
• Open circuit
< 2 mA
Error messaging Ex i input/output
• Settings (LF switch)
Activated/deactivated
• Error indication
LED red "LF"
Error messaging and power
supply failure
• Contact (30 V/100 mA), closed
to ground in case of error
• pac-Bus, floating contact
(30 V/100 mA)
Mechanical specifications
Screw terminals
Certificates and approvals
• One-wire connextion
Explosion protection ATEX
- Rigid
0.2 ... 2.5 mm2
(0.00031 ... 0.0039 in2)
- Flexible
0.2 ... 2.5 mm2
(0.00031 ... 0.0039 in2)
- Flexible with end ferrules
(without/with plastic ferrule)
0.25 ... 2.5 mm2
(0.00039 ... 0.0039 in2)
• Two-wire connection
0.2 ... 1
(0.00031 ... 0.00155 in2)
- Flexible
0.2 ... 1.5 mm2
(0.00031 ... 0.0023 in2)
- Flexible with end ferrules
0.25 ... 1 mm2
(0.00039 ... 0.00155 in2)
Type of installation
DMT 03 ATEX E 010 X
• Degree of protection
II 3 (1) G Ex nA nC [ia] IIC T4
II (1) D [Ex iaD]
Installation
In Zone 2, Div. 2 and in the safe
area
Other approvals
USA (FM)
Kanada (CSA)
Shipping (DNV)
mm2
- Rigid
Weight
• EC type-examination certificate
Approx. 160 g (0.35 lb)
On DIN rail according to
EN 50022 (NS35/15; NS35/7.5)
Mounting position
Vertical or horizontal
Enclosure material
PA 6.6
Fire protecting class (UL-94)
V0
Auxiliary power
Safety specifications (CENELEC)
• Max. voltage Uo
27 V
• Max. current Io
88 mA
• Max. power Po
576 mW
• Max. connectable capacitance
Co for IIC/IIB
90 nF/705 nF
• Max. connectable inductance
Lo for IIC/IIB
2.3 mH/14 mH
• Internal capacitance Ci
and inductance Li
Negligible
• Insulation voltage Um
253 V
7
• When connecting mA sources:
Rated voltage UN
24 V DC
Voltage range
18 ... 31.2 V
- Max. output voltage Uo
4.1 V
Residual ripple within voltage
range
 3.6 VSS
- Max. connectable voltage Ui
30 V
- Max. connectable current Ii
100 mA
Rated current (UN, 20 mA)
70 mA
Negligible
Power consumption (UN, 20 mA)
1.7 W
- Internal capacitance Ci and
inductance Li
Power loss (at UN, RL = 250 )
1.3 W
Operation indicator
Green "PWR" LED
Reverse polarity protection
Yes
Undervoltage monitoring
Yes (no faulty module/output
states)
• For more information and value
combinations
See "Certification"
Galvanic isolation
• Test voltage according to
EN 60079-11
- Ex i input to output
1.5 kV AC
- Ex i input to auxiliary power
1.5 kV AC
- Ex i input to Error contact
1.5 kV AC
• Test voltage according to
EN 50178
- Output to auxiliary power
350 V AC
- Error contact to auxiliary power
and output
350 V AC
Siemens FI 01 · 2015 US Edition
7/5
© Siemens AG 2015
Supplementary Components
Isolating power supplies and Output isolators
SITRANS I100
■ Selection and Ordering data
SITRANS I100 Isolating Power
Supply with HART
■ Schematics
Article No.
7NG4124-0AA00
Safe area
Hazardous area
For rail mounting, for supplying
2-/3-wire transmitters and for mA
sources, output 0/4 ... 20 mA, with
intrinsically safe input
Division 1
Zone 0/1
Division 2
Zone 2
pac-Bus
24 V
LF - +
9- 8 LF 24 V DC
7+
Accessories
pac-Bus basic set
With 5 single elements and 1 terminal set (beginning and end)
7NG4998-1AA
pac-Bus extension set
With 5 single elements
7NG4998-1AB
221 Ω
12+
I
P
1110
3+
21+
1
■ Dimensional drawings
Field device
108 (4.25)
99 (3.9)
17.6
(0.7)
Transmitter supply unit
HART SIL2
SITRANS I100 isolating power supply with HART, connection diagram
122 (4.8)
114.5 (4.5)
+
RL
SITRANS I100 isolating power supply with HART, output configuration
7
SITRANS I100 isolating power supply with HART, dimensions in mm
(inch)
7/6
SPS / PCS
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Supplementary Components
Isolating power supplies and Output isolators
SITRANS I200
■ Overview
■ Technical specifications
SITRANS I200 output isolator with HART
Input
Input signal
0/4 ... 20 mA with HART
Functional range
0 ... 24 mA
Max. input current
50 mA
Input resistance (changeable
switch LI)
225 /550 
Communication signal
Bidirectional HART transmission,
0.5 ... 30 kHz
Ex i output
Output signal
0/4 ... 20 mA with HART
Connectable load resistance
0 ... 800 
Min. load resistance for short-circuit
monitoring
150 
Residual ripple
 50 mV
Analog output 0/4 to 20 mA for HART
No-load voltage
 25.6 V
The output isolators are used for the intrinsically safe operation
of valve positioners, i/p converters or indicators.
Response time (10 % ... 90 %)
 25 ms
Transfer behavior
Input/Output
1:1
(0 ... 20 mA --> 0 ... 20 mA,
4 ... 20 mA --> 4 ... 20 mA)
Operation of intrinsically safe HART valve positioners (e.g.
SIPART PS2 and SITRANS VP300) is also possible. The units
transfer a superimposed HART communication signal bidirectionally.
■ Benefits
•
•
•
•
For HART output signals 0/4 to 20 mA
Intrinsically safe output [Ex ia] IIC
Galvanic isolation between input, output and auxiliary power
Open-circuit and short-circuit monitoring and messaging (can
be switched off)
• Installation possible in Zone 2 and Div. 2
• Can be used up to SIL 2 (IEC 61508)
Zones
Ex i interface
Installation in
0
1
2
20
21
22
X
X
X
X
X
X
X
Measuring accuracy
Accuracy, typical data expressed
as % of calibrated span at UN,
23 °C
Linearity error
 0.1 %
Offset error
 0.1 %
Temperature influence
 0.1 %/10 K
Power supply effect within voltage
range
 0.01 %
Load resistance effect
 0.02 %
Degree of protection of enclosure
IP30
Degree of protection of terminals
IP20
Ambient conditions
• Ambient temperature
-20 ... +70 °C (-4 ... +158 °F)
(see "Operating instructions")
• Storage temperature
-40 ... +80 °C (-40 ... +176 °F)
• Relative humidity (no condensation)
 95 %
Electromagnetic compatibility
Tested under the following standards and regulations:
EN 61326-1 Use in the industrial
environment
X
■ Design
The HART output isolator is comprised of a compact plastic
housing (IP30) and is equipped with push-in screw terminals.
On the front are a green LED for indicating the power supply status and a red LED for signaling errors.
7
Rated conditions
The auxiliary power supply can be connected individually using
push-in screw terminals or jointly for up to 40 units using
pac-Bus.
0/4 ... 20 mA
Analog
input
0/4 ... 20 mA HART
Analog
output
HART
Ex i
SITRANS I200 output isolator, function block diagram
Siemens FI 01 · 2015 US Edition
7/7
© Siemens AG 2015
Supplementary Components
Isolating power supplies and Output isolators
SITRANS I200
Mechanical specification
Certificates and approvals
Screw terminals
Explosion protection ATEX
• One-wire connection
• EC type-examination certificate
DMT 03 ATEX E 012 X
- Rigid
0.2 ... 2.5 mm2
(0.00031 ... 0.0039 in2)
• Degree of protection
II 3 (1) G Ex nA nC [ia] IIC T4
II (1) D [Ex iaD]
- Flexible
0.2 ... 2.5 mm2
(0.00031 ... 0.0039 in2)
Installation
In Zone 2, Div. 2 and in the safe
area
- Flexible with end ferrules
(without/with plastic ferrule)
0.25 ... 2.5 mm2
(0.00039 ... 0.0039 in2)
Other approvals
USA (FM)
Canada (CSA)
Shipping (DNV)
• Two-wire connection
0.2 ... 1 mm2
(0.00031 ... 0.00155 in2)
- Rigid
- Flexible
- Flexible with end ferrules
0.2 ... 1.5
(0.00031 ... 0.0023 in2)
25.6 V
• Max. current Io
96 mA
0.25 ... 1 mm2
(0.00039 ... 0.00155 in2)
• Max. power Po
605 mW
103 nF/800 nF
1.9 mH/11 mH
Weight
Approx. 160 g (0.35 lb)
• Max. connectable capacitance Co
for IIC/IIB
Type of installation
On DIN rail according to
EN 50022 (NS35/15; NS35/7.5)
• Max. connectable inductance Lo
for IIC/IIB
Mounting position
Vertical or horizontal
Enclosure material
PA 6.6
• Internal capacitance Ci and induc- Negligible
tance Li
Fire protecting class (UL-94)
V0
• Insulation voltage Um
Rated voltage UN
24 V DC
Voltage range
18 ... 31.2 V
Residual ripple within voltage
range
 3.6 VSS
Rated current (UN, 20 mA)
80 mA
Power consumption (UN, 20 mA)
1.3 W
Power loss (at UN, RL = 500 )
1.1 W
Operation indicator
Green "PWR" LED
Reverse polarity protection
Yes
Undervoltage monitoring
Yes (no faulty module/output
states)
Galvanic isolation
• Test voltage according to
EN 60079-11
- Ex i output to input
1.5 kV AC
- Ex i output to auxiliary power
1.5 kV AC
- Error contact to Ex i output
1.5 kV AC
• Test voltage according to
EN 50178
- Input to auxiliary power
350 V AC
- Error contact to auxiliary power
and input
350 V AC
Error detection Ex i output
• Open circuit
> 10 k
• Short-circuit
< 15 
• Input behavior
> 6 k
• Open-circuit detection only for
input current
 3.6 mA
• Settings (LF switch)
Activated/deactivated
• Error indication
LED red "LF"
• Error messaging and power
supply failure
• Contact (30 V/100 mA), closed
to ground in case of error
• pac-Bus, floating contact
(30 V/100 mA)
7/8
253 V
• For more information and value
combinations see "Certification".
Auxiliary power
7
Safety specifications (CENELEC)
• Max. voltage Uo
mm2
Siemens FI 01 · 2015 US Edition
■ Selection and Ordering data
SITRANS I200 output isolator
with HART
Article No.
7NG4131-0AA00
For rail mounting, input
0/4 ... 20 mA, output 0/4 ... 20 mA,
intrinsically safe
Accessories
pac-Bus basic set
With 5 single elements and 1
terminal set (beginning and end)
7NG4998-1AA
pac-Bus extension set
With 5 single elements
7NG4998-1AB
© Siemens AG 2015
Supplementary Components
Isolating power supplies and Output isolators
SITRANS I200
■ Dimensional drawings
108 (4.25)
17.6
(0.7)
122 (4.8)
114.5 (4.5)
99 (3.9)
SITRANS I200 output isolator with HART, dimensions in mm (inch)
■ Schematics
Safe area
Hazardous area
Division 1
Zone 0/1
Division 2
Zone 2
pac-Bus
V
LF 24
- +
9- 8 LF 24 V DC
7+ +
7
LI1
I
P
Field device
11-
2 -
10+
1 +
Isolating transformer
HART SIL2
SPS/PCS
SITRANS I200 output isolator with HART, connection diagram
Siemens FI 01 · 2015 US Edition
7/9
© Siemens AG 2015
Supplementary Components
Displays
SITRANS RD100
■ Overview
Power supply
External loop power supply
30 V DC max.
Display
• 1 inch (2.54 cm) high LCD
• Numeric range from
-1 000 … +1 999
Certificates and approvals
Hazardous
• Intrinsically Safe
• CSA/FM Class I, II, III, Div. 1,
Groups A, B, C, D, E, F, G T4
• CSA/FM Class I, Zone 0,
Group IIC
• Non-incendive
• CSA/FM Class I, Div. 2,
Groups A, B, C, D
• CSA/FM Class II and III, Div. 2,
Groups F and G
Options
Mounting
The SITRANS RD100 is a 2-wire loop powered, NEMA 4X enclosed remote digital display for process instrumentation.
■ Benefits
•
•
•
•
•
Easy setup
Approved for hazardous locations
NEMA 4X, IP67 impact-resistant enclosure
Simple two-step calibration
Two modes of input allow for easy servicing,
with no interruption of loop required
■ Application
7
The RD100 is very versatile. It can be installed indoors or outdoors, in hot or cold environments, and in safe or hazardous
areas.
It has been approved by FM and CSA as Intrinsically Safe and
non-incendive, and operates from -40 to +85 ºC
(-40 to +185 ºF), adding only 1 V to the loop.
The RD100 has a large 1 inch (2.54 cm) high display making it
easy to read.
Calibration consists of a quick, two-step process involving the
adjustment of only two non-interacting potentiometers.
Key Applications
Remotely displays process variables in level, flow, pressure,
temperature and weighing applications, in a 4 to 20 mA loop.
■ Technical specifications
Mode of operation
Measuring principle
Analog to digital conversion
Measuring range
4 … 20 mA
Measuring points
1 instrument only
Accuracy
 0.1 % of span  1 count
Rated operating conditions
Ambient conditions
• Operating temperature range
-40 … +85 ºC (-40 … +185 ºF)
Design
Weight
340 g (12 oz)
Material (enclosure)
Impact-resistant glass filled
polycarbonate body and clear
polycarbonate cover
Degree of protection
NEMA 4X, IP67
7/10
Siemens FI 01 · 2015 US Edition
• 2 inch (5.08 cm) pipe mounting
kit (zinc plated or stainless steel)
• Panel mounting kit
Selection and Ordering data
Article No.
SITRANS RD100
A 2-wire loop powered, NEMA 4X enclosed remote
digital display for process instrumentation.
7ML57417AA 0 0 - 0
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Conduit hole location (½ inch)
None
Bottom
Rear
Top
1
2
3
4
Selection and Ordering data
Article No.
Operating Instructions
English
French
German
Note: The Operating Instructions should be ordered
as a separate line item.
This device is shipped with the Siemens Milltronics
manual CD containing Quick Starts and Operating
Instructions.
Accessories
Panel mount kit
2 inch (5.08 cm) pipe mounting kit (zinc plated seal)
2 inch (5.08 cm) pipe mounting kit (stainless steel,
Type 304, EN 1.4301)
7ML1998-5JU01
7ML1998-5JU11
7ML1998-5JU31
7ML1930-1BN
7ML1930-1BP
7ML1930-1BQ
© Siemens AG 2015
Supplementary Components
Displays
SITRANS RD100
■ Dimensional drawings
RD100 - front view
RD100 - side view
Wall mounting
holes beneath
cover screws
E
F
A
C
D
B
A: 80 (3.15)
C: 60 (2.36)
E: 65 (2.56)
B: 140 (5.51)
D: 120 (4.72)
F: 20 (0.79)
SITRANS RD100, dimensions in mm (inch)
■ Schematics
Control loop connected to
input signal PCB
Calibrator connected to
input signal PCB
Input signal
PCB
Display PCB component side
(may be removed for bench calibration)
LO calibration control
HI calibration control
Balance control
(factory adjust only)
S-
Loop jumper
(remove when display PCB
is connected)
S+
-
Red
4-20 mA
S+ S-
S- S+
+
Transmitter
Loop jumper
+
Display PCB
component side
S+ S- S- S+
DP1
DP2
DP3
Black
-
Calibrated current
source
Calibrator connected to
display PCB
+
Power
supply
Field wiring is
made to the
Input Signal
PCB which is
mounted to the
base of the
enclosure.
DP1
DP2
DP3
S+
S-
Calibrated current
source
The display PCB may be removed from
the enclosure for bench calibration. Loop
jumper must be installed on input signal
PCB to maintain loop.
Refer to RD100 instruction manual for
more details.
Input signal PCB
(mounted to base
of enclosure)
SITRANS RD100 connections
Siemens FI 01 · 2015 US Edition
7/11
7
© Siemens AG 2015
Supplementary Components
Displays
SITRANS RD200
■ Overview
■ Technical specifications
Mode of operation
Measuring principle
Analog to digital conversion
Measuring points
• 1 instrument
• Remote monitoring of
100 instruments with PC and
RD software
Input
Measuring range
• Current
• 4 … 20 mA, 0 … 20 mA
• Voltage
• 0 … 10 V DC, 1 … 5 V, 0 … 5 V
• Thermocouple temperature
• Type J: -50 … +750 °C
(-58 … +1 382 °F)
• Type K: -50 … +1 260 °C
(-58 … +2 300 °F)
• Type E: -50 … +870 °C
(-58 … +1 578 °F)
• Type T: -180 … +371 °C
(-292 … +700 °F)
• Type T, 0.1 resolution:
-180.0 … +371 °C
(-199.9 … +700 °F)
• RTD temperature
• 100  RTD: -200 … +750 ºC
(-328 … +1 382 ºF)
The SITRANS RD200 is a universal input, panel mount remote
digital display for process instrumentation.
■ Benefits
7
• Easy setup and programming via front panel buttons or
remotely using RD software
• Display readable in sunlight
• Universal input: accepts current, voltage, thermocouple and
RTD signals
• Single or dual 24 V DC transmitter power supply
• Analog to Modbus RTU conversion as standard feature
• Two optional relays for alarm indication or process control
applications
• Linear or square root function supported
• Meter Copy feature to reduce setup time, cost or errors
• RD software supporting remote configuration, monitoring and
logging for up to 100 displays
• Other features include: 4 to 20 mA analog output option, supports pump alternation control, and optional NEMA 4 and 4X
FIELD ENCLOSURES
• Large display option for improved visibility at greater distances
Output signal
Output
• PDC output
• 4 … 20 mA (optional)
• Modbus RTU
Relays
2 SPDT Form C relays, rated
3 A at 30 V DC or 3 A at
250 V AC, non-inductive,
auto-initializing (optional)
Communications
• RS 232 with PDC or
Modbus RTU
• RS 422/485 with PDC or
Modbus RTU
Accuracy
4 … 20 mA optional output
 0.1 % FS  0.004 mA
Process input
 0.05 % of span  1 count,
square root: 10 … 100 % FS
Thermocouple temperature input
Data can be remotely collected, logged and presented from as
many as 100 displays on your local computer using the free
downloadable RD software.
• Type J:  1 °C ( 2 °F)
• Type K:  1 °C ( 2 °F)
• Type E:  1 °C ( 2 °F)
• Type T:  1 °C ( 2 °F)
• Type T, 0.1 Resolution:  1 °C
( 1.8 °F)
RTD temperature input
• 100  RTD:  1 °C ( 1 °F)
The display accepts a single input of current, voltage, thermocouple, and RTD. This makes the RD200 an ideal fit for use with
most field instruments.
Ambient conditions
■ Application
The RD200 is a universal remote display for level, flow, pressure,
temperature, weighing, and other process instruments.
The RD200 can be set up as a standard panel mount, or combined with optional enclosures to allow it to house up to
6 displays.
Key Applications
Rated operating conditions
Storage temperature range
-40 … +85 °C (-40 … +185 °F)
Operating temperature range
0 … 65 °C (32 … 149 °F)
Design
Weight
269 g (9.5 oz) (including options)
Material (enclosure)
• 1/8 DIN, high impact plastic,
UL94V-0, color: gray
• Optional plastic, steel and stainless steel (Type 304, EN 1.4301)
NEMA 4 enclosures
Degree of protection
Type 4X, NEMA 4X, IP65 (front
cover); panel gasket provided
Tank farms, pump alternation control, local or remote display of
level, temperature, flow, pressure and weighing instrument values, PC monitoring and data logging with RD software.
7/12
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Supplementary Components
Displays
SITRANS RD200
Electrical connection
• mA output signal
2-core copper conductor, twisted,
shielded, 0.82 … 3.30 mm²
(18 … 12 AWG), Belden 8 760 or
equivalent is acceptable
• Electrical connection and
relay connection
Copper conductor according to
local requirements,
rated 3 A at 250 V AC
Power supply
Input voltage option 1
85 … 265 V AC, 50/60 Hz;
90 … 265 V DC, 20 W max.
Input voltage option 2
12 … 36 V DC; 12 … 24 V AC,
6 W max.
Transmitter power supply
One or two isolated transmitter
power supplies (optional)
• Single power supply
One 24 V DC  10 % at
200 mA max.
• Dual power supplies
Two 24 V DC  10 % at
200 mA and 40 mA max.
External loop power supply
35 V DC max.
Output loop resistance
• 24 V DC, 10 … 700  max.
• 35 V DC (external),
100 … 1 200  max.
Displays and controls
Display
• 14 mm (0.56 inch) high LED
• 2X option for 30.5 mm (1.2 inch)
high, red LED
• Numeric range from
-1 999 … +9 999
• 4 digits, automatic lead zero
blanking
• 8 intensity levels
Memory
• Non-volatile
• Stores settings for minimum of
10 years if power is lost
Programming
• Primary: front panel
• Secondary: meter copy or PC
with SITRANS RD software
Certificates and approvals
CE, UL, CUL
7
Options
Enclosures
Plastic, steel and stainless steel
(Type 304, EN 1.4301) NEMA 4
and 4X enclosures
Mounting
• 2 inch (5.08 cm) pipe mounting
kit (zinc plated seal)
• 2 inch (5.08 cm) pipe mounting
kit (stainless steel, Type 304,
EN 1.4301)
Siemens FI 01 · 2015 US Edition
7/13
© Siemens AG 2015
Supplementary Components
Displays
SITRANS RD200
Selection and Ordering data
Article No.
Selection and Ordering data
SITRANS RD200
A universal input, panel mount remote digital display for process instrumentation.
7ML5740-
Accessories
77 7 77 - 7A
SITRANS RD200 copy cable 2.1 m (7 ft)
7ML1930-1BR
SITRANS RD200 RS 232 serial adapter (copy cable
included)
7ML1930-1BS
SITRANS RD200 RS 422/485 serial adapter
(copy cable included)
7ML1930-1BT
RS 232 to RS 422/485 isolated converter
7ML1930-1BU
RS 232 to RS 422/485 non-isolated converter
7ML1930-1BV
SITRANS RD200 RS 232 and RS 485 isolated
multi-input adapter board
7ML1930-1BW
USB to RS 422/485 isolated converter
7ML1930-1BX
USB to RS 422/485 non-isolated converter
7ML1930-1BY
USB to RS 232 converter
7ML1930-6AK
RD Software CD for 1 ... 100 displays
7ML1930-1CC
Low cost polycarbonate plastic enclosure for
1 display
2 inch (5.08 cm) pipe mounting kit (zinc plated
seal) only available with 7ML1930-1CF
2 inch (5.08 cm) pipe mounting kit (stainless steel,
Type 304, EN 1.4301) only available with
7ML1930-1CF
7ML1930-1CF
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Input voltage
85 ... 265 V AC, 50/60 Hz; 90 ... 265 V DC,
20 W max.
12 ... 36 V DC; 12 ... 24 V AC, 6 W max.
Transmitter supply
None
Single 24 V DC transmitter supply1)
Dual 24 V DC transmitter supply1)2)
Output
None
2 relays
4 ... 20 mA output
Communication
Modbus enabled
Approvals
CE, UL, CUL
1
2
A
B
C
A
B
C
0
1
Display Size
Standard
2X option for 30.5 mm (1.2 inch) high, red LED
0
1
7ML1930-1BP
7ML1930-1BQ
Thermoplastic enclosure
For use with 1 display
7ML1930-1CG
1)
Available with input voltage option 1 only
For use with 2 displays
7ML1930-1CH
2)
Available with output option C only
For use with 3 displays
7ML1930-1CJ
For use with 4 displays
7ML1930-1CK
For use with 5 displays
7ML1930-1CL
For use with 6 displays
7ML1930-1CM
Selection and Ordering data
Article No.
Operating Intructions
7
Article No.
English
7ML1998-5JS01
Spanish
7ML1998-5JS21
German
Note: The Operating Instructions should be ordered
as a separate line item.
This device is shipped with the Siemens Milltronics
manual CD containing Quick Starts and Operating
Instructions.
7ML1998-5JS31
Other Operating Instructions
Stainless steel enclosure (Type 304, EN 1.4301)
For use with 1 display
7ML1930-1CN
For use with 2 displays
7ML1930-1CP
For use with 3 displays
7ML1930-1CQ
For use with 4 displays
7ML1930-1CR
For use with 5 displays
7ML1930-1CS
For use with 6 displays
7ML1930-1CT
SITRANS RD Enclosures, English
7ML1998-5JX01
Steel enclosure
SITRANS RD Enclosures, German
7ML1998-5JX31
For use with 1 display
7ML1930-1CU
SITRANS RD Serial communications accessories,
English
A5E31979195
For use with 2 displays
7ML1930-1CV
For use with 3 displays
7ML1930-1CW
For use with 4 displays
7ML1930-1CX
SITRANS RD Serial communications accessories,
German
A5E31979197
SITRANS RD Software, English
7ML1998-5JW01
For use with 5 displays
7ML1930-1CY
7ML1998-5JW31
For use with 6 displays
7ML1930-1DA
SITRANS RD Software, German
7/14
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Supplementary Components
Displays
SITRANS RD200
■ Dimensional drawings
RD200 - side view
RD200 - t op view
Screw terminal
connector
[0.5 Nm (4.5 lb/in)
tightening torque]
64 (2.5)
62 (2.45)
45
(1.76)
92
(3.61)
81 (3.2)
15
(0.59)
119 (4.68)
91 (3.6)
SITRANS RD200, dimensions in mm (inch)
■ Schematics
RD200 connector labeling
Relay 2
6
5
Relay 1
4
3
2
24V OUT
1
2
POWER
1
NO NC COM NO NC COM P+
2
1
+
-
P-
RTD
TC
7
V+ mA+ EXC T+ COM
1
2
3
4
5
RTD TC
SIGNAL
Signal connector
Signal connector
mA+ EXC T+ COM
2
3
4
5
V+
1
TC
4 ... 20 mA output and input signal powered by meter
Signal connector
mA+ EXC T+ COM
2
3
4
5
RTD TC
+
SERIAL
Three-wire RTD
input connections
Thermocouple
input connections
V+
1
SWITCH
V+ mA+ EXC T+ COM
1
2
3
4
5
mA out
16
1+
5
24 V out
P1+ P1- P2+
4
3
2
P21
RTD TC
Switch
position
RTD
sensor
Switch
position
2-wire
4 ... 20 mA
transmitter
+
-
Remote display,
chart recorder
+
SITRANS RD200 connections
Siemens FI 01 · 2015 US Edition
7/15
© Siemens AG 2015
Supplementary Components
Displays
SITRANS RD300
■ Overview
■ Technical specifications
Mode of operation
Measuring principle
Analog to digital conversion
Measuring points
1 or 2 instruments
Input
Measuring range
• Current
• 4 … 20 mA, 0 … 20 mA
• Voltage
• 0 … 10 V DC, 1 … 5 V, 0 … 5 V
Output signal
The SITRANS RD300 is a panel mount remote digital display for
process instrumentation and acts as a multi-purpose, easy to
use, rate/totalizer ideal for flow rate, total, and control applications.
■ Benefits
7
• Easy setup and programming via front panel buttons or remotely using RD software
• Display readable in sunlight
• Input: accepts current and voltage
• Single or dual 24 V DC transmitter power supply
• Serial communication using built in protocol or Modbus RTU
• Supports up to 8 relays and 8 digital I/O for process control
and alarming
• 32-point linearization, square root or exponential linearization
• Multi-pump alternation control
• Supports total, grand total or non-resettable grand total
• 9-digit totalizer with total overflow feature
• Large dual-line 6-digit display
• Configure, monitor, and datalog from a PC
• Dual-input option with math functions: addition, difference,
average, multiplication, division, minimum, maximum,
weighted average, ratio, concentration
■ Application
The RD300 is a remote display for level, flow, pressure, weighing, and other process instruments. This display also acts as a
multi-purpose, easy to use rate/totalizer ideal for flow rate, total,
and control applications.
Data can be remotely collected, logged and presented on your
local computer using the free downloadable RD software.
The display accepts a single or dual input of current and voltage.
This makes the RD300 an ideal fit for use with most field instruments.
The RD300 can be set up as a standard panel mount, or combined with optional enclosures to allow it to house up to 6 displays.
Output
• 4 … 20 mA (optional)
• Modbus RTU
Relays
2 or 4 SPDT (Form C) internal
and/or 4 SPST (Form A) external;
rated 3 A at 30 VDC and 125/250
VAC resistive load; 1/14 HP
(50 W) at 125/250 V AC for
inductive loads (optional)
Communications
• RS 232 with Modbus RTU
• RS 422/485 with Modbus RTU
Accuracy
4 … 20 mA optional output
 0.1 % FS  0.004 mA
Process input
 0.05 % of span  1 count,
square root: 10 … 100 % FS
Rated operating conditions
Ambient conditions
Storage temperature range
-40 … +85 °C (-40 … +185 °F)
Operating temperature range
0 … 65 °C (32 … 149 °F)
Design
Weight
269 g (9.5 oz) (including options)
Material (enclosure)
• 1/8 DIN, high impact plastic,
UL94V-0, color: gray
• Optional plastic, steel and stainless steel (Type 304, EN 1.4301)
NEMA 4 enclosures
Degree of protection
Type 4X, NEMA 4X, IP65 (front
cover); panel gasket provided
Electrical connection
mA output signal
2-core copper conductor, twisted,
shielded, 0.82 … 3.30 mm²
(18 … 12 AWG), Belden 8 760 or
equivalent is acceptable
Electrical connection and
relay connection
Copper conductor according to
local requirements,
rated 3 A at 250 V AC
Power supply
Input voltage option
85 … 265 V AC, 50/60 Hz;
90 … 265 V DC, 20 W max. or
jumper selectable 12/24 V DC
± 10 %, 15 W max.
Transmitter power supply
Terminals P+ & P-: 24 V DC
± 10 %, 12/24 V DC powered
models selectable for 24, 10, or
5 V DC supply (internal jumper
J4), 85 ... 265 V AC models rated
at 200 mA max, 12/24 V DC powered models rated at 100 mA
max, at 50 mA max. for 5 or
10 V DC supply.
External loop power supply
35 V DC max.
Output loop resistance
• 24 V DC, 10 … 700  max.
• 35 V DC (external),
100 … 1 200  max.
Key Applications
Tank farms, pump alternation control, local or remote display of
level, flow, pressure and weighing instrument values, PC monitoring and data logging with RD software.
7/16
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Supplementary Components
Displays
SITRANS RD300
Article No.
Selection and Ordering data
Displays and controls
Main Display
0.6 inch (15 mm) high, red LEDs
Operating Intructions
Second display
0.46 inch (12 mm) high, red
LEDs, 6-digits: each
(-99 999 ... 999 999)
Single input process and flow rate/totalizer Mtr
• Non-volatile
• Stores settings for minimum of
10 years if power is lost
Memory
Programming
• Primary: front panel
• Secondary: meter copy or PC
with SITRANS RD software
Certificates and approvals
English
A5E31917845
French
A5E31948924
German
A5E31948919
Dual input process Mtr
English
A5E33481367
German
A5E33481387
Note: The operating instructions should be ordered
as a separate line on the order.
CE, UL, CUL
Options
Other Operating Instructions
Enclosures
Plastic, steel and stainless steel
(Type 304, EN 1.4301) NEMA 4
and 4X enclosures
SITRANS RD DIN-Rail Mounting Kit, English
A5E31979181
SITRANS RD DIN-Rail Mounting Kit, German
A5E31979184
SITRANS RD Expansion Modules, English
A5E31979173
Selection and Ordering data
Article No.
SITRANS RD Expansion Modules, German
A5E31979176
SITRANS RD300
Dual line Remote digital display compatible with
PI instruments
7ML5744-
SITRANS RD Serial Communications Accessories,
English
A5E31979195
SITRANS RD Serial Communications Accessories,
German
A5E31979197
7 7 7 7 7 - 00 A
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Input voltage
85 ... 265 V AC, 50/60 Hz; 90 ... 265 V DC,
20 W max.
12 ... 36 V DC; 12 ... 24 V AC, 6 W max.
Output
None
2 Relays
4 Relays
4 ... 20 mA output
2 Relays and 4 ... 20 mA output
4 Relays and 4 ... 20 mA output
Accessories
DIN-Rail Mounting Kit
7ML1930-6AB
1
4 Relays Expansion Module
7ML1930-6AC
2
4 Digital I/O Module
7ML1930-6AD
Dual output 4 ... 20mA expansion module for dual
input meter
7ML1930-6AP
Meter Copy Cable
7ML1930-6AE
RS 232 Serial Adapter
7ML1930-6AF
RS 422/485 Serial Adapter
7ML1930-6AG
RD300 USB Serial Adapter
7ML1930-6AJ
USB to RS 232 Converter
7ML1930-6AK
Snubber
7ML1930-6AL
A
B
C
D
E
F
Type
Single input process and flow rate/totalizer Mtr
Dual input process Mtr
Display
Standard
SunBright
A
B
Plastic enclosure
0
1
Approvals
UL & C-UL & CE
0
For 1 meter
7ML1930-6AM
For 2 meters
7ML1930-6AN
For 4 meters
7ML1930-1CK
For 5 meters
7ML1930-1CL
For 6 meters
7ML1930-1CM
■ Dimensional drawings
NO NC C NO NC C
NO NC C NO NC C
-
+ R
Optional
connectors
installed
44.5
(1.76)
62
(2.45)
106
(4.17)
15
(0.59)
121
(4.77)
128
(5.05)
91.5
(3.61)
152 (6) Clearance
119
(4.68)
SITRANS RD300, dimensions in mm (inch)
Siemens FI 01 · 2015 US Edition
7/17
7
© Siemens AG 2015
Supplementary Components
Displays
SITRANS RD300
■ Schematics
Connector labeling for fully loaded single input meter
RELAY2
RELAY1
MA OUT
6
RELAY4
5
4
3
RELAY3
2
1
6
5
4
3
2
1
3
2
1
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
I-
I+
R
P+
P-
F4
COM
V+
mA+
1
2
3
4
5
6
1 2 3 4 5 6 7 8
SIGNAL
DW1815
M-LINK
+
-
1
2
POWER
Transmitter powered by external supply or self-powered
INPUT SIGNAL
INPUT SIGNAL
P+
P-
F4
COM
V+
mA+
P+
P-
F4
COM
V+
mA+
1
2
3
4
5
6
1
2
3
4
5
6
+
+
External
Power
Supply
-
-
2-Wire
4 ... 20 mA
Transmitter
+
2-Wire 4 ... 20 mA
Self-Powered
Transmitter
Transmitter powered by internal supply
7
INPUT SIGNAL
INPUT SIGNAL
P+
P-
F4
COM
V+
mA+
P+
P-
F4
COM
V+
mA+
1
2
3
4
5
6
1
2
3
4
5
6
+
+
-
2-Wire
4 ... 20 mA
Transmitter
-
Signal
3-Wire 4 ... 20 mA
Transmitter
Voltage Input Connections
INPUT SIGNAL
INPUT SIGNAL
P+
P-
F4
COM
V+
mA+
P+
P-
F4
COM
V+
mA+
1
2
3
4
5
6
1
2
3
4
5
6
-
+
Voltage
Signal
+
SITRANS RD300 connections
7/18
-
3-Wire Voltage
Transducer
Siemens FI 01 · 2015 US Edition
Signal
© Siemens AG 2015
Supplementary Components
Remote data manager
SITRANS RD500
■ Overview
■ Benefits
The SITRANS RD500 is a remote data manager providing
remote monitoring through integrated web access, alarm event
handling, and data capture for instrumentation and other devices.
• RD500 supports report and alarm events via email, SMS, and
FTP transfer
• Web provides worldwide access to instrument data and
RD500 configuration and setup
• Simple configuration using a standard web browser,
no programming or additional software required
• Offers scalability with optional I/O modules for current
(4 to 20 mA), voltage (0 to 10 V), thermocouple (TC),
resistance temperature detector (RTD), and digital input,
output and counter
• 10 base-TI 100 Base-TX Ethernet and support for GSM,
GPRS, 3G, and PSTN provide flexible remote communications
options
• Supports up to 128 devices with the flexible I/O modules and
supports addressing for Modbus serial devices via RS 232
and RS 485 serial ports
• Integrated FTP server and client supports FTP data synchronization to central servers
• Compact flash slot supports up to 2 gigabytes of expandable
memory for data capture and storage, 1 gigabyte industrial
compact flash card included
• Log files formats are CSV (comma separated values) for
data files and HTML for report files
• Supports modbus TCP via Ethernet and GPRS for
easy integration into control systems
• Optional 3G modem offers VPN support
■ Application
The RD500 is an easy-to-use remote data monitoring solution,
using a web-based application and hardware modules. The
unique modular approach allows a variety of process signals to
be monitored, while the serial ports allow data to be collected
from Modbus RTU devices.
The RD500 comprises a master communications module, and
up to 16 slave modules. Various module types are available, allowing up to a maximum of 128 conventional inputs and outputs.
The RD500’s serial ports can support addressing for
Modbus RTU slave devices including field instruments.
The RD500’s built-in web server, FTP, and email client allows the
process to be monitored remotely. Alarm notifications are communicated through email and SMS text messages to one or more
recipients to ensure that appropriate actions are taken by personnel.
The RD500 supports modems, providing flexibility for applications in which GSM/GPRS/3G cellular or landline connectivity is
desired.
The RD500 is configured via a web-based interface - a standard
browser is all the software you need to configure your system.
Key Applications
Remote monitoring, inventory management, web enabled instrumentation or other devices remote configuration and maintenance devices
WWW
With SITRANS RD500, monitor inventory levels, process, environmental, and remote maintenance
applications, and get web access to most types of field instrumentation, including flow, level, pressure,
temperature measurement, and weighing.
Siemens FI 01 · 2015 US Edition
7/19
7
© Siemens AG 2015
Supplementary Components
Remote data manager
SITRANS RD500
■ Technical specifications
Communication
Mode of operation
USB/PG port
Adheres to USB specifications
1.1. Device only using Type B
connection.
Measuring principle
Remote data monitor
Measuring points
• Up to 128 standard input/
outputs
• Addressing for Modbus serial
devices
Serial ports
Format and baud rates for each
port are individually software programmable up to 115 200 baud
RS 232/PG port
RS 232 port via RJ12
Input
See table on page 7/21
Comms ports
Output
See table on page 7/21
RS 422/485 port via RJ45 and
RS 232 port via RJ 12
Accuracy
See table on page 7/21
Ethernet port
10 BASE-T/100 BASE-TX; RJ45
jack is wired as a NIC (Network
Interface Card)
Rated operating conditions
Storage temperature range
-30 … +70 ºC (-22 … +158 ºF)
Operating temperature
0 … 50 ºC (32 … 122 ºF)
Operating and storage humidity
80 % max relative humidity,
non-condensing, from 0 … 50 °C
(32 … 122 °F)
Dimensions
78.5 (3.09)
Material (enclosure)
High impact plastic and
stainless steel
Installation category
I
Pollution degree
2
Weight
456.4 g (15.1 oz)
Mounting
Snaps onto standard DIN style
top hat (T) profile mounting rails
according to EN 50022
– 35 x 7.5 and – 35 x 15
Power
24 V DC  10 %
400 mA min. (1 module)
3.5 Amps max. (16 modules)
Must use Class 2 or SELV-rated
power supply
105.4 (4.15)
134.7 (5.30)
Design
7
■ Dimensional drawings
Display
Status LEDs
• STS - status LED indicates condition of master
• TX/RX - transmit/receive LEDs
show serial activity
• Ethernet - link and activity LEDs
• CF - CompactFlash LED indicates card status and read/write
activity
Mounting
Depress
24.5 (1) min.
clearance
3
4
Memory
On-board user memory
4 Mbytes of non-volatile Flash
memory
On-board SDRAM
2 Mbytes
Memory card
CompactFlash Type II slot for
Type I and Type II cards;
1 Gbytes (optional 2 Gbytes)
DIN rail
4
24.5 (1) min.
clearance
Certificates and approvals
Safety
7/20
• UL listed to U.S. and Canadian
safety standards for use in
Class I, II and III, Division 1 and
2 hazardous locations
• CE, RCM
Siemens FI 01 · 2015 US Edition
SITRANS RD500, dimensions in mm (inch)
© Siemens AG 2015
Supplementary Components
Remote data manager
SITRANS RD500
SITRANS RD500 Module Specifications
8 inputs, 6 solid
state outputs
8 inputs,
6 relay outputs
8 channel,
4 … 20 mA
8 channel  10 V
6 channel, RTD
8 channel thermocouple module
Article number
7ML1930-1ES
7ML1930-1ER
7ML1930-1EP
7ML1930-1EQ
7ML1930-1ET
7ML1930-1EU
Application
8 inputs, 6 outputs
used to monitor
contact or sensor
inputs
8 inputs, 6 outputs
used to monitor
contact or sensor
inputs
16 bit analog input
module provides
high density signal
measurement for
data monitoring
applications and
accepts
0/4 … 20 mA
process signals
16 bit analog input
module provides
high density signal
measurement for
data monitoring
applications and
accepts  10 V
process signals
16 bit analog input
module provides
high-density signal
measurement for
data acquisition
applications and
accepts various
RTD inputs
16 bit thermocouple input module
provides high density signal measurement for data
acquisition applications and accepts
wide range of thermocouple types
Accuracy
Not applicable
Not applicable
 0.1 % of span
 0.1 % of span
 (0.2 % of span,
1 °C) 0 … 50 °C
(32 … 122 °F);
 (0.1 % of span,
1 °C) 18 … 28 °C
(64 … 82 °F);
includes NIST conformity, A/D conversion errors,
temperature coefficient and linearization conformity at
23 °C after
20 minutes warmup
 (0.3 % of span,
1 °C); includes
NIST conformity,
cold junction effect,
A/D conversion
errors, temperature
coefficient and linearization conformity at 23 °C after
20 minute warm-up
Mounting
Snaps onto standard DIN style top hat (T) profile mounting rails according to EN 50022 – 35 x 7.5 and - 35 x 15
Inputs
Dip switch selectable for sink or
source
Outputs
Solid state output,
switched DC, contact rating 1 A DC
max.
Dip switch selectable for sink or
source
Max. voltage
• 30 V DC,
reverse polarity
protected
Off voltage
• < 1.2 V
On voltage
• > 3.8 V
Input frequency
• Filter switch on:
50 Hz
• Filter switch off:
300 Hz
8 single-ended
Ranges
• 0 … 20 mA or
4 … 20 mA
Resolution
• full 16-bit
Sample time
• 50 … 400 ms
depending on
number of enabled inputs
8 single-ended
Ranges
• 0 … 10 V DC or
 10 V DC
Resolution
• full 16-bit
Sample time
• 50 … 400 ms
depending on
number of enabled inputs
6 single-ended
Resolution
• full 16-bit
Sample time
• 67 … 400 ms
depending on
number of enabled inputs
Form A, NO
pairs share common terminals:
1 & 2, 3 & 4, 5 & 6
current rating by
pair: 3 Amps at
30 V DC/125 V AC
resistive
1/10 HP at
125 V AC
Not applicable
Not applicable
Not applicable
8 single-ended
Resolution
• full 16-bit
Sample time
• 50 … 400 ms
depending on
number of enabled inputs
7
Not applicable
Note:
To ensure the secure operation of a plant or machine it is necessary to take additional, suitable preventive action (e.g. cell protection concept) and to integrate the automation and drive components into a state-of-the-art holistic industrial security concept
for the entire plant or machine. Please find further information at:
http://www.siemens.com/industrialsecurity
Siemens FI 01 · 2015 US Edition
7/21
© Siemens AG 2015
Supplementary Components
Remote data manager
SITRANS RD500
Selection and Ordering data
Article No.
Selection and Ordering data
SITRANS RD500
The SITRANS RD500 is a remote data manager
providing integrated web access, alarm event handling and data capture for instrumentation.
7ML5750-
Other Operating Instructions
77 A 0 0 - 0
RD500 Remote Data Manager manual, English:
web access, alarm event handling, and data capture
7ML1998-5MK01
RD500 Remote Data Manager manual, German:
web access, alarm event handling, and data capture
7ML1998-5MK31
RD500 8 channel 0 (4) ... 20 mA input module
manual, English
7ML1998-5MB01
RD500 8 channel 0 (4) ... 20 mA input module
manual, German
7ML1998-5MB31
RD500 8 channel ± 10 V input module manual,
English
7ML1998-5MC01
RD500 8 channel ± 10 V input module manual,
German
7ML1998-5MC31
RD500 8 inputs, 6 relay outputs module manual,
English
7ML1998-5MD01
RD500,8 inputs, 6 relay outputs module manual,
German
7ML1998-5MD31
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Communications Connection
Ethernet1)
Digital Communications to Instruments
RS 485 Modbus RTU
1)
1
A
Configuration limited to 16 modules.
Selection and Ordering data
Article No.
Input configuration modules
Note: one RD500 supports 16 input modules maximum
RD500 8 channel 0 (4) ... 20 mA input module
7ML1930-1EP
RD500 8 channel ± 10 V input module
7ML1930-1EQ
7ML1930-1ER
RD500 8 inputs, 6 solid state outputs module
manual, English
7ML1998-5ME01
RD500 8 digital inputs/pulse counters, 6 relay
outputs module
7ML1930-1ES
RD500 8 inputs, 6 solid state outputs module
manual, German
7ML1998-5ME31
RD500 8 digital inputs/pulse counters, 6 solid state
outputs module
7ML1930-1ET
RD500 6 channel input, RTD module manual,
English
7ML1998-5MF01
RD500 6 channel input, RTD module
RD500 8 channel thermocouple module
7ML1930-1EU
RD500 6 channel input, RTD module manual,
German
7ML1998-5MF31
3G external ethernet modem with antennae
MTCBA-H4-EN2-P1
7ML1930-1GJ
RD500 8 channel thermocouple module manual,
English
7ML1998-5MJ01
Multitech GPRS modem, internal (including
antennae)
7ML1930-1EY
RD500, 8 channel thermocouple module manual,
German
7ML1998-5MJ31
Industrial CompactFlash card, 2 GB
7ML1930-1FB
Industrial CompactFlash card, 1 GB1)
7ML1930-1FC
RJ11 serial to terminal block RS 232
7ML1930-1FD
RJ45 serial to terminal block RS 485
7ML1930-1FE
GPRS Spare modem antenna
7ML1930-1FF
RD500 Spare Module base
RD500 Spare End terminator
Ethernet Cat 5e Red X/O cable for configuration,
1.52 m (5 ft)
7ML1930-1FM
USB cable type A/B
7ML1930-1FN
Remote mount external antenna 17 ft (5 m)
7ML1930-1FY
Optional equipment
7
Article No.
SITRANS RD100, loop powered display - see
page 7/10
7ML5741-...
SITRANS RD200, universal input display with
Modbus conversion - see page 7/12
7ML5740-...
7ML5744-...
7ML1930-1FG
SITRANS RD300, dual line display with totalizer
and linearization curve and Modbus conversion see page 7/16
7ML1930-1FH
1)
Operating Instructions
Application manual, English
7ML1998-5MA01
Application manual, German
Note: Additional Operating Instructions should be
ordered as a separate line item.
This device is shipped with the Siemens Milltronics
manual CD containing Quick Starts and Operating
Instructions.
7ML1998-5MA31
7/22
Siemens FI 01 · 2015 US Edition
Accessories
1 Gbyte industrial grade compact flash card included
© Siemens AG 2015
Supplementary Components
Remote data manager
SITRANS RD500
■ Schematics
RD500 port pin outs
RS232
Power connection
RS 422/485
4-wire connections
1 COMMON
2 24 VDC ± 10 %
3 N/C
CTS (PIN 1)
Rx
COMM
COMM
Tx
RTS (PIN 6)
RS 485
2-wire connections
5V
5V
Power connector
7
130K
1
8
130K
2
USB/PG
TxB
1
8
TxA
130K
5 TxEN
(OC)
TxB (PIN 1)
TxA
RxA
RxB
TxEN
COMM
TxB
TxA (PIN 8)
COMMS PORT
7
Tx/Rx
Tx
RS232/PG PORT
TxA
2
5 TxEN
(OC)
6 GND
Expansion
port
RS485
COMM
+24
N/C
130K
TxB
5V
130K
4 RxB
Rx
3 RxA
130K
RS232
Common +24 V DC
CTS (PIN 1)
Rx
COMM
COMM
Tx
RTS (PIN 6)
COMMS PORT
6 GND
GREEN/
AMBER
LED
YELLOW
LED
ETHERNET (NIC)
Communication ports
Configuration ports
RS 232
MILLTRONICS BW500
USB/PG
RS232
RTS
Tx
COMM
COMM
Rx
CTS
A
M
RUN
PAR
ZERO
SPAN
ALT
DISP
RESET
TOTAL
CLEAR
ENTER
green/
amber LED
yellow LED
7
or
Ethernet (crossover)
TxA
TxB
COMM
RxB
RxA
TxA
TxB
RS485
RS 485
Ethernet connection (Port 3)
green/
amber LED
yellow LED
Standard ethernet cable
SITRANS RD500 connections
Siemens FI 01 · 2015 US Edition
7/23
© Siemens AG 2015
Supplementary Components
WirelessHART products
SITRANS AW200 - WirelessHART adapter
■ Overview
■ Application
SITRANS AW200 WirelessHART adapter
The SITRANS AW200 WirelessHART adapter is a batterypowered communication component, which integrates HART
and 4 to 20 mA field devices into a WirelessHART network. On
the wireless communication side, the adapter supports the WirelessHART standard. HART and 4 to 20 mA field devices are connected on the field device side.
7
The SITRANS AW200 WirelessHART adapter
• Support the WirelessHART standard (HART V 7.1)
• Fatures a very high degree of security for wireless data transmission
• Integrates one 4 to 20 mA field device or up to four HART field
devices (in multidrop mode) into a WirelessHART network
• Features intelligent energy management for the power supply
of connected field devices
• Can be easily parameterized using SIMATIC PDM
The WirelessHART adapter can be used in a number of different
applications, e.g.
• Access to installed basis
Diagnostic information is obtained from existing wired HART
devices through a permanent electrical connection of a WirelessHART adapter, and is sent to an asset management software near the system, e.g. SITRANS MDS.
• Status monitoring of the plant
Wireless devices are mounted at critical points in the plant,
which are not usually connected to the control room due to difficult accessibility or extensive costs for wiring. Better data
flow and diagnostics increase the system’s reliability, transparency and safety.
• Process optimization
A temporary installation of a standard 4 to 20mA or HART device together with the WirelessHART adapter SITRANS AW200
allows flexible monitoring and plant optimization at lower costs
and reduced effort.
• Process monitoring
Measured values from e.g. tanks or silos are transmitted to a
superordinate system in regular time intervals, together with
the device and battery status.
■ Design
The SITRANS AW200 WirelessHART adapter consists of
• A housing with mounted antenna
• Electronics
• A high-performance lithium battery unit
4
3
2
1
■ Benefits
• High quality and service life
• Save on wiring costs for difficult installation conditions
(e.g. moveable equipment parts) or for temporary installations
• Subsequent integration of an installed field device with HART
interface into maintenance and diagnostic systems if the control system does not feature the required communication
mechanisms. This application is described in Section 8 of this
catalogue under "WirelessHART - Technical Description".
• Proven HART devices can continue to be used for wireless
communication, without any limitations .
• Field devices with a 4 to 20 mA interface (without HART) can
also be connected.
• Intelligent energy management to achieve the best possible
life time for the installed battery unit.
• Optimum addition to wired communication and expansion of
solution options for system solutions in process automation.
• Burst mode and event notification parameterization for the
adapter and connected field devices.
6
1
2
3
4
5
6
LED
Push button
Plug to connect battery
Battery compartment
Terminals 1 to 6
Terminals for HART modem
5
SITRANS AW200 WirelessHART adapter, assembly
The housing can be opened by loosening 4 screws. This allows
to access the electronics and battery unit. The battery unit can
be removed without the use of tools, since it is connected to the
housing with clips.
The back of the housing features a connection part with a fixing
nut onto which different replaceable connecting pieces can be
screwed to mount the adapter directly on a field device.
The bottom of the housing contains an optional cable opening
which can be used for a cable gland. In the case of an offset
mounted adapter, it is possible to feed up to 2 cables.
7/24
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Supplementary Components
WirelessHART products
SITRANS AW200 - WirelessHART adapter
■ Function
Interface
ES
OS
MS
Industrial Ethernet
SIMATIC
system
SITRANS
AW200
Connection
Function
1
Power supply for the field device
2
HART/4 ... 20 mA
3
External supply/Dimensions
4
High-resistance HART connection
5, 7
High-resistance HART connection
6, 8
Mass, high-resistance connection
Terminal block with 6 screw connection clamps
Parameterization
The SITRANS AW200 configured via HART. This can be done using a handheld communicator or even more conveniently with a
HART modem and the SIMATIC PDM parameterization software.
SIMATIC ET 200
with HART support
Wireless
HART
IE/WSNPA LINK
Initial start-up of the adapter is usually carried out via
SIMATIC PDM and HART modem or a handheld communicator.
During initial start-up, the network ID and join key is set up in the
adapter, among others. Using these parameters, the adapter is
then integrated into an existing WirelessHART network.
Once it is integrated into the network, the adapter and connected HART devices can be conveniently operated via the
WirelessHART network or with the onsite HART modem.
Siemens HART field devices for the adapter
SITRANS SITRANS
P280
TF280
PROFIBUS
DP/PA
LINK
HART and 4 to 20mA field devices can be connected to the
SITRANS AW200 WirelessHART adapter. Depending on the
electrical data of the field devices, they can receive their power
supply from the WirelessHART adapter or will require an external
power supply. Please find current information about connectivity
to field devices from Siemens as FAQ under
http://www.siemens.com/automation/service&support.
PROFIBUS PA
Note:
SITRANS AW200 WirelessHART adapter functional diagram
Measured values and diagnostic information of connected field
devices with HART communication are transmitted via a wired
connection to the WirelessHART adapter. The adapter transmits
this information in the form of wireless signals to the
IE/WSN-PA LINK, the Siemens WirelessHART gateway. From
here, the information is available to the network of the system.
Where a field device with a 4 to 20 mA output signal is connected to the adapter, only the measured value will be transmitted.
Siemens will only approve the Siemens HART field devices listed
there for the adapter, and will only supply technical support for
these devices.
Based on HART specifications, it is generally possible to connect devices that are not listed, however with the following limitations:
• All warranties and liabilities will be excluded.
• No technical support
Following parameterization and integration into a WirelessHART
network, each WirelessHART adapter is able to recognize its
neighbors. It notes the strength of the wireless signal, synchronizes itself, receives network information and then establishes
connections to the neighbors in the wireless network. A WirelessHART network organizes itself. Manual settings for organizational purposes are not required.
Two- and four-wire field devices can be connected to a WirelessHART adapter. In the case of a connected two-wire field device, power can be supplied by the adapter. Where multiple twowire field devices are connected (multi drop operation), the
adapter must be connected to an external power supply.
The WirelessHART adapter may also be connected in parallel to
an already existing installation which consists of a power supply
and a HART field device.
Siemens FI 01 · 2015 US Edition
7/25
7
© Siemens AG 2015
Supplementary Components
WirelessHART products
SITRANS AW200 - WirelessHART adapter
■ Technical specifications
Input
Design
Input
Communication
Point-to-Point connection to a
HART field device or
Point-to-Point connection to a
4 ... 20 mA field device or
Up to four HART field devices
with external power supply which
are integrated using the multidrop
method
Weight
HART communication using multidrop method, 4 ... 20 mA power
signal with Point-to-Point connection
Enclosure
• Material
Polyester (PBT FR)
• Cable entry
2x M20x1.5
Degree of protection
IP65, IP66; NEMA 4
Antenna
Omnidirectional dipolar aerial,
vertical rotation
Mounting adapter
M20 x 1.5 on M20 x 1.5,
M20 x 1.5 on G½,
M20 x 1.5 on ½"- 14 NPT,
M20 x 1.5 on ¾" -14 NPT
Protocol
HART V7 (compatible with previous HART versions)
Transfer rate
1200 bits/s using HART multidrop method
Battery
Lithium thionylchlorid high-performance battery unit
WirelessHART V7
Supply voltage
5 ... 7.2 V DC
Nominal 250 kBits/s
Capacity
19 Ah at 20 °C
Transmission frequency band
2.4 GHz (ISM band)
Service life
Range (under reference conditions)
Outside areas up to 250 m, within
buildings up to 50 m
Up to 5 years, depending on
update rate, connected field
device and ambient conditions
RF signal strength
Can be configured: 0 dBm and
10 dBm
Power supply
Output
Communication
Transfer rate
Output signals
• WirelessHART adapter
7
0.5 kg without battery, 0.75 kg
with battery
Measured voltage and up to three
other variables may be selected
from the following: adapter temperature, battery voltage, energy
consumed, expected battery life
time
• 4 ... 20 mA field device
Scaled or linearized process values
• HART field device
Up to four process variables, can
be configured via PDM or gateway
Measuring accuracy
(as per reference conditions
IEC 61298-2)
0.125 % re: measuring range
Effect of ambient temperature
(4 ... 20 mA circuit)
5 µA/10 K
Rated conditions
Outside/Inside
Ambient conditions
• Ambient temperature
-40 ... +80 °C (-40 ... +176 °F)
The capacity of the battery
decreases rapidly if ambient temperature falls below -30 °C.
• Storage temperature
-40 ... +85 °C (-40 ... +185 °F)
without batteries
< 21 °C with batteries
• Relative humidity
Max 90 % at 25 °C
(non-condensating)
• Resistance to vibration
20  f  2000 Hz: 0,01 g²/Hz as
per IEC 68-2-64
• Shock resistance
15 g, 11 ms as per IEC 68-2-27
Electromagnetic compatibility
As per EN 61326,
EN 301 489-1/17 and
NAMUR NE 21
7/26
• No-load voltage
8 ... 23 V DC
• Current
4 ... 20 mA DC (as per NAMUR
recommendation NE 43)
• Fault current
I  3.6 mA or I  21 mA
• Protection
Short-circuit proof, activated at
voltages > 25 mA
External voltage supply for one or
more field devices (multidrop)
• Voltage
< 30 V DC
• Current
< 25 mA
Certificates and approvals
Wireless communication approvals
Max. measuring error
(4 ... 20 mA circuit)
Location
Voltage supply for one field device
(independent of multidrop)
Siemens FI 01 · 2015 US Edition
ETSI (R&TTE)
FCC Part 15.247 for wireless
applications in the 2.4 GHz transmission frequency band
EN 300328
© Siemens AG 2015
Supplementary Components
WirelessHART products
SITRANS AW200 - WirelessHART adapter
Selection and ordering data
Article No.
SITRANS AW200
adapter for WirelessHART
communication
7 MP 3 1 1 2 - 7777 0 - 0 AA 0
Click on the Article No. for the
online configuration in the PIA Life
Cycle Portal.
WirelessHART adapter AW200 with
4 ... 20 mA- or HART interface
Without battery
Power supply
Battery powered
1
A
Certificates and approvals1)
Without
A
Enclosure
Polyester
0
Accessories
Lithium battery for SITRANS AW200
7MP3990-0AA00
Thread adapter for direct mounting of the
adapter to a field device
• M20 thread adapter
• Thread adapter G½
• Thread adapter ½" - 14 NPT
• Thread adapter ¾" - 14 NPT
7MP3990-0BA00
7MP3990-0BB00
7MP3990-0BC00
7MP3990-0BD00
Mounting bracket for attaching to
wall/pipe, material: stainless steel
SS304, including cable gland
7MP3990-0CA00
1)
Additional approvals in process.
7
Siemens FI 01 · 2015 US Edition
7/27
© Siemens AG 2015
Supplementary Components
WirelessHART products
SITRANS AW200 - WirelessHART adapter
192 (75.6)
12.5 (4.9)
88.5 (34.8)
182.5 (71.9)
88.5 (34.8)
138.3 (54.4)
31 (12.2)
■ Dimensional drawings
7
28
(12.2)
26 (10.2)
91 (35.8)
100.6 (12.2)
SITRANS AW200 WirelessHART adapter, dimensions in mm (inch)
7/28
Siemens FI 01 · 2015 US Edition
110.4 (43.5)
© Siemens AG 2015
Supplementary Components
WirelessHART products
SITRANS AW200 - WirelessHART adapter
SITRANS AW200 with built-in mounting bracket for wall or pipe mounting
■ Schematics
Power supply (DC) without
communication resistance
WirelessHART adapter
with terminals 1 to 6
1
2
3
4
5
6
WirelessHART adapter
with terminals 1 to 6
Field
device
1
2
3
4
5
Connection of a two-wire field device with external power supply
6
Field device with
power supply
Connection of a four-wire field device
7
Field device
Connection of a two-wire field device, power supply provided by adapter
WirelessHART adapter
with terminals 1 to 6
1 2 3 4 5 6
1 2 3 4 5 6
WirelessHART
adapter with
terminals 1 to 6
Controls with
communication
resistance
Field
device
Connection of adapter parallel to wired 4 to 20 mA communication
Siemens FI 01 · 2015 US Edition
7/29
© Siemens AG 2015
Supplementary Components
WirelessHART products
SITRANS AW210 - WirelessHART adapter
■ Overview
■ Application
SITRANS AW210 WirelessHART adapter
The WirelessHART adapter SITRANS AW210 is a communication component which can integrate a wide range of field
devices into a WirelessHART network. On the wireless communication side, the adapter supports the WirelessHART standard.
HART and 4 to 20 mA field devices are connected on the field
device side.
7
The WirelessHART adapter SITRANS AW210
• Supports the WirelessHART standard (HART V 7.1)
• Features an extremely high degree of security for wireless
data transmission.
• Integrates a 4 to 20 mA field device into a WirelessHART
network
• Integrates up to eight HART field devices (in multidrop mode)
into a WirelessHART network
• Can be powered with the 4 to 20 mA loop or an external power
supply
• Power management can be activated to minimize energy
consumption
• Easy to configure with SIMATIC PDM, AMS, Handheld 475.
The WirelessHART adapter can be used in a number of different
applications:
• Access to installed basis
Diagnostic information is obtained from existing wired HART
devices thanks to the permanent electrical connection of a
WirelessHART adapter and power from the 4 to 20 mA loop.
This information is sent to central system-based asset management software such as SITRANS MDS.
• Status monitoring of the plant
Wireless devices are mounted at critical points in the plant
which are not usually connected to the control room due to difficult access or high wiring costs. Better data flow and diagnostics increase plant reliability, transparency and safety.
• Process optimization
Temporary installation of a 4 to 20mA or standard HART device together with a SITRANS AW210 WirelessHART adapter
allows easier, flexible monitoring and plant optimization at
lower costs. SITRANS AW210 can also be usefully used where
there is already an external power supply, or one is needed
anyway.
• Process monitoring
Measured values, for example from tanks or silos, are transmitted to a higher-level system at regular intervals together
with the device status. SITRANS AW210 is particularly easy to
use with 4-wire devices, as they have an external power supply.
■ Design
SITRANS AW210 WirelessHART Adapter consists of:
• An enclosure with a fitted aerial
• Electronics
2
1
3
■ Benefits
•
•
•
•
•
•
•
•
•
"Intrinsically safe" or "Explosion proof"
High quality and service life
Extremely rugged enclosure
No additional cabling required with loop power supply
Subsequent integration of an installed field device with HART
interface into maintenance and diagnostic systems if the control system does not feature the required communication
mechanisms
Proven HART devices can continue to be used for wireless
communication without any limitations
Field devices with a 4 to 20 mA interface (without HART) can
also be connected
Ideal addition to wired communication and to the range of
system solutions in process automation
Burst mode and event notification configuration for the
adapter and connected field devices
7/30
Siemens FI 01 · 2015 US Edition
1 Ground connection
2 Enclosure with potted aerial
3 ½" NPT screw connection
SITRANS AW210 Wireless-HART Adapter, assembly
The enclosure contains the potted electronics and the wireless
module. The aerial is fitted at the top in the enclosure.
On the base of the enclosure is the connector with a ½" NPT female thread. Six cables run from this connector to connect the
adapter.
© Siemens AG 2015
Supplementary Components
WirelessHART products
SITRANS AW210 - WirelessHART adapter
Parameter assignment
■ Function
ES
OS
SITRANS AW210 is configured via HART. Configuration can be
carried out using handheld communicator 475 or, more conveniently, with a HART modem and the SIMATIC PDM configuration
software.
MS
Industrial Ethernet
SITRANS
AW210
SIMATIC
system
SITRANS
AW200
Following integration into the network, the adapter and HART devices connected can be conveniently operated via the WirelessHART network or locally, as detailed above.
SIMATIC ET 200
with HART support
Wireless
HART
Initial startup of the adapter is usually carried out via
SIMATIC PDM and a HART modem or a handheld communicator. During initial startup, the network ID and join key are set in
the adapter. These parameters are used to integrate the adapter
into an existing WirelessHART network.
IE/WSNPA LINK
Siemens HART field devices for the adapter
In principle, all HART devices certified by the
HART Communication Foundation (HCF) can be operated with
the SITRANS AW210 WirelessHART adapter. See
http://www.siemens.com/automation/service&support for FAQ
with the latest information on connectivity for Siemens field devices.
Note:
SITRANS SITRANS
P280
TF280
DP/PA
LINK
PROFIBUS
SITRANS
AW210
PROFIBUS PA
SITRANS AW210 WirelessHART Adapter, functional diagram
The measured values and diagnostic information from the connected field devices with HART communication are transmitted
to the WirelessHART adapter over wired connections. The
adapter transmits this information as wireless signals to the
IE/WSN-PA link, the Siemens WirelessHART gateway. The measured values, all parameters and diagnostic information about
the plant network can be accessed from this gateway.
If a field device with a 4 to 20 mA output signal is connected to
the adapter, the current will be converted to a digital measured
value and transmitted on the basis of a measuring range specified in SITRANS AW210.
Following configuration and integration into a WirelessHART network, each WirelessHART adapter is able to recognize its neighbors. It notes the strength of the wireless signal, synchronizes itself, receives network information and then establishes
connections to its neighbors in the wireless network. A WirelessHART network organizes itself. Manual settings for organization are not required.
Two-wire and four-wire field devices can be connected to a WirelessHART adapter. Either up to 2 or up to 8 HART field devices
can be connected to the adapter, depending on the selected
product version. The adapter either has an external voltage supply or is loop-powered. The WirelessHART adapter can therefore
also be connected in parallel to an existing installation consisting of a voltage supply and a HART field device.
Siemens has only approved the Siemens HART field devices
listed there for the adapter, and will only provide technical support for these devices.
Based on HART specifications, it is generally possible to connect devices that are not listed, however with the following
restrictions:
• All warranties and liability will be excluded
• No technical support
■ Technical specifications
Input
Point-to-point connection to a
HART field device or
Point-to-point connection to a
4 ... 20 mA field device or
Up to eight HART field devices
with an external voltage supply
integrated using multidrop
Communication
• HART communication with multidrop, as primary or secondary
HART master (can be specified)
• 4 ... 20 mA current signal with a
point-to-point connection scaling in user-defined measuring
range in SITRANS AW210
- Linear
- User-defined scaling with up to
32 points
Protocol
HART V7 (compatible with previous HART versions)
Siemens FI 01 · 2015 US Edition
7/31
7
© Siemens AG 2015
Supplementary Components
WirelessHART products
SITRANS AW210 - WirelessHART adapter
Output
Certificates and approvals
Communication
WirelessHART V7
Transmission frequency band
2.4 … 2.4835 GHz (ISM band),
16-channel frequency hopping
spread spectrum
Range (under reference conditions)
Outside up to 235 m (771 ft)
RF signal strength
10 dBm
Output signals
• WirelessHART adapter
7
• HART Cmd 3
Measured current and up to 4
other dynamic variables (measured values, derived values) or
device variables
• HART Cmd 9
Up to 8 dynamic variables with
status
• HART Cmd 48
Additional status information
• 4 ... 20 mA field device
Scaled or linearized process values
• HART field device
• HART Cmd 3
Measured current and up to 4
other dynamic variables (measured values, derived values) or
device variables
• HART Cmd 9
Up to 8 dynamic variables with
status
• HART Cmd 48
Additional status information
Update time for output signals
You can set the update times separately for the adapter and the
connected devices.
The possible settings are:
• 1, 2, 4, 8, 16, 32 s
• 1, 2, 5, 10, 30, 60 min (times also
depend on the gateway)
Wireless communication approvals
Explosion protection
Intrinsic safe "i" gases and
vapors
II 1G Ex ia IIC T*; IP68
T* = T5 for Ta = -40 ... +85 °C
T* = T6 for Ta = -40 ... +75 °C
Intrinsic safe dust
II 1 D Ex iaD 20 IP68 T95C;
Ta = -40 ... +85 °C
Non-sparking (zone 2)
II 3 G Ex nA nC IIC T* Gc; IP68
T* = T5 for Ta = -40 ... +85 °C
T* = T6 for Ta = -40 ... +75 °C
Explosion protection to FM for US
Intrinsic safe, Non-sparking
IS/I,II,III/1/ABCDEFG/
T5 Ta = -40 ... +85 °C,
T6 Ta = -40 ... +75 °C
NI/I/2/ABCD/
T5 Ta = -40 ... +85 °C,
T6 Ta = -40 ... +75 °C
S/II,III/2/EFG/
T5 Ta = -40 ... +85 °C,
T6 Ta = -40 ... +75 °C
I/0/AEx ia/IIC/
T5 Ta = -40 ... +85 °C
T6 Ta = -40 ... +75 °C;
20/AEx iaD/T95°C;
Ta = -40 ... 85°C
I/2/AEx nA nC/IIC/
T5 Ta = -40 ... +85 °C,
T6 Ta = -40 ... +75 °C; IP68
Explosion protection to FM for CA
Intrinsic safe, Non-sparking
IS/I,II,III/1/ABCDEFG/
T5 Ta = -40 ... +85 °C
T6 Ta = -40 ... +75 °C;
NI/I/2/ABCD/
T5 Ta = -40 ... +85 °C
T6 Ta = -40 ... +75 °C;
S/II,III/2/EFG/
T5 Ta = -40 ... +85 °C
T6 Ta = -40 ... +75 °C;
I/0/Ex ia/IIC/
T5 Ta = -40 ... +85 °C
T6 Ta = -40 ... +75 °C;
I/2/Ex nA nC/IIC/
T5 Ta = -40 ... +85 °C
T6 Ta = -40 ... +75 °C
II/1/EFG Ta = -40 ... +85°C; IP68
Flameproof gases and vapors
II 2 G Ex d IIC T* Gb; IP68
T* = T5 for Ta = -40 ... +85 °C
T* = T6 for Ta = -40 ... +75 °C
Protection by enclosure dust
II 2 D Ex tb IIIC T95°C
Ta = -40 ... +85°C; IP68
Explosion protection to FM for US
Explosionproof, flameproof, gas,
dust
XP/I/1/ABCD
I/1 AEx d IIC T5, T6 Gb
DIP/II,III/1/EFG
21/AEx tb IIIC T95°C
T5 Ta = -40 ... +85°C,
T6 Ta = -40 ... +75°C
Type 6P, IP68
Explosion protection to FM for CA
Explosionproof, flameproof, gas,
dust
XP/I/1/ABCD
I/1 Ex d IIC T5, T6 Gb
DIP/II,III/1/EFG
T5 Ta = -40 ... +85°C,
T6 Ta = -40 ... +75°C
Measuring accuracy
Max. measuring error
(4 ... 20 mA circuit)
1 % of measuring range,
40 … 85 °C (104 … 185 °F)
Rated conditions
Location
Outside/inside
Ambient conditions
• Ambient temperature
-40 ... +85 °C (-40 ... +185 °F)
In hazardous areas up to 75 °C
(167 °F)
• Storage temperature
-40 ... +85 °C (-40 ... +185 °F)
Electromagnetic compatibility
To EN 301 489-17 and
EN 300 328-1
Design
Weight
0.46 kg (1.01 lb)
Enclosure
• Material
- Enclosure
Aluminum alloy, RoHS-compliant
polyurethane corrosion-resistant
coating
- Cap
Resin
• Cable entry
½" NPT female thread
Degree of protection
IP68
Aerial
Potted in enclosure
Auxiliary power
Power supply
Loop power 1 … DC 2.5 V,
can be set by user in 0.5 V DC
increments
Loop-powered, operating current
DC 3.2 … 25 mA operating current; overvoltage, surge and
reverse polarity protection
7/32
Siemens FI 01 · 2015 US Edition
• CE (R&TTE, EMC)
• FCC Part 15.247 for wireless applications in the 2.4 GHz transmission frequency band
• IC
© Siemens AG 2015
Supplementary Components
WirelessHART products
SITRANS AW210 - WirelessHART adapter
■ Schematics
Selection and ordering data
Article No.
SITRANS AW210
Adapter for WirelessHART
communication
7 MP 3 1 1 1 - 7777 0 - 0 AA 0
SITRANS AW2101)
Click on the Article No. for the
online configuration in the PIA Life
Cycle Portal.
Black/direct supply
24 V
Red/loop power
WirelessHART-Adapter AW210 with
4 ... 20 mA- or HART interface
White/return line
2 devices
1
8 devices
2
Yellow/HART
Green and yellow/internal ground
Auxiliary Power
A
Loop powered or 24 V DC (external)
Certificates and approvals
Field device
Intrinsically safe gas, vapors and dust
(ATEX) , Intrinsic Safe (FM)
B
Explosionproof gas, vapour and dust
(ATEX), Explosionproof (FM)
C
1)
Device control switch is on.
External 24 V DC power supply, connection of one device
Enclosure
0
Aluminum
SITRANS AW2101)
Accessories
Thread adapter M20x1.5 (male
thread) on ½-14 NPT (female thread)
IP65, not explosion proof
7MP1990-0BA00
Black/direct supply
24 V
Red/loop power
White/return line
Yellow/HART
■ Dimensional drawings
Green and yellow/internal ground
60.70 (2.39)
Field device
1)
7
Device control switch is on.
113.79 (4.48)
External 24 V DC power supply, connection of multiple devices
SITRANS AW2101)
Black/direct supply
24 V
21.08
(0.83)
250 Ω
Red/loop power
White/return line
4 ... 20 mA
250 Ω
Yellow/HART
Green and yellow/internal ground
SITRANS AW210 WirelessHART adapter, dimensions in mm (inches)
Field device
1)
Device control switch has no effect.
Loop power for connection of one 4 ... 20 mA HART device
Siemens FI 01 · 2015 US Edition
7/33
© Siemens AG 2015
Supplementary Components
WirelessHART products
IE/WSN-PA LINK
■ Overview
■ Application
The IE/WSN-PA LINK connects wireless HART field devices by
radio to the Ethernet. On the radio side, the IE/WSN-PA LINK
supports the WirelessHART standard and on the Ethernet side
the TCP/IP and Modbus TCP communication.
The IE/WSN-PA LINK thus enables wireless diagnostics, maintenance and process monitoring.
Monitoring
WirelessHART is particularly suitable for use in plant sections
that are to be included in monitoring, but which do not have any
existing MSR cabling, e.g. external tank stores or other installations where high cabling costs are anticipated. Data for the visualization can be retrieved from the IE/WSN-PA link via Industrial
Ethernet or Modbus TCP.
ES
• The IE/WSN-PA LINK is a network transition for the connection
of WirelessHART field devices (HART V7.1) to Industrial Ethernet, as an alternative or supplement to the wired connection.
• Connection of up to 100 WirelessHART devices
• Approved for operation in hazardous areas in Zone 2
• Open TCP/IP communication and Modbus TCP via the Ethernet interface
• Can be used with HART-OPC servers of the HART Communication Foundation
OS
MS
Industrial Ethernet
SIMATIC
system
SITRANS
AW200
Note:
A general introduction to WirelessHART and information on the WirelessHART adapter and the WirelessHART field devices can be found in
Catalog FI 01 or on the Internet at http://www.siemens.com/wirelesshart
Wireless
HART
■ Benefits
• Extended possible solutions for connecting process industry
field devices by means of alternative or supplementary WirelessHART communication
• Reliable data transmission using intermeshed network technology; the self-organizing network with alternative paths enables radio obstacles to be bypassed
• Reduction of cabling costs under difficult installation conditions, e.g. if the field devices are located on inaccessible plant
components or are only required temporarily
• To improve process monitoring and for maintenance tasks,
sensors can be retrofitted
• Existing transmitters can be integrated wirelessly into maintenance and diagnostics systems by means of WirelessHART
adapters
• Without additional software, restricted monitoring is possible
via web services and the integrated web server of the IE/WSNPA LINK.
IE/WSNPA LINK
DP/PA
LINK
SITRANS SITRANS
P280
TF280
PROFIBUS
7
SIMATIC ET 200
with HART support
PROFIBUS PA
Monitoring of process states via WirelessHART
Retrofitting for diagnostics and maintenance
For this application, wireless adapters are looped into the 420 mA interface or screwed directly onto the HART device. The
acyclic HART message frames are transmitted by radio between
IE/WSN-PA LINK and a wireless adapter. Without affecting the
operation of the plant, the wireless adapter modulates the acyclic HART message frames to the 4-20 mA interface or extracts
them from the 4-20 mA interface.
The IE/WSN-PA LINK collects the data of all wireless adapters
and transfers it via Industrial Ethernet to the diagnostics and
maintenance station.
If greater distances between the IE/WSN-PA LINK and the monitoring station are to be spanned without cabling, this can be implemented by means of Industrial Wireless LAN with the access
points and client modules of the SCALANCE W family.
7/34
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Supplementary Components
WirelessHART products
IE/WSN-PA LINK
■ Function
SITRANS
MDS
OS
WirelessHART
The IE/WSN-PA LINK establishes on the radio side an intermeshed wireless sensor network for communication with wireless field devices (e.g. transmitters). The data from the wireless
field devices is received by the IE/WSN-PA LINK and transmitted
via Industrial Ethernet to the connected systems. The supported
wireless network is an open wireless network specified by the
HART Communication Foundation (HCF) in accordance with the
WirelessHART (HART V7.1) standard.
Industrial Ethernet
Controller without
HART support
SITRANS
AW200
On the field device side, the IE/WSN-PA LINK requires field devices that support WirelessHART (HART). Existing field devices
can be integrated by means of wireless adapters into the WirelessHART communication. To this end, the adapters are looped
into the 4-20 mA interface. In addition, as many as four standard
HART field devices with external power supply can be connected to the adapter in multidrop mode. Individually connected
devices can be operated with the battery of the adapter.
4–20 mA
IEEE 802.11
4–20 mA
Wireless
HART
The adapter wirelessly transmits all data and process values of
the connected devices. The advantage of this solution is that
tried and tested devices can continue to be used.
Industrial
Ethernet
Industrial Ethernet
IE/WSNPA LINK
G_IK10_XX_30348
4–20 mA
PROFIBUS
Remote I/O station
w/o HART support
Retrofitting of plants for diagnostics and maintenance
Via the Ethernet interface the IE/WSN-PA LINK supports the use
of the HART OPC server and the Modbus TCP protocol.
Configuration
The configuration is web-based, without additional software, and
performed from the PC. By means of the web user interface it is
also possible to display the device states and measured values
of the WirelessHART devices.
Increased availability of WirelessHART application due to redundancy mode
• 2 x 10/100/1 000 Mbit/s RJ45 ports, electrical (no integral switch;
interfaces can be used, for example, for continuous connection
to the plant network as well as the temporary connection of a PC)
• 1 x screw terminal for connection to Modbus RTU via RS 485
• 1 x screw terminal for the 24 V DC connection
• Rugged metal enclosure with IP65 protection for use outdoors, also in hazardous zone 2
• Mounting: wall or mast mounting (vertical);
U-bolts for mast mounting are included in the scope of delivery.
Product versions
• With integral, non-detachable antenna
• Redundancy function and with N connector for connection of
an external antenna
For increased availability requirements, the link can be used redundantly. The redundancy function is only available for the device variant with a connection for an external antenna.
Two links are connected to the same Ethernet subnet via a
switch to provide the redundancy. The two links are connected
to each other via an Ethernet cable (management coupling).
One of the two links is configured as the active device. It carries
out the communication between the control center and the WirelessHART wireless network under normal conditions. The second link is configured identically. It is used as a standby device.
In a redundancy scenario, the standby device becomes the active device.
SITRANS
P280
Control center
SITRANS
P280
P2
WirelessHart
SITRANS
TF280
SITRANS
TF280
SITRANS
AW200
SITRANS
TF280
SITRANS
AW200
IE/WSN-PA
LINK
P1
P2
IE/WSN-PA
LINK
P1
SCALANCE
X208
WirelessHART – Wireless connection
Industrial Ethernet
Management – Coupling between redundant
gateways
G_IK10_XX_30298
■ Design
WirelessHART network operated with a redundant gateway
Siemens FI 01 · 2015 US Edition
7/35
7
© Siemens AG 2015
Supplementary Components
WirelessHART products
IE/WSN-PA LINK
■ Integration
■ Technical specifications
Integration into automation systems
The IE/WSN-PA LINK can be integrated into automation systems
via Ethernet or Modbus TCP. Communication modules
(CP 343-1 or CP 443-1) are required to connect the IE/WSN-PA
LINK to SIMATIC S7-300/400. Function blocks and technical
support can be found at:
www.siemens.com/simatic-net/ik-info
Integration in PCS 7
For integration of the IE/WSN-PA LINK into PCS 7 you can obtain
function blocks and technical support at:
www.siemens.com/simatic-net/ik-info
7
7/36
Siemens FI 01 · 2015 US Edition
Article No.
Product type designation
Transfer rate
• at the interface 1
• at the interface 2
• at the interface 3
Interfaces
Number of electrical connections
• at interface 1 in accordance with
Industrial Ethernet
• at interface 2 in accordance with
Industrial Ethernet
• at interface 3 in accordance with
RS 485
• For power supply
Design of electrical connection
• at interface 1 in accordance with
Industrial Ethernet
• at interface 2 in accordance with
Industrial Ethernet
• at interface 3 in accordance with
RS 485
• For power supply
Interfaces wireless
Number of radio cards permanently installed
Number of internal antennas
Number of electrical connections
for external antenna(s)
Design of electrical connection for
external antenna(s)
Supply voltage, current consumption, power loss
Type of power supply
Supply voltage, external
• Minimum
• Maximum
Current consumed from external
power supply at 24 V DC, maximum
Active power loss, maximum
Permitted ambient conditions
Ambient temperature
• During operating
• During storage
• During transport
Relative humidity at 25 °C without
condensation during operating
phase, maximum
Protection class IP
Design, dimensions and weights
Width of the housing
Height of the enclosure
• Without antenna
• With antenna
Depth of the housing
Net weight
Mounting type
• Wall mounting
• Mast mounting
Mounting type
6GK14116GK14116CA40-0AA0
6CA40-0BA0
IE/WSN-PA LINK IE/WSN-PA LINK
10 … 100 Mbit/s
10 … 100 Mbit/s
9.6 to 57.6 kbit/s
1
1
1
1
RJ 45 port
RJ 45 port
2-pin terminal strip
3-pin terminal strip
1
1
1
0
0
1
-
N-Connector
DC
24 V
20 V
28 V
0.5 A
12 W
-40 … +70 °C
-40 … +85 °C
-40 … +85 °C
90 %
IP 65
229 mm
306 mm
354 mm
89 mm
4.54 kg
Yes
Yes
Material for mast mounting included
in scope of delivery
© Siemens AG 2015
Supplementary Components
WirelessHART products
IE/WSN-PA LINK
Wireless frequencies
Radio frequency with
WirelessHART in the 2.4 GHz
frequency band
• Initial value
• End value
Performance data
WirelessHART
Number of WirelessHART devices
which can be operated
Network latency
• For 100 field devices and WirelessHART network maximum
• For 50 field devices and WirelessHART network maximum
Transmission link between two
devices with WirelessHART network
• Maximum
• Note
Protocol is supported HART
Product properties, functions,
components general
Protocol is supported
• Address Resolution Protocol
(ARP)
• HTTP
• HTTPS
• Modbus TCP
• Modbus TCP secure
• Modbus RTU
Product functions management,
configuration
Product function
• Web-based management
• DHCP client
Product functions Diagnosis
Product function
• Web-based diagnostics
• WirelessHART diagnostics via
Modbus
Product functions Redundancy
Product function device redundancy
Product functions Security
Product function
• Password protection - multilevel
• WirelessHART join key
• ACL - MAC-based
• WirelessHART network ID
Protocol is supported SSL
Principle of encryption
Product functions Time
Protocol is supported NTP
Standards, specifications,
approvals
Standard for WirelessHART
Standard for wireless communication IEEE 802.15.4
Certificate of suitability
• CE mark
• Concerning CSA
2.4 GHz
2.5 GHz
100
10 s
5s
• Concerning FM
100 m
Values may vary in the case of radio
obstacles
Yes
• Concerning ATEX
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
• Regarding IECEx
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
AES 128 bit
Yes
Regarding NEMA
Wireless approval
HART V 7.1
Yes
Yes
CSA Division 2 & Dust Ignition-proof
for Class I, Division 2, Groups A, B,
C, and D. Dust Ignition-proof for
Class II, Groups E, F, and G / Suitable for Class III Hazardous Locations. / Install per Siemens drawing
A5E02467236A. Temperature Code:
T4 (-40°C < Ta < 60°C) CSA Enclosure Type 4X
FM Division 2, Non-Incendive for
Class I, Division 2, Groups A, B, C,
and D. Dust Ignition-proof for Class
II, III, Division 1, Groups E, F, and G
/ Indoor and outdoor locations /
NEMA Type 4X Temperature Code:
T4 (-40°C < Ta < 60°C)
ATEX type n, see note: Certificate
number: Baseefa10ATEX0044X,
ATEX marking: Ex II 3 G, Ex nA nL
IIC T4 (-40 °C <= Ta <= 60 °C),
rated voltage: 28 V, ATEX Dust Ignition-proof: Certificate number:
Baseefa10ATEX0045X, ATEX marking: II 3 D, Ex tD A22 IP66 T135
(-40 °C <= Ta <= 60 °C), rated voltage: 28 V. Note on type n: Conditions for safe handling during
installation: The device does not
pass the 500 V insulation test in
accordance with paragraph 6.8.1 of
EN 60079-15:2005. This must be
taken into account when installing
the device.
IECEx type n, see note: Certificate
number: IECEx BAS 10.0014X, Ex
nA nL IIC T4 (-40 °C <= Ta <= 60
°C), rated voltage: 28 V, IECEx Dust
Ignition-proof, see note: Certificate
number: IECEx BAS 10.0015X, Ex
tD A22 IP66 T135
(-40 °C <= Ta <= 60 °C), rated voltage: 28 V. Note on type n: Conditions for safe handling during
installation: The device does not
pass the 500 V insulation test in
accordance with paragraph 6.8.1 of
EN 60079-15:2005. This must be
taken into account when installing
the device.
FCC and IC
IC approval
approval
Yes
Siemens FI 01 · 2015 US Edition
7/37
7
© Siemens AG 2015
Supplementary Components
IE/WSN-PA LINK
■ Selection and Ordering data
Article No.
Article No.
IE/WSN-PA LINK
IE FC Stripping Tool
Gateway between WirelessHART
and Industrial Ethernet;
transmission frequency: 2.4 GHz
Preadjusted stripping tool for fast
stripping of the Industrial Ethernet
FC cables
• With integral, non-detachable
antenna
6GK1411-6CA40-0AA0
Network components for
IWLAN
see "Industrial Wireless Communication"
• N connector for connection of
external antennas
6GK1411-6CA40-0BA0
HARTING adapter cable 1)
M12 female NPT 1/2 thread to
RJ45 11cm,
(minimum order quantity: 10);
The adapter is provided for easy
connection of the link to the
Industrial Ethernet;
21036836420
Not included in the scope of delivery of the IE/WSN-PA link;
You can find ordering information
on the Internet at:
http://www.harting.com
SITOP compact 24 V/ 0.6 A
6EP1331-5BA00
Antennas
Antennas with omni-directional
characteristics;
country permits, compact instructions (hard copy),
German/English
Wall or mast-mounting
• Antenna ANT792-6MN
Antenna gain including N-Connect connector 6 dBi, 2.4 GHz
6GK5792-6MN00-0AA6
Roof mounting
1-phase power supply with widerange input 85 – 264 V AC/110 –
300 V DC,
stabilized output voltage 24 V,
rated output current value 0.6 A,
slim design
1)
• ANT795-6MN antenna
Antenna gain incl. N-Connect
connector 6/8 dBi, 2.4/5 GHz
6GK5795-6MN00-0AA6
• Antenna mounting tool
(ANT795-6MN)
Mounting tool for installation of
ANT795-6MN under a roof
6GK5795-6MN01-0AA6
LP798-1N Lightning Protector
6GK5798-2LP00-2AA6
Antenna cables
IWLAN N-Connect male/male
flexible connection cable
Flexible connecting cable for connecting an external antenna;
assembled with two N-Connect
male connectors
•1m
•2m
•5m
• 10 m
6XV1875-5AH10
6XV1875-5AH20
6XV1875-5AH50
6XV1875-5AN10
HF coupling
6GK5798-0CP00-1AA0
N-Connect male/male connector
for connecting the LP798-1N
lightning protector
Accessories
IE FC M12 Plug PRO
M12 plug-in connector suitable
for on-site assembly (D-coded,
IP65/IP67), metal housing, FastConnect connection system, for
connecting HARTING adapter
cables to the Industrial Ethernet
• 1 unit
6GK1901-0DB20-6AA0
IE FC TP Standard Cable GP 2 x
2 (Type A)
6XV1840-2AH10
4-core, shielded TP installation
cable for connection to IE
FC Outlet RJ45/IE FC RJ45 Plug;
PROFINET-compatible; with UL
approval;
sold by the meter;
max. length 1000 m, minimum
order quantity 20 m
7/38
When using the Harting adapter cable for the Ethernet connection, the
requirements for intrinsic safety approval are not applicable. When used in
an application relevant to intrinsic safety guidelines, it requires acceptance
by the appropriate approval agency.
■ More information
Current approvals can be found on the Internet at:
Lightning protector with N/N
female/female connector,
IP65 (-40 … +100 °C)
7
6GK1901-1GA00
Siemens FI 01 · 2015 US Edition
http://support.automation.siemens.com/WW/view/en/46374734