© Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor SITRANS FCS200 ■ Overview ■ Function The flow measuring principle is based on the Coriolis effect. See "System information SITRANS F C". ■ Integration The complete flowmeter consists of the sensor (SITRANS FCS200) and a transmitter SITRANS F C MASS 6000 or SIFLOW FC070. All communication options are available for MASS 6000. The sensor is shipped with a SENSORPROM memory unit containing all information about calibration data, device identity and factory pre-programming of transmitter settings. 3 Installation guidelines Siemens Flow Instruments recommends installing the sensor in one of the following ways: SITRANS FCS200 (DN10, DN 15 and DN 25) is a Coriolis sensor specialized for accurate mass flow measurement of gases. The sensor offers superior performance in terms of flow accuracy and turn down ratio. The ultra compact sensor design makes installation, replacement and commissioning very straight forward and easy. ■ Benefits • High accuracy gas measurement • Approved for use in hazardous area • DN 10 and DN 15 is custody transfer approved, according to OIML R 139 (Compressed gaseous fuel measuring systems for vehicles). For custody transfer applications SIFLOW FC070 Ex CT must be used. • Self-draining in vertical orientation • Pt1000 temperature measurement for optimum accuracy • SENSORPROM enabling true "plug & play" • Rigid enclosure design reducing influence from pipeline vibration and thermal stress • High-pressure measurement up to 350 bar (5076 psi) • Ultra compact sensor design with space-saving split flow Vertical orientation with an upwards flow ■ Application SITRANS FCS200 is designed for measurement of gases and is suitable for use in the oil and gas industry: • Filling of gas bottles • CNG dispensers • Metering of general gas applications Horizontal installation, tubes up ■ Design SITRANS FCS200 is available in DN 10, DN 15 and DN 25. The sensor consists of 2 parallel measuring pipes, welded directly onto a flow splitter at each end of the sensor to eliminate a direct coupling to the process connectors and significantly reduce effects from external vibrations. The flow-splitters are welded directly onto a rigid sensor housing which acts as a mechanical low pass filter. The SITRANS FCS200 DN 10 and DN 15 wetted parts material is Hastelloy C22, and the DN 25 wetted parts material is AISI 316Ti/1.4571. The enclosure is made of stainless steel AISI 316L/1.4404 with a grade of encapsulation of IP67. The two black rupture discs are designed to protect the enclosure from overpressure. 3/200 Siemens FI 01 · 2015 US Edition Horizontal installation, tubes sideways © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor SITRANS FCS200 ■ Technical specifications Sensor size ■ Characteristic curves DN 10 DN 15 DN 25 DN 10 Mass Flow Accuracy [% of rate] 0.5 Repeatability [% of rate] 0.25 Max. zero point error [kg/h (lb/h)] 0.25 (0.55) Measuring range [kg/min (lb/min)] 0 … 42 (0 … 92.6) 1.2 (2.65) bar 2.5 3.0 (6.6) 2.0 0 … 200 0 … 500 (0 … 440.9) (0 … 1102.3) Process temperature -40 ... +125 °C (-40 ... +257 °F) Ambient temperature -40 ... +60 °C (-40 ... +140 °F) Temperature error Pressure [bar (psi)] 1.5 0.5 °C (0.9 °F) 350 (5076) Enclosure grade 350 (5076) 3 1.0 0.5 214 (3104) 0 IP66/IP67 (EN 60529) 0 200 0 500 1000 1500 2000 2500 3000 3500 [kg/h] 400 600 800 1000 1200 1400 [kg/h] Material Measuring pipe Hastelloy C22/2.4602 Hastelloy C22/2.4602 Splitter Hastelloy C22/2.4602 Stainless Stainless steel AISI steel AISI 316L/1.4571 316L/1.4571 Enclosure and connection (flanges) Connection thread Stainless steel AISI 316L/1.4571 DN 15 bar 1.2 1.0 Stainless steel 0.8 ¼" NPT ½" NPT ½" VCO ½" NPT ¾" NPT 1" NPT ¾" VCO 1" NPT 1½" NPT 1" VCO 0.6 0.4 0.2 Ex approval • ATEX II 1/2 G Ex ia IIC T5/T4 Ga/Gb • IECEx Ex ia IIC T5/T4 Ga/Gb • FM Class I, Div 1, Groups A, B, C and D Weight approx. 2.8 kg (6.2 lb) 6.0 kg (13.2 lb) 11 kg (24.2 lb) Approvals Custody transfer DN 10/DN 15 0 DN 25 bar 3.5 PTB Germany approval nr: 5.4.11/11.22 OIML R 139 - Compressed gaseous fuel measuring systems for vehicles 3.0 2.5 2.0 1.5 1.0 0.5 0 0 5000 10000 15000 20000 25000 [kg/h] The pressure drop as a function of capacity for CNG with a pressure of 200 bar (2900 psi) and an ambient temperature of 20 °C (68 °F). Siemens FI 01 · 2015 US Edition 3/201 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor SITRANS FCS200 Operating instructions for SITRANS FCS200 Article No. Selection and Ordering data SITRANS F C Flow sensors SITRANS FCS200 sensor, without heating jacket 7 ME 4 5 0 0 7 77 7 7 - 7 7 7 7 Click on the Article No. for the online configuration in the PIA Life Cycle Portal. 3 Sensor size and material DN 10, Hastelloy C22/2.4602 DN 15, Hastelloy C22/2.4602 DN 25, Stainless steel AISI 316Ti/1.4571 2D 2E 1F Pressure PN 214 (DN 25) PN 350 (DN 10 and DN 15) K N ½“/VCO ¾“/VCO 1“/VCO 71 72 73 ¼“/NPT pipe thread ½“/NPT pipe thread 81 82 ¾“/NPT pipe thread 1“/NPT pipe thread 1½“/NPT pipe thread 83 84 85 Configuration Standard 1 Transmitter A None Cable No cable A Calibration Standard calibration 1 Order code Selection and Ordering data Additional information Please add “-Z“ to Article No. and specify Order code(s) and plain text. Pressure testing certificate PED: 97/23/EC C11 Material certificate EN 10204-3.1 C12 NDT-Penetrant inspection report ISO 3452 C13 Factory certificate according to EN 10204 2.2 C14 Factory certificate according to EN 10204 2.1 C15 Tag name plate, stainless steel Y17 Accessories Article No. Description 3/202 5 m (16.4 ft) FDK:083H3015 10 m (32.8 ft) FDK:083H3016 25 m (82 ft) FDK:083H3017 50 m (164 ft) FDK:083H3018 75 m (246 ft) FDK:083H3054 150 m (492 ft) FDK:083H3055 Siemens FI 01 · 2015 US Edition Article No. • English A5E02508199 • German A5E03082574 • Spanish A5E03082587 • French A5E03082581 • Italian A5E03504933 Spare parts Process connection/flange Cable with multiple plug Standard blue cable between SIFLOW FC070/MASS 6000 and FCS200, 5 x 2 x 0.34 mm2 twisted and screened in pairs. Temperature range -20 °C ... +110 °C (-4 °F ... +230 °F) Description Description Article No. Multiple plug for cable mounting FDK:083H5056 2 kB SENSORPROM unit (Sensor Serial No. and Article No. must be specified by ordering) FDK:083H4410 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor SITRANS FCS200 ■ Dimensional drawings SITRANS FCS200, DN 10 ... DN 15 3 SITRANS FCS200, DN 10 ... DN 15, dimensions in mm (inch) Position DN 10 with NPT DN 10 with VCO DN 15 connectors connectors mm (inch) mm (inch) mm (inch) (1) 350 (13.78) 330 (12.99) 450 (17.72) (2) 72 (2.84) 72 (2.84) 72 (2.84) (3) 100 (3.94) 100 (3.94) 148 (5.83) (4) 204 (8.03) 204 (8.03) 253 (9.96) (5) 40 (1.57) 40 (1.57) 48 (1.89) Siemens FI 01 · 2015 US Edition 3/203 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor SITRANS FCS200 SITRANS FCS200, DN 25 DN 25 - NPT 3 DN 25 - VCO SITRANS FCS200, DN 25, dimensions in mm (inch) Position DN 25 DN 25 with NPT connection with VCO connection mm (inch) mm (inch) (1) 520 (20.47) 550 (21.65) (2) 72 (2.84) 72 (2.84) (3) 200 (7.87) 200 (7.87) (4) 357 (14.77) 357 (14.77) (5) 74 (2.91) 74 (2.91) (6) 80 (3.15) 80 (3.15) (7) 125 (4.92) 125 (4.92) (8) 32 (1.26) 32 (1.26) 3/204 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 1.5 ■ Overview ■ Application In many industries such as the food and beverage or pharamceutical industry, accurate recipe control means everything. The MASS 2100 DI 1.5 has demonstrated superiour performance in numerous applications and field trails relating to accuracy and turn-down ratio. It is today the preferred meter for research and development and mini-plant applications for liquid or gas measurement, where measuring small quantities is important. The main applications for the MASS 2100 DI 1.5 sensor can be found in: MASS 2100 DI 1.5 is suitable for low flow measurement applications of a variety of liquids and gases. The sensor offers superior performance in terms of flow accuracy, turn-down ratio and density accuracy. The ease of installation through a "plug & play" mechanical and electrical interface ensures optimum performance and operation. The sensor delivers true multi-parameter measurements i.e.: Mass flow, volume flow, density, temperature and fraction. ■ Benefits • High accuracy better than 0.1 % of mass flow rate • Large dynamic turn-down ratio better than 500:1, from 30 kg/h to a few g/h • Densitometer performance available through a density accuracy better than 0.001 g/cm3 with a repeatability better than 0.0002 g/cm3. • Single continuous tube design, with no internal welds, reductions or flow splitters offers optimal hygiene, safety and CIP cleanability for food and beverage and pharmaceutical applications. • Market’s biggest wall thickness, ensuring optimal life-time and corrosion resistance and high-pressure durability • Balanced pipe design with little mechanical energy-loss, ensures optimal performance and stability under non-ideal and unstable process conditions (pressure, temperature, densitychanges etc.). • 4-wire Pt1000 temperature measurement ensures optimum accuracy on mass flow, density and fraction flow • Multi-plug electrical connector and SENSORPROM enables true "plug & play". Installation and commissioning in less than 10 minutes • Intrinsically safe Ex ia design as standard • Sensor pipe available in high-quality stainless steel AISI 316L/ 1.4435 or Hastelloy C22/2.4602 offering optimum corrosion resistance • Dual-drive pick-up and driver construction facilitate ultra lowweight pipe construction giving the markets’ smallest and most stable zero point. • Rugged and space-saving sensor design in stainless steel matching all environments • High-pressure program as standard • The sensor calibration factor is also valid for gas measurement. Chemical industry Liquid and gas measurement within Miniplant and R & D, dosing of additives and catalysts Cosmetic industry Dosing of essence and fragrances Pharmaceutical industry High-speed dosing and coating of pills, filling of ampuls/injectors Food and beverage industry Dosing of flavourings, colours and additives, density measurement, inline measurement of liquid or gaseous CO2 Automotive industry Fuel injection nozzle and pump testing, filling of AC units, engine consumption, paint robots, ABS test-beds ■ Design The MASS 2100 sensor consists of a single bent tube in a double omega pipe configuration, welded directly to the process connectors at each end. The sensor is available in 2 material configurations, AISI 316L/ 1.4404 or Hastelloy C22/2.4602 with ¼” NPT or ¼” ISO process connections. The enclosure is made in stainless steel AISI 316L/1.4404 with a grade of encapsulation of IP65/NEMA 4. The sensor is available in either a standard version with a maximum liquid temperature of 125 °C (257 °F) or a high-temperature version, with raised electrical connector for 180 °C (356 °F). The sensor can be installed in horizontal or vertical position. The enclosed single quick release clamp fitting which, along with its compact design and single multi-plug electrical connector, will keep installation costs and time to a minimum as shown below. Siemens FI 01 · 2015 US Edition 3/205 3 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 1.5 ■ Function ■ Technical specifications The measuring principle is based on the Coriolis effect. See “System information SITRANS F C Coriolis mass flowmeters”. ■ Integration The sensor can be connected to all MASS 6000 transmitters for remote installation only. 3 All sensors are delivered with a SENSORPROM containing all information about calibration data, identity and factory pre-programming of transmitter settings Installation guidelines MASS 2100 DI 1.5 (1/16“) Installation of MASS 2100 sensor • The optimal installation is horizontal. If vertical mounting is necessary, upward flow is recommended to facilitate the removal of air bubbles. To remove the air from the sensor the flow speed in the sensor must be at least 1 m/s. If there are solid particles in the liquid, especially in connection with low flow, it is recommended that the sensor be mounted horizontally with inlet flange uppermost so that particles are more easily flushed out. To ensure that the sensor does not become partially empty, there must be sufficient counter-pressure on the unit min. 0.2 bar (2.9 psi). • Mount the sensor on a vibration-free wall or steel frame. • Locate the sensor low in the system in order to avoid an underpressure in the sensor separating air/gas in the liquid. • Ensure that the sensor is not emptied of liquid (during normal operation) otherwise incorrect measurement will occur. Inside pipe diameter (sensor consists of one continuous pipe) 1.5 mm (0.06”) Pipe wall thickness 0.25 mm (0.010”) Mass flow measuring range 0 ... 30 kg/h (0 ... 66 lb/h) Density 0 ... 2.9 g/cm3 (0 ... 0.10 lb/inch3) Fraction e.g. 0 ... 100 °Brix Temperature Standard -50 ... +125 °C (-58 ... +257 °F) High-temperature version -50 ... +180 °C (-58 ... +356 °F) Liquid pressure measuring pipe1) Stainless steel 230 bar (3336 psi) at 20 °C (68 °F) Hastelloy C22/2.4602 365 bar (5294 psi) at 20 °C (68 °F) Materials Measuring pipe and connection Stainless steel AISI 316L/1.4435 Hastelloy C22/2.4602 IP65 and stainless steel AISI316L/1.4404 Enclosure and enclosure material2) Connection thread ISO 228/1 G¼” male ANSI/ASME B1.20.1 ¼” NPT male Cable connection Multiple plug connection to sensor 5 x 2 x 0.35 mm2 twisted and screened in pairs, ext. Ø 12 mm Ex-version II 1G Eex ia IIC T3-T6, DEMKO 03 ATEX 135252X c-UL-us Ex ia IIC T3-T6 UL WYMG.E232147 Weight approx. 2.6 kg (5.73 lb) Horizontal 1) According to DIN 2413, DIN 17457 2) Housing is not rated for pressure containment. For accuracy specifications see “System information SITRANS F C”. Pressure drop Viscosity [cSt] Liquid and gas application Δp [bar] 100 1000 500 200 100 Vertical 50 10 20 10 5 1 1.0 0.1 Liquid application (left), gas application (right) 0.01 0.1 1 10 70 Mass flow [kg/h] MASS 2100 DI 1.5 (1/16“), pressure drop for density = 1000 kg/m3 3/206 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 1.5 Selection and Ordering data Article No. Ord. code Selection and Ordering data SITRANS F C Flow sensors 7 ME 4 1 0 0 - Additional information MASS 2100 DI 1.5 (1/16“) sensor 7 77 7 7 - 7 7 7 7 7 7 7 Please add “-Z“ to Article No. and specify Order code(s) and plain text. Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Order code Pressure testing certificate PED: 97/23/EC C11 Diameter Material certificate EN 10204-3.1 C12 Stainless steel AISI 316L/1.4435 DI 1.5, max. 125 °C (257 °F) DI 1.5, max. 180 °C (356 °F) Welding certificate NDT-Penetrant: ISO 3452 C13 1A 1B Factory certificate according to EN 10204 2.2 C14 Factory certificate according to EN 10204 2.1 C15 2A 2B Tag name plate, stainless steel Y17 Tag name plate, plastic Y18 Customer-specific transmitter setup Y20 Customer-specified, matched pair (5 x 2) Y60 Customer-specified calibration (5 x 2) Y61 Customer-specified, matched pair (10 x 1) Y62 Customer-specified calibration (10 x 1) Y63 Cleaned for oil and grease Y80 Special version Y99 Hastelloy C22/2.4602 DI 1.5, max. 125 °C (257 °F) DI 1.5, max. 180 °C (356 °F) Pressure PN 100 PN 230 (AISI 316L/1.4404) PN 365 (C22/2.4602) D L P Process connection/flange Pipe thread G ¼“ male ¼“ NPT male 10 11 Operating instructions for SITRANS F C MASS 2100 DI 1.5 Configuration Standard Density Brix/Plato Fraction (specification required) 1 2 3 9 N0Y Transmitter compact mounted on sensor A MASS 6000, Ex d, stainless steel enclosure, 1 current, 1 freq./pulse and 1 relay output, 24 V AC/DC with Ex de [ia/ib] T3 -T6 Exapproval. B MASS 6000, IP67, Polyamide enclosure, cable glands M20, 1 current, 1 freq./pulse and 1 relay output, 24 V AC/DC. C MASS 6000, IP67, Polyamide enclosure, cable glands M20, 1 current, 1 freq./pulse and 1 relay output, 115/230 V AC 50/60 Hz D MASS 6000, IP67, Polyamide enclosure, cable glands ½" NPT, 1 current, 1 freq./pulse and 1 relay output, 24 V AC/DC E MASS 6000, IP67, Polyamide enclosure, cable glands ½" NPT, 1 current, 1 freq./pulse and 1 relay output, 115/230 V AC 50/60 Hz, ½" NPT F 25 m (82 ft) cable 50 m (164 ft) cable 75 m (246 ft) cable 150 m (492 ft) cable Description Article No. • English A5E03089952 This device is shipped with a Quick Start guide and a CD containing further SITRANS F literature. All literature is also available for free at: No transmitter, sensor and adapter only Cable No cable 5 m (16.4 ft) cable 10 m (32.8 ft) cable 3 http://www.siemens.com/flowdocumentation Accessories Article No. Description Cable with multiple plug Standard blue cable between MASS 6000 and MASS 2100, 5 x 2 x 0.34 mm2 twisted and screened in pairs. Temperature range -20 °C ... +110 °C (-4 °F ... +230 °F) A B C D • 5 m (16.4 ft) FDK:083H3015 • 10 m (32.8 ft) FDK:083H3016 • 25 m (82 ft) FDK:083H3017 • 50 m (164 ft) FDK:083H3018 • 75 m (246 ft) FDK:083H3054 • 150 m (492 ft) FDK:083H3055 Spare parts E F Description Article No. Multiple plug for cable mounting FDK:083H5056 2 kB SENSORPROM unit FDK:083H4410 (Sensor Serial No. and Article No. must be specified by ordering) G Calibration Standard calibration 3 flow x 2 points Standard calibration matched pair 3 flow x 2 points Accredited calibration matched pair 5 flow x 2 points (DANAK) 1 2 Extended calibration customer-specified select Y60, Y61, Y62 or Y63 (see additional information) 8 Bracket A5E02590427 3 Siemens FI 01 · 2015 US Edition 3/207 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 1.5 ■ Dimensional drawings MASS 2100 DI 1.5 (1/16“) Ø57 (2.4) 64,5 (2.54) 4 (0.16) 120 (4.72) NV21 G 1/4” Ø18,8 (0.74) Ø24 (0.94) 1/4” NPT Ø18,8 (0.74) Ø24 (0.94) 1/4” NPT ANSI/ASME B1.20.1-1983 20 (0.79) NV21 15 (0.6) 12 (0.47) 15 (0.6) 12 (0.47) 86 (3.39) 152 (5.98) 10 (0.39) 78 (3.07) 20 (0.79) 3 Ø129 (5.08) 46 (1.81) 25 (0.98) Ø 9 (0.35) G 1/4” ISO 228/1 100 (3.94) Dimensions in mm (inch) MASS 2100 DI 1.5 High-temperature version to 180 °C (356 °F) Ø57 (2.4) 192,6 (7.58) 1/4” NPT Ø18,8 (0.74) Ø24 (0.94) 1/4” NPT ANSI/ASME B1.20.1-1983 4 (0.16) 120 (4.72) NV21 G 1/4” Ø18,8 (0.74) Ø24 (0.94) G 1/4” ISO 228/1 Ø 9 (0.35) 20 (0.79) NV21 15 (0.6) 12 (0.47) 15 (0.6) 12 (0.47) 86 (3.39) 152 (5.98) 100 (3.94) Dimensions in mm (inch) 3/208 Siemens FI 01 · 2015 US Edition 10 (0.39) 64,5 (2.54) 78 (3.07) 20 (0.79) Ø129 (5.08) 46 (1.81) 25 (0.98) © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor SITRANS FC300 ■ Overview • High-pressure program as standard • The sensor calibration factor is also valid for gas measurement. ■ Application The industry today has an increasing demand for mass flowmeters with a reduced physical size without loss of performance. The meters must be suitable for installation in traditional process industry environment as well as OEM equipment for instance within automotive or appliance industry. Independent of industry application the meter must deliver accurate and reliable measurements. The new and versatile design of the FC300 offers this flexibility. The main applications for the SITRANS FC300 DN 4 can be found in: SITRANS FC300 is a compact Coriolis mass sensor suitable for flow measurement of a variety of liquids and gases. The sensor offers superior performance in terms of flow accuracy, turn-down ratio and density accuracy. The ease of installation through a „plug & play“ interface ensures optimum performance and operation. A new designed encapsulation in stainless steel with a surprisingly low weight of only 3.5 kg (7.7 lb), ensures a rigid and robust sensor performance for a wide range of applications. ■ Benefits • High accuracy better than 0.1 % of mass flow rate • Large dynamic turn-down ratio better than 500:1 • Densitometer performance available through a density accuracy as follows: - For 316L/1.4404 version better than 0.0015 g/cm3 (0.000036 lb/inch3) with repeatability better than 0.0002 g/cm3 (0.0000072 lb/inch3) - For C22/2.4602 version better than 0.0025 g/cm3 (0.000090 lb/inch3) with repeatability better than 0.001 g/cm3 (0.000036 lb/inch3) • One tube without internal welds, reductions or flow splitters offers optimal hygiene, safety and CIP cleanability for food and beverage and pharmaceutical applications • Larger wall thickness, ensures optimal life-time and corrosion resistance and high-pressure durability • Balanced pipe design with little mechanical energy loss, ensures optimal performance and stability under non-ideal and unstable process conditions (pressure, temperature, densitychanges etc.). • 4-wire Pt1000 temperature measurement ensures optimum accuracy on mass flow, density and fraction flow • Multi-plug electrical connector and SENSORPROM enable true „plug & play“. Installation and commissioning in less than 10 minutes. • Intrinsically safe Ex design ia IIC as standard • Sensor pipe available in high-quality stainless steel AISI 316L/1.4435 or Hastelloy C22/2.4602 offering optimum corrosion resistance. • Rugged and space-saving sensor design in stainless steel matching all applications. Chemical industry Liquid and gas measurement in normal as well as corrosive environments Cosmetic industry Dosing of essence and fragrances Pharmaceutical industry High-speed dosing and coating of pills, filling of ampuls/injectors Food and beverage industry Filling, dosing of flavorings, colors and additives, inline density measurement Measurement and dosing of liquid or gaseous CO2 Automotive industry Fuel injection nozzle and pump testing, filling of AC units, engine consumption, paint robots, ABS test-beds ■ Design The FC300 sensor consists of a single tube bent in double omega pipe geometry, welded directly to the process connectors at each end. The sensor is available in 2 material configurations, AISI 316L/1.4404 or Hastelloy C22/2.4602 with ¼”-NPT or G¼”-ISO process connections. The enclosure is made of stainless steel AISI 316L/1.4409 with a grade of encapsulation of IP67/NEMA 4. The enclosure has a very robust design and with an overall size of 130 x 200 x 60 mm (5.12“ x 7.87“ x 2.36“) the sensor is very compact and requires only little installation space. The sensor can be delivered in a standard version with a maximum liquid temperature of 115 °C (239 °F) or a high-temperature version, with raised electrical connector for 180 °C (356 °F). The sensor can be installed in horizontal or vertical position. The sensor can be mounted directly on any given plane surface or if desired with the enclosed quick release clamp fitting which, along with its compact design and multi-plug electrical connector, will keep installation costs and time to a minimum. ■ Function The measuring principle is based on the Coriolis effect. See “System information SITRANS F C Coriolis mass flowmeters”. ■ Integration The sensor can be connected to all MASS 6000 and SIFLOW FC070 (standard and Ex types) transmitters for remote installation only. All sensors are delivered with a SENSORPROM containing all information about calibration data, identity and factory pre-programming of transmitter settings Siemens FI 01 · 2015 US Edition 3/209 3 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor SITRANS FC300 Installation guidelines for SITRANS FC300 sensor Horizontal installation as shown in figure A is recommended with gas or liquid applications. This installation is also recommended when the flow velocity is low (< 1 m/s) or the liquid contains solid particles or air bubbles. 3 ■ Technical specifications Sensor size DN 4 (1/6“) Mass flow Measuring range 0 ... 350 kg/h (0 ... 772 lb/h) Vertical installation as shown in figure B can be used for liquid or gas applications. Accuracy, mass flow 0.1 % of rate Repeatability 0.05 % of rate For liquid applications upwards flow is recommended to facilitate the removal of air bubbles and to avoid partly emptying of the sensor. For gas applications we recommend to place the flow inlet on the sensor high and the outlet low to remove impurities and oil films. • To ensure that the sensor does not become partly empty, there must be a sufficient counter-pressure on the unit min. 0.2 bar (2.9 psi). • Mount the sensor on a vibration-free and plane wall or steel frame. • Locate the sensor low in the system in order to avoid underpressure in the sensor separating air/gas in the liquid. • Ensure that the sensor is not emptied of liquid (during normal operation) otherwise incorrect measurement will occur. Max. zero point error 0.010 kg/h (0.022 lb/h) Horizontal mounting (recommended) (fig. A) Density Density range 0 ... 2.9 g/cm3 (0 ... 0.105 lb/inch3) Density error • Stainless steel 0.007 g/cm3 (0.00025 lb/inch3) • Hastelloy C22/2.4602 0.0025 g/cm3 (0.00009 lb/inch3) Repeatability error 0.0002 g/cm3 (0.0000072 lb/inch3) Temperature Standard -40 ... +115 °C (-40 ... +239 °F) High-temperature version -40 ... +180 °C (-40 ... +356 °F) Temperature error 0.5 °C (0.9 °F) Brix Measuring range 0 ... 100 °Brix Brix error 0.3 °Brix Inside pipe diameter Stainless steel version 3.5 mm (0.14“) Hastelloy version 3.0 mm (0.12“) Pipe wall thickness Stainless steel version 0.25 mm (0.0098“) Liquid or gas (low to high flow) Hastelloy version 0.5 mm (0.0196“) Vertical mounting (fig. B) Liquid pressure measuring pipe1) Stainless steel 130 bar (1885 psi) at 20 °C (68 °F) Hastelloy C22/2.4602 410 bar (5945 psi) at 20 °C (68 °F) Materials Stainless steel AISI 316L/1.4435 Measuring pipe and connection Hastelloy C22/2.4602 Enclosure2) Material Stainless steel AISI 316L/1.4404 Enclosure grade IP67/NEMA4 Connection thread ISO 228/1 G¼” male ANSI/ASME B1.20.1 ¼” NPT male Ex approval Ex ia IIC T3-T6 05ATEX138072X c-UL-us Class 1 Div. 1, Gr. A, B, C, D Liquid or gas (medium to high flow) 3/210 Siemens FI 01 · 2015 US Edition Weight 3.5 kg (7.7 lb) Dimensions 135 x 205 x 58 mm (5.31“ x 8.07“ x 2.28“) 1) According to DIN 2413, DIN 17457 2) Housing is not rated for pressure containment. © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor SITRANS FC300 Selection and Ordering data Article No. Order code Selection and Ordering data SITRANS F C Flow sensors 7 ME 4 4 0 0 - SITRANS FC300 DN 4 (1/6“) sensor 7 77 7 7 - 7 7 7 7 7 7 7 Additional information Please add “-Z“ to Article No. and specify Order code(s) and plain text. Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Pipe material and temperature Stainless steel AISI 316L/1.4435 115 °C (239 °F) 180 °C (356 °F) Hastelloy C22/2.4602 115 °C (239 °F) 180 °C (356 °F) Pressure PN 100 PN 130 (316L/C22) PN 410 (C22) Pressure testing certificate PED: 97/23/EC C11 Material certificate EN 10204-3.1 C12 Welding certificate NDT-Penetrant: ISO 3452 C13 1G 1H Factory certificate according to EN 10204 2.2 C14 Factory certificate according to EN 10204 2.1 C15 2G 2H Tag name plate, stainless steel Y17 Tag name plate, plastic Y18 Customer-specific transmitter setup Y20 Customer-specified, matched pair (5 x 2) Y60 Customer-specified calibration (5 x 2) Y61 Customer-specified, matched pair (10 x 1) Y62 Customer-specified calibration (10 x 1) Y63 Cleaned for oil and grease Y80 Special version Y99 D G Q Process connection Pipe thread G ¼“ male ¼“ NPT male Configuration Standard Density Brix/Plato Fraction (specification required) 10 11 1 2 3 9 N0Y No transmitter, sensor and adapter only A MASS 6000, Ex d, stainless steel enclosure, 1 current, 1 freq./pulse and 1 relay output, 24 V AC/DC with Ex de [ia/ib] T3 -T6 Exapproval B MASS 6000, IP67, Polyamide enclosure, cable glands M20, 1 current, 1 freq./pulse and 1 relay output, 24 V AC/DC C MASS 6000, IP67, Polyamide enclosure, cable glands M20, 1 current, 1 freq./pulse and 1 relay output, 115/230 V AC 50/60 Hz D MASS 6000, IP67, Polyamide enclosure, cable glands ½" NPT, 1 current, 1 freq./pulse and 1 relay output, 24 V AC/DC E MASS 6000, IP67, Polyamide enclosure, cable glands ½" NPT, 1 current, 1 freq./pulse and 1 relay output, 115/230 V AC 50/60 Hz, ½" NPT F 25 m (82 ft) cable 50 m (164 ft) cable 75 m (246 ft) cable 150 m (492 ft) cable Calibration Standard calibration 3 flow x 2 points Standard calibration matched pair 3 flow x 2 points Accredited calibration matched pair 5 flow x 2 points (DANAK) Extended calibration customer-specified select Y60, Y61, Y62 or Y63 (see additional information) 3 Operating instructions for SITRANS F C FC300 Transmitter compact mounted on sensor Cable No cable 5 m (16.4 ft) cable 10 m (32.8 ft) cable Order code Description Article No. • English A5E00698213 • German A5E00728101 • Spanish A5E00746629 • French A5E00746625 This device is shipped with a Quick Start guide and a CD containing further SITRANS F literature. All literature is also available for free at: http://www.siemens.com/flowdocumentation Accessories Article No. Description Cable with multiple plug Standard blue cable between MASS 6000 and MASS 2100, 5 x 2 x 0.34 mm2 twisted and screened in pairs. Temperature range -20 °C ... +110 °C (-4 °F ... +230 °F) A B C D E F • 5 m (16.4 ft) FDK:083H3015 • 10 m (32.8 ft) FDK:083H3016 • 25 m (82 ft) FDK:083H3017 • 50 m (164 ft) FDK:083H3018 • 75 m (246 ft) FDK:083H3054 • 150 m (492 ft) FDK:083H3055 Spare parts G 1 2 3 Description Article No. Multiple plug for cable mounting FDK:083H5056 2 kB SENSORPROM unit FDK:083H4410 (Sensor Serial No. and Article No. must be specified by ordering) 8 Mounting bracket in AISI 304 A5E02590439 Demo suitcase including MASS 6000, FC300 (DN 4), and HART module A5E00789737 Siemens FI 01 · 2015 US Edition 3/211 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor SITRANS FC300 ■ Characteristic curves Pressure drop Viscosity [cSt] Δp [bar] 1000 10 500 200 100 50 20 10 3 5 2 1 1.0 0.1 3 10 100 500 Mass flow [kg/h] Stainless steel 316L/1.4404 9LVFRVLW\>F6W@ P [bar] 10 1.0 0.1 3 10 Hastelloy C22/2.4602 3/212 Siemens FI 01 · 2015 US Edition 100 300 [kg/h] © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor SITRANS FC300 ■ Dimensional drawings 1/4”-18 NPT Ø18,8 (0.74) SITRANS FC300 DN 4 15 (0.59) 12 (0.47) 3 38 (1.50) 15 (0.59) 12 (0.47) G 1/4” Ø18,8 (0.740) 1/4”-18 NPT (ANSI/ASME B1.20.1) G 1/4” (ISO 228/1 ) M8 NV 5 (0.20) 190 (3.54) 14 ± 2 (0.55 ± 0.08) 121 (4.76) 77 (3.03) 19 (0.75) 205 (8.07) 20 (1.33) NV 24 (0.95) 28,8 (1.134) Ø27 (1.06) 18,8 (0.74) 110 (4.33) M4 58 (2.28) 135 (5.31) 2 x M8 32 (1.26) 75 (2.95) NV 6 (0.24) SITRANS FC300, dimensions in mm (inch) Siemens FI 01 · 2015 US Edition 3/213 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 3 to DI 15 ■ Overview ■ Application Coriolis mass flowmeters are suitable for measuring all liquids and gases. The measurement is independent of changes in process conditions/parameters such as temperature, density, pressure, viscosity, conductivity and flow profile. Due to this versatility the meter is easy to install and the Coriolis flowmeter is recognized for its high accuracy in a wide turndown ratio which is a paramount in many applications. The main applications of the Coriolis flowmeter can be found in all industries, such as: 3 MASS 2100 DI 3 to DI 15 is suitable for accurate mass flow measurement of a variety of liquids and gases. The sensor offers superior performance in terms of flow accuracy, turn-down ratio and density accuracy. The ease of installation through a "plug & play" mechanical and electrical interface ensures optimum performance and operation. The sensor delivers true multi-parameter measurements i.e.: Mass flow, volume flow, density, temperature and fraction. Chemical and pharma Detergents, bulk chemicals, pharmaceuticals, acids, alkalis Food and beverage Dairy products, beer, wine, soft-drinks, Brix/Plato, fruit juices and pulps, bottling, CO2 dosing, CIP-liquids Automotive Fuel injection nozzle and pump testing, filling of AC units, engine consumption, paint robots Oil and gas Filling of gas bottles, furnace control, test separators, LPG Water and waste water Dosing of chemicals for water treatment ■ Benefits • High accuracy better than 0.1 % of mass flow rate • Large dynamic turn-down ratio better than 500:1 • Densitometer performance available through density accuracy (depending upon sensor size) ranging from 0.0005 to 0.0015 g/cm3 with a typical repeatability better than 0.0001 to 0.0002 g/cm3 • Single continuous tube design, with no internal welds, reductions or flow splitters offers optimal hygiene, safety and CIP cleanability for food and beverage and pharmaceutical applications • Markets’ thickest sensor walls ensure optimal life-time and corrosion resistance and high-pressure durability • Full bore design provides lower pressure loss due to same internal diameter throughout the entire sensor • Balanced pipe design with little mechanical energy loss, ensures optimal performance and stability under non-ideal and unstable process conditions (pressure, temperature, density changes etc.) • 4-wire Pt1000 temperature measurement ensures optimum accuracy on mass flow, density and fraction flow • Multi-plug electrical connector and SENSORPROM enables true "plug & play". Installation and commissioning in less than 10 minutes • Intrinsically safe Ex design ia IIC as standard, making service in hazardous area possible without having to demount the sensor if a compact Ex d transmitter needs service • Sensor pipe available in high-quality stainless steel AISI 316L/1.4435 or Hastelloy C22/2.4602 offering optimum corrosion resistance • Centre-block design decouples process noise from the environment such as vibrations, pulsations, pressure shocks etc. making installation flexible and versatile • Rugged and space-saving sensor design in stainless steel matching all environments • High-pressure program as standard • The sensor calibration factor is also valid for gas measurement • Uniform sensor interface matching all transmitter versions at the same time whether it is compact IP67/NEMA 6, compact Ex d or remote installation, one sensor fits all 3/214 Siemens FI 01 · 2015 US Edition The wide varity of combinations and versions from the modular system means that ideal adaptation is possible to each measuring task. ■ Design The MASS 2100 sensor consists of a single bent tube in a double bent pipe configuration, welded directly to the process connectors at each end. The centre-block is brazed onto the sensor pipes from the outside acting as a mechanical low pass filter. The sensor is available in 2 material configurations, AISI 316L/1.4404 or Hastelloy C22/2.4602 with a wide variety of process connections. The enclosure is made in stainless steel AISI 316L/1.4404 with a grade of encapsulation of IP67. The sensor is as standard Ex ia approved, intrinsically safe. The sensor can be installed in horizontal or vertical position. In horizontal position the sensor is self draining. Heating: All the sensors MASS 2100, DI 3 to DI 15, can optionally be equipped with a heating coil to avoid solidification of sensitive fluids during down-time or period between discontinuing processes. This feature gives the user an alternative to the costly electrical heating normally used, as it gives the freedom to choose either hot water, superheated steam or hot oil, to maintain a constant temperature inside the sensor. © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 3 to DI 15 ■ Function The measuring principle is based on the Coriolis effect. See “System information SITRANS F C Coriolis mass flowmeters”. ■ Integration The sensor can be connected to all MASS 6000 transmitters for compact and remote installation as well as SIFLOW FC070 standard and Ex type transmitters. All sensors are delivered with a SENSORPROM containing all information about calibration data, identity and factory pre-programming of transmitter settings. 3 Installation guidelines MASS 2100 DI 3 ... DI 15 (1/8" ... ½") Installation of sensor In order to perform according to given specifications for flow and density accuracy, the sensor must be installed using rigid mounting brackets as shown in the installation examples. If the liquid is volatile or contains solid particles, vertical mounting is not recommended. Liquid Gas Horizontal Vibration Always locate the flowmeter as far away as possible from components that generate mechanical vibration in the piping. Vertical Cross talk Cross talk between sensors mounted close to each other may disturb the measurement. To avoid cross talk never mount more than one meter on each frame and mount flexible hose connections between the sensors as shown. Zero point adjustment To facilitiate zero point adjustment a shut-off valve should always be mounted in connection with the sensor as a proper zero point setting is essential for a good accuarcy. Siemens FI 01 · 2015 US Edition 3/215 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 3 to DI 15 ■ Technical specifications 3 Versions (mm (inch)) DI 3 (1/8) DI 6 (¼) DI 15 (5/8) DI 25 (1) DI 40 (1½) Inside pipe diameter (sen- mm (inch) sor consists of one continuous pipe) 3.0 (0.12) 6.0 (0.24) 14.0 (0.55) 29.7 (1.17) 43.1 (1.70) Pipe wall thickness mm (inch) 0.5 (0.02) 1.0 (0.04) 1.0 (0.04) 2.0 (0.08) 2.6 (0.10) Mass flow measuring range kg/h (lb/h) 0 ... 250 (0 ... 550) 0 ... 1000 (0 ... 2200) 0 ... 5600 (0 ... 12345) 0 ... 25000 (0 ... 55100) 0 ... 52000 (0 ... 114600) Density g/cm3 (lb/inch3) Fraction e.g. °Brix 0 ... 2.9 (0 ... 0.10) 0 ... 70 (applicable temperature range: 10 ... 99 °C (50 ... 210.2 °F)) Temperature Standard °C (°F) -50 ... +180 °C (-58 ... +356 °F) Liquid pressure measuring pipe1) Stainless steel bar (psi) 230 (3336) 265 (3844) 130 (1885) 110 (1595) 105 (1523) Hastelloy C22/2.4602 bar (psi) 350 (5076) 410 (5946) 200 (2900) 185 (2683) not available Materials Measuring pipe, flange and thread connection Stainless steel AISI 316L/1.4435 Hastelloy C22/2.4602 not available IP67 (NEMA 4) and stainless steel AISI 316L/1.4404, The housing is not rated for pressure containment Enclosure and enclosure material Process connections2) Flange EN 1092-1, PN 40 DN 10 DN 15 DN 25 DN 40 ANSI B16.5, Class 150 ½” ½” 1” 1½” ANSI B16.5, Class 600 (Class 300) ½” ½” 1” 1½” DIN 11851 DN 10 DN 15 DN 32 DN 40 ISO 2853/BS 4825 part 4 (SS3351) 25 mm 25 mm 38 mm 51 mm 25 mm 25 mm 38 mm 51 mm Dairy screwed connection (PN 16/25/40)3) Dairy clamp connection (PN 16)3) ISO 2852/BS 4825 part 3 (SMS3016) Thread ISO 228/1, PN 100 G¼” female G¼” male G½” male G1“ male G2“ male ANSI/ASME B1.20.1, PN 100 ¼” NPT female ¼” NPT male ½” NPT male 1“ NPT male 2“ NPT male Multiple plug connection to sensor 5 x 2 x 0.35 mm2 twisted and screened in pairs, ext. Ø 12 mm Cable connection Ex ia IIC T3-T6, DEMKO 03 ATEX 135252X Ex-version Weight approx. kg (lb) 4 (8.8) 1) Max. at 20 °C (68 °F), DIN 2413, DIN 17457 2) Other connections to order, see “Selection and Ordering data” 3) Material, AISI 316/1.4401 or corresponding 8 (17.6) For accuracy specification see “System information SITRANS F C”. 3/216 Siemens FI 01 · 2015 US Edition 12 (26.5) 48 (105.8) 70 (154.5) © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 3 to DI 15 Pressure drop D p [ bar] Viscosity [cSt] Δp [bar] 1000 10 500 200 100 50 20 Viscosity [cSt] 10 10 00 0 50 0 20 10 0 10 5 20 50 2 1 1 1.0 1.0 0.1 3 10 100 300 Mass flow [kg/h] MASS 2100 DI 3 (1/8”), pressure drop for density = 1000 kg/m3 0.1 60 100 1000 MASS 2100 DI 15 (½”), pressure drop for density = 1000 kg/m3 Viscosity [cSt] Δp [bar] 1000 10 500 6000 Mass flow [kg/h] Viscosity [cSt] 200 100 Δp [bar] 1000 10 500 50 20 200 1 100 50 1.0 1.0 20 1 0.1 10 100 1000 Mass flow [kg/h] MASS 2100 DI 6 (¼“), pressure drop for density = 1000 kg/m3 0.1 300 1000 10000 30000 Mass flow [kg/h] MASS 2100 DI 25 (1”), pressure drop for density = 1000 kg/m3 Siemens FI 01 · 2015 US Edition 3/217 3 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 3 to DI 15 ANSI Flange Ratings per ASME B16.5, Group Material 3.8 Viscosity [cSt] Δp [bar] 1000 500 200 1.0 CLASS600 100 98 90 80 70 60 50 20 CLASS300 50 49 1 40 30 20 CLASS150 0.1 500 1000 10000 50000 Mass flow [kg/h] 15 10 -20 0 30 80 130 180 Process temperature (°C) MASS 2100 DI 40 (1½”), pressure drop for density = 1000 kg/m3 ASME flanges B16.5 Hastelloy C22/2.4602 Pressure/temperature curves DIN 32676 ANSI Flange Ratings per ASME B16.5, Material Group 2.3 45 Process pressure (bar) 110 Process Pressure (bar) 100 90 80 CLASS600 70 60 35 30 25 PN25 25 60 50 15 PN16 16 40 CLASS300 10 PN10 10 30 5 30 -20 20 0 20 40 60 80 100 120 140 160 180 Process temperature (°C) 10 CLASS150 -20 40 20 0 30 80 130 12 180 DIN 32676 flanges stainless steel (PN 10 ... PN 25) Process temperature (°C) DIN 11851 ASME flanges B16.5 stainless steel 45 Process Pressure (bar) 3 100 Process Pressure (bar) 110 10 40 PN40 DN10 - DN40 40 35 30 25 PN25 DN50 - DN100 25 20 15 PN16 DN125 - DN150 16 10 5 -20 0 20 40 60 80 100 120 140 160 180 Process temperature (°C) DIN 11581 flanges stainless steel (PN 25 ... PN 40) 3/218 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 3 to DI 15 ISO 228, Pipe thread NPT - ANSI/ASME B1.20.1, Pipe thread Metric flange ratings, EN 1092-1, Material group 13E0 360 100 PN100 90 80 82 70 60 PN63 Process Pressure (bar) Process pressure (bar) 110 310 260 PN265 3 PN230 50 52 210 40 PN40 188 33 30 160 164 20 PN130 10 -20 0 30 80 130 110 180 Process temperature (°C) 92 PN100 71 60 EN 1092 flanges stainless steel (PN 40 ... PN 100) -20 0 30 80 130 180 Process temperature (°C) Flange EN 1092-1, UNS NO6022 ISO 228 and NPT pipe thread stainless steel (PN 100 ... PN 265) 100 PN100 ISO 228, Pipe thread NPT - ANSI/ASME B1.20.1, Pipe thread UNS NO6022 90 420 80 79 70 60 PN63 50 50 40 PN40 30 Process Pressure (bar) Process Pressure (bar) 110 PN410 370 PN365 PN350 320 322 270 287 275 31 20 10 -20 0 30 80 130 180 220 Process temperature (°C) EN 1092 flanges Hastelloy C22/2.4602 (PN 40 ... PN 100) PN200 PN185 170 157 145 120 -20 0 30 80 130 180 Process temperature (°C) ISO 218 and NPT pipe thread stainless steel (PN 185 ... PN 410) For further information on the PED standard and requirements, see page 9/6. Siemens FI 01 · 2015 US Edition 3/219 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 3 to DI 15 Selection and Ordering data Article No. Ord. code SITRANS F C sensors Article No. Ord. code SITRANS F C sensors MASS 2100 without heating jacket 7 ME 4 1 0 0 - MASS 2100 without heating jacket 7 ME 4 1 0 0 - MASS 2100 heated, DN 15 connection 7 ME 4 2 0 0 - MASS 2100 heated, DN 15 connection 7 ME 4 2 0 0 - MASS 2100 heated, ½ inch, ANSI B16.5 connection 7 ME 4 2 1 0 - MASS 2100 heated, ½ inch, ANSI B16.5 connection 7 ME 4 2 1 0 - 7 77 7 7 - 7 7 7 7 7 7 7 Click on the Article No. for the online configuration in the PIA Life Cycle Portal. 3 Selection and Ordering data 7777 7 - 7 7 7 7 7 7 7 Dairy screwed connection DIN 11851 Diameter Stainless steel AISI 316L/1.4435 DI 3 (PN 100/PN 230) 1C DI 6 DI 15 1D 1E Hastelloy C22/2.4602 DI 3 (PN 100/PN 350) DI 6 2C 2D DN 10 (PN 40) DN 15 (PN 40) DN 25 (PN 40) 40 41 42 DN 32 (PN 40) DN 40 (PN 25) DN 50 (PN 25) 43 44 45 DN 65 (PN 25) 46 Dairy clamp connection ISO 2852 (DIN 32676) Cone down the sensor in order to obtain selfdrainage with connectors ISO 2852 Pressure PN 16 (DI 6, DI 15) PN 25 (DI 6, DI 15) PN 40 (DI 6, DI 15) A B C PN 100 (DI 3, DI 6, DI 15) PN 130 (DI 15, ½“, AISI 316L/1.4404) D G PN 200 (DI 15, ½“, Hastelloy C22/2.4602) PN 230 (DI 3, ¼“, AISI 316L/1.4404) PN 265 (DI 6, ¼“, AISI 316L/1.4404) K L M PN 350 (DI 3, ¼“, Hastelloy C22/2.4602) PN 410 (DI 6, ¼“, Hastelloy C22/2.4602) N Q Class 150 (DI 6, DI 15) Class 600 (DI 6, DI 15) R S 25 mm (PN 16) 38 mm (PN 16) 51 mm (PN 16) 50 51 52 Dairy screwed connection ISO 2853 25 mm (PN 16) 38 mm (PN 16) 51 mm (PN 16) 60 61 62 Configuration/calibration type Standard Density Brix/Plato 1 2 3 Fraction (specification required) 9 N0Y Transmitter compact mounted on sensor Process connection/flange No transmitter, sensor and adapter only A G ¼“ ¼“ NPT G ½“ 10 11 12 MASS 6000, Ex d, stainless steel enclosure, 1 current, 1 freq./pulse and 1 relay output, 24 V AC/DC with Ex de [ia/ib] T3 -T6 Exapproval B ½“ NPT G1 1“ NPT 13 14 15 MASS 6000, IP67, Polyamide enclosure, cable glands M20, 1 current, 1 freq./pulse and 1 relay output, 24 V AC/DC C G 2“ 2“ NPT 16 17 MASS 6000, IP67, Polyamide enclosure, cable glands M20, 1 current, 1 freq./pulse and 1 relay output, 115/230 V AC 50/60 Hz D MASS 6000, IP67, Polyamide enclosure, cable glands ½" NPT, 1 current, 1 freq./pulse and 1 relay output, 24 V AC/DC E MASS 6000, IP67, Polyamide enclosure, cable glands ½" NPT, 1 current, 1 freq./pulse and 1 relay output, 115/230 V AC 50/60 Hz F Pipe thread Flange EN1092-1 Form B DN 10 (PN 40/PN 100) DN 15 (PN 40/PN 100) DN 25 (PN 40/PN 100) 20 21 22 DN 40 (PN 40/PN 100) DN 50 (PN 40/PN 100) 23 24 Flange ASME/ANSI B 16.5 ½“ (class 150/class 600) ¾“ (class 150/class 600) 1“ (class 150/class 600) 30 31 32 1 ½“ (class 150/class 600) 2“ (class 150/class 600) 33 34 Cable No cable 5 m (16.4 ft) cable 10 m (32.8 ft) cable A B C 25 m (82 ft) cable 50 m (164 ft) cable 75 m (246 ft) cable D E F 150 m (492 ft) cable G Calibration/verification 3/220 Siemens FI 01 · 2015 US Edition Standard calibration 3 flow x 2 points Stand. calibration matched pair 3 flow x 2 points Accredited calibration matched pair 5 flow x 2 points (DANAK to ISO 17025) 1 2 3 Extended calibration customer-specified select Y60, Y61, Y62 or Y63 (see additional information) 8 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 3 to DI 15 ■ Selection and Ordering data Dairy MLFB example 7 ME 4 1 0 0 - 77777 7777 MASS 2100 1E Sensor size DI 15, AISI 316L/1.4435 Accessories Description Dimension Article No. Mating parts for hygienic fittings DIN 11851 Includes: • 2 unions • 2 mating parts (for welding in) • 2 EPDM gaskets DN 10 FDK:085U1016 DN 15 FDK:085U1017 DN 25 FDK:085U1019 DN 32 FDK:085U1020 DN 40 FDK:085U1021 DN 50 FDK:085U1022 DN 65 FDK:085U1023 Mating parts for hygienic clamp ISO 2852 Includes: • 2 clamps • 2 mating parts • 2 EPDM gaskets 25 mm FDK:085U1029 40 mm FDK:085U1031 50 mm FDK:085U1032 2 EPDM gaskets with collar for mounting set DIN 11851 DN 10 FDK:085U1006 DN 15 FDK:085U1007 DN 25 FDK:085U1009 DN 32 FDK:085U1010 Addtional information DN 40 FDK:085U1011 Please add “-Z“ to Article No. and specify Order code(s) and plain text. DN 50 FDK:085U1012 DN 65 FDK:085U1013 C PN 40 41 DN 15 connector 1 Standard configuration/calibration D MASS 6000 IP67 compact mounted A No cable 1 Standard calibration, 3 flow x 2 points Order code Selection and Ordering data Pressure testing certificate PED: 97/23/EC C11 Material certificate EN 10204-3.1 C12 NDT- X-ray inspection report: EN 1435 DI3 sensor only: NDT-Penetrant inspection report ISO 3452. C13 Factory certificate according to EN 10204 2.2 C14 Factory certificate according to EN 10204 2.1 C15 Tag name plate, stainless steel Y17 Tag name plate, plastic Y18 Customer-specific transmitter setup Y20 Customer-specified, matched pair (5 x 2) Y60 Customer-specified calibration (5 x 2) Y61 Customer-specified, matched pair (10 x 1) Y62 Customer-specified calibration (10 x 1) Y63 Cleaned for oil and grease Y80 Special version Y99 Operating instructions for SITRANS F C MASS 2100 DI 3 to DI 40 Description Article No. 5 m (16.4 ft) FDK:083H3015 10 m (32.8 ft) FDK:083H3016 25 m (82 ft) FDK:083H3017 50 m (164 ft) FDK:083H3018 75 m (246 ft) FDK:083H3054 150 m (492 ft) FDK:083H3055 Spare parts Description Article No. Adapter for MASS 2100 FDK:083L8889 FDK:083H5056 Description Article No. Multiple plug for cable mounting • English A5E02896535 • German A5E03073519 • Spanish A5E03073549 2 kB SENSORPROM unit, including programming (Sensor Serial No. and Article No. must be specified by ordering) • French A5E03073539 This device is shipped with a Quick Start guide and a CD containing further SITRANS F literature. Length Cable with multiple plug Standard blue cable between MASS 6000 and MASS 2100, 5 x 2 x 0.34 mm2 twisted and screened in pairs. Temperature range -20 °C ... +110 °C (-4 °F ... +230 °F) FDK:083H4410 All literature is also available for free at: http://www.siemens.com/flowdocumentation Siemens FI 01 · 2015 US Edition 3/221 3 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 3 to DI 15 ■ Dimensional drawings MASS 2100 sensor 155 (6.10) 130 (5.12) L2 225 (8.86) L2 88 (3.5) D1 D4 H1 D2 77 (3.03) B1 D3 284 (11.2) 3 L1 D5 L1 Flange EN 1092-1 ANSI B16.5 L1 Clamp ISO 2852 L1 Dairy screwed connection DIN 11851 (Connection) L1 Screwed connector for Di 3 ISO 228/1-G 1/4 and ANSI/ASME B1.20.1-1983 1/4 NPT 17.5 (0.69) Dimension in mm (inch) For not listed variants please contact product support Sensor size Connections DI (inch) Type Pressure rating Size DI 3 (1/8) Pipe thread ISO 228/1 - G¼ Pipe thread ANSI/ASME B 1.20.1 - ¼” NPT PN 100 PN 100 DI 6 (¼) Flange EN 1092-1 Flange EN 1092-1 Flange ANSI B16.5 Flange ANSI B16.5 Screwed connection DIN 11851 Clamp ISO 2852 Flange EN 1092-1 Flange EN 1092-1 Flange ANSI B16.5 Flange ANSI B16.5 Screwed connection DIN 11851 Clamp ISO 2852 Flange EN 1092-1 Flange EN 1092-1 Flange ANSI B16.5 Flange ANSI B16.5 Screwed connection DIN 11851 Clamp ISO 2852 Flange EN 1092-1 Flange EN 1092-1 Flange ANSI B16.5 Flange ANSI B16.5 Screwed connection DIN 11851 Clamp ISO 2852 PN 100 PN 40 Class 150 Class 600 PN 40 PN 16 PN 100 PN 40 Class 150 Class 600 PN 40 PN 16 PN 100 PN 40 Class 150 Class 600 PN 40 PN 16 PN 100 PN 40 Class 150 Class 600 PN 25 PN 25 DI 15 (½) DI 25 (1) DI 40 (1½) 3/222 Siemens FI 01 · 2015 US Edition L1 mm L2 mm L3 mm H1 mm B1 mm D1 mm D2 mm D3 mm D4 mm D5 mm ¼” ¼” 400 400 280 280 75.5 75.5 60 60 0 0 21.3 21.3 104 104 - - - DN 10 DN 10 ½“ ½“ DN 10 25 mm DN 15 DN 15 ½“ ½“ DN 15 25 mm DN 25 DN 25 1“ 1“ DN 32 38 mm DN 40 DN 40 1½“ 1½“ DN 50 51 mm 580 560 624 608 532 570 634 620 639 660 586 624 970 934 967 992 922 940 1100 1063 1100 1128 1090 1062 390 390 390 390 390 390 444 444 444 444 444 444 700 700 700 700 700 700 850 850 850 850 850 850 62.0 62.0 62.0 62.0 62.0 62.0 75.5 75.5 75.5 75.5 75.5 75.5 75.5 75.5 75.5 75.5 75.5 75.5 75.5 75.5 75.5 75.5 75.5 75.5 40 40 40 40 40 40 44 44 44 44 44 44 126 126 126 126 126 126 180 180 180 180 180 180 12 12 12 12 12 12 20 20 20 20 20 20 25 25 25 25 25 25 0 0 0 0 0 0 17.0 17.0 17.0 17.0 17.0 17.0 21.3 21.3 21.3 21.3 21.3 21.3 33.7 33.7 33.7 33.7 33.7 33.7 48.3 48.3 48.3 48.3 48.3 48.3 104 104 104 104 104 104 129 129 129 129 129 129 219 219 219 219 219 219 273 273 273 273 273 273 100 90.0 88.9 95.3 105 95.0 88.9 95.3 140.0 115.0 108.0 124.0 170.0 150.0 127.0 155.4 - 70.0 60.0 60.5 66.5 75.0 65.0 60.5 66.5 100.0 85.0 79.2 88.9 125.0 110.0 98.6 114.3 - 14.0 14.0 15.7 15.7 14.0 14.0 15.7 15.7 18.0 14.0 15.7 19.1 22.0 18.0 15.7 22.4 - © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 3 to DI 15 For not listed variants please contact product support. Sensor size Connections DI (inch) Type Pressure rating Size DI 3 (1/8) Pipe thread ISO 228/1 - G¼ PN 100 Pipe thread ANSI/ASME B 1.20.1 - ¼” NPT PN 100 DI 6 (¼) Flange EN 1092-1 Flange EN 1092-1 DI 15 (½) DI 25 (1) DI 40 (1½) L1 inch L3 inch H1 inch B1 inch D1 inch D2 inch D3 inch D4 inch D5 inch ¼” 15.75 11.02 2.97 2.36 0 0.84 4.09 - - - ¼” 15.75 11.02 2.97 2.36 0 0.84 4.09 - - - PN 100 DN 10 22.83 15.35 2.44 1.57 0.47 0.67 4.09 3.94 2.76 0.55 PN 40 DN 10 22.05 15.35 2.44 1.57 0.47 0.67 4.09 3.54 2.36 0.55 Flange ANSI B16.5 Class 150 ½“ 24.57 15.35 2.44 1.57 0.47 0.67 4.09 3.5 2.38 0.62 Flange ANSI B16.5 Class 600 ½“ 23.94 15.35 2.44 1.57 0.47 0.67 4.09 3.75 2.62 0.62 Screwed connection DIN 11851 PN 40 DN 10 20.94 15.35 2.44 1.57 0.47 0.67 4.09 - - - Clamp ISO 2852 PN 16 25 mm 22.44 15.35 2.44 1.57 0.47 0.67 4.09 - - - Flange EN 1092-1 PN 100 DN 15 24.96 17.48 2.97 1.73 0.79 0.84 5.08 2.95 4.13 0.55 Flange EN 1092-1 PN 40 DN 15 24.41 17.48 2.97 1.73 0.79 0.84 5.08 3.74 2.56 0.55 Flange ANSI B16.5 Class 150 ½“ 25.16 17.48 2.97 1.73 0.79 0.84 5.08 3.5 2.38 0.62 Flange ANSI B16.5 Class 600 ½“ 25.98 17.48 2.97 1.73 0.79 0.84 5.08 3.75 2.62 0.62 Screwed connection DIN 11851 PN 40 DN 15 23.07 17.48 2.97 1.73 0.79 0.84 5.08 - - - Clamp ISO 2852 PN 16 25 mm 24.57 17.48 2.97 1.73 0.79 0.84 5.08 - - - Flange EN 1092-1 PN 100 DN 25 38.19 27.56 2.97 4.96 0.98 1.33 8.62 3.94 5.51 0.71 Flange EN 1092-1 PN 40 DN 25 36.77 27.56 2.97 4.96 0.98 1.33 8.62 4.53 3.35 0.55 Flange ANSI B16.5 Class 150 1“ 38.07 27.56 2.97 4.96 0.98 1.33 8.62 4.25 3.12 0.62 Flange ANSI B16.5 Class 600 1“ 39.06 27.56 2.97 4.96 0.98 1.33 8.62 4.88 3.50 0.75 Screwed connection DIN 11851 PN 40 DN 32 36.30 27.56 2.97 4.96 0.98 1.33 8.62 - - - Clamp ISO 2852 PN 16 38 mm 37.01 27.56 2.97 4.96 0.98 1.33 8.62 - - - Flange EN 1092-1 PN 100 DN 40 43.31 33.46 2.97 7.09 0 1.9 10.75 4.92 6.69 0.87 Flange EN 1092-1 PN 40 DN 40 41.85 33.46 2.97 7.09 0 1.9 10.75 5.91 4.33 0.71 Flange ANSI B16.5 Class 150 1½“ 43.31 33.46 2.97 7.09 0 1.9 10.75 5 3.88 0.62 Flange ANSI B16.5 Class 600 1½“ 44.41 33.46 2.97 7.09 0 1.9 10.75 6.12 4.50 0.88 Screwed connection DIN 11851 PN 25 DN 50 42.91 33.46 2.97 7.09 0 1.9 10.75 - - - Clamp ISO 2852 51 mm 41.81 33.46 2.97 7.09 0 1.9 10.75 - - - PN 25 L2 inch Siemens FI 01 · 2015 US Edition 3/223 3 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MASS 2100 DI 3 to DI 15 MASS 2100 sensor with “heating jacket” H3 L5 D6 D7 B2 H3 3 D8 Dimensions in mm (inch) Sensor size Connections heated L5 H3 B2 D6 D7 D8 DI (inch) Type Pressure rating Size mm (inch) mm (inch) mm (inch) mm (inch) mm (inch) mm (inch) DI 3 (1/8) EN 1092-1 PN 40 DN 15 234 (9.21) 122 (4.8) 22 (0.87) 95 (3.74) 65.0 (2.56) 14.0 (0.55) ANSI B16.5 Class 150 ½" 234 (9.21) 131.6 (5.18) 22 (0.87) 88.9 (3.5) 60.5 (2.38) 15.7 (0.62) EN 1092-1 PN 40 DN 15 234 (9.21) 112 (4.41) 22.7 (0.89) 95 (3.74) 65.0 (2.56) 14.0 (0.55) ANSI B16.5 Class 150 ½" 234 (9.21) 121.6 (4.79) 22.7 (0.89) 88.9 (3.5) 60.5 (2.38) 15.7 (0.62) EN 1092-1 PN 40 DN 15 234 (9.21) 126.5 (4.98) 31.5 (1.24) 95 (3.74) 65.0 (2.56) 14.0 (0.55) ANSI B16.5 Class150 ½" 234 (9.21) 136.1 (5.36) 31.5 (1.24) 88.9 (3.5) 60.5 (2.38) 15.7 (0.62) EN 1092-1 PN 40 DN 15 420 (16.54) 213.6 (8.41) 60 (2.36) 95 (3.74) 65.0 (2.56) 14.0 (0.55) ANSI B16.5 Class 150 ½" 420 (16.54) 223.2 (8.79) 60 (2.36) 88.9 (3.5) 60.5 (2.38) 15.7 (0.62) EN 1092-1 PN 40 DN 15 500 (19.68) 267.5 (10.53) 43 (1.69) 95 (3.74) 65.0 (2.56) 14.0 (0.55) ANSI B16.5 Class 150 ½" 500 (19.68) 277.1 (10.91) 43 (1.69) 88.9 (3.5) 60.5 (2.38) 15.7 (0.62) DI 6 (¼) DI 15 (½) DI 25 (1) DI 40 (1½) MASS 2100 and MASS 6000 Ex d compact version MASS 2100 and MASS 6000 IP67 compact version Ø130 (5.12) + H5 H6 + 255.1 (10.04) L3 / Dimensions in mm (inch) Dimensions in mm (inch) Sensor size L3 [mm (inch)] [DI (inch)] H5 H6 H5 + H6 [mm (inch)] [mm (inch)] [mm (inch)] Sensor size L3 H5 H6 [DI (inch)] [mm (inch)] [mm (inch)] [mm (inch)] H5 + H6 [mm (inch)] 3 (1/8) 75 (2.95) 82 (3.23) 247 (9.72) 329 (12.95) 3 (1/8) 75 (2.95) 82 (3.23) 306 (12.04) 388 (15.28) 6 (¼) 62 (2.44) 72 (2.83) 257 (10.12) 329 (12.95) 6 (¼) 62 (2.44) 72 (2.83) 316 (12.44) 388 (15.28) 15 (½) 75 (2.95) 87 (3.43) 267 (10.51) 354 (13.94) 15 (½) 75 (2.95) 87 (3.43) 326 (12.83) 413 (16.26) 25 (1) 75 (2.95) 173 (6.81) 271 (10.67) 444 (17.48) 25 (1) 75 (2.95) 173 (6.81) 330 (13.00) 503 (19.80) 40 (1½) 75 (2.95) 227 (8.94) 271 (10.67) 498 (19.61) 40 (1½) 75 (2.95) 227 (8.94) 330 (13.00) 557 (21.93) 3/224 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MC2 ■ Overview SITRANS F C MC2 is available in sizes DN 100 and DN 150 (4" and 6"). The MC2 sensor is suitable for accurate mass flow measurement of a variety of liquids. The sensor offers superior performance in terms of flow accuracy, turn-down ratio and density accuracy and delivers true multi-parameter measurements i.e.: mass flow, volume flow, density, temperature and fraction flow. The very compact sensor construction makes installation and commissioning of even the largest sizes very straight forward and easy. ■ Benefits • High accuracy better than 0.15 % of mass flow rate • Large dynamic turn-down ratio • Densitometer performance available through density accuracy better than 0.001 g/cm3 • Space-saving split-flow sensor design facilitating low pressure loss • Parallel S-tube design and optimal oriented inductive sensors enhances accuracy and turn-down ratio. • Self-draining in both horizontal and vertical position • Rigid enclosure design reduces the influence from pipeline vibration and thermal stress • 4-wire Pt100 temperature measurement ensures optimum accuracy on mass flow, density and fraction flow • SENSORPROM enables true "plug & play" - installed and commissioned in less than 10 minutes. • Safe Ex design Ex em [ib] IIC • Sensor pipe available in high-quality stainless steel AISI 316Ti/1.4571 or Hastelloy C4/2.4610 offering optimum corrosion resistance. • CIP cleanability for food and beverage and pharmaceutical applications The main applications of the Coriolis flowmeter can be found in all industries, such as: Chemical and pharma Detergents, bulk chemicals, pharmaceuticals, acids, alkalis Food and beverage Dairy products, beer, wine, softdrinks, Plato/Brix, fruit juices and pulps, bottling, CO2 dosing, CIPliquids Oil and gas Liquid measurement, furnace control, test separators, LPG, oil bunkering Water and waste water Dosing of chemicals for water treatment The wide variety of combinations and versions from the modular system means that ideal adaptation is possible to each measuring task. MC2 ist not recommended for gas applications. ■ Design The MC2 sensor consists of 2 parallel measuring pipes, welded directly onto a flow-splitter at each end to eliminate a direct coupling to the process connectors and significantly reduce effects from external vibrations. The flow-splitters are welded onto a rigid sensor housing which acts as a mechanical low-pass filter. The sensor is available in 2 material configurations, AISI 316L/ 1.4436 or Hastelloy C4/2.4610 with a wide variety of process connections. The enclosure is made of stainless steel AISI 304/1.4301 with an encapsulation grade of IP67/NEMA 4. The sensor is Ex-approved Ex em [ib] IIC. It can be installed in horizontal or vertical position, and is selfdraining in both positions. The MC2 Ex version sensor is based on a different Ex concept than MASS 6000. Therefore the MC2 Ex version sensor can only be connected to MASS 6000 IP67, MASS 6000 19" or SIFLOW FC070 standard versions, which have to be remote mounted in the safe area. MASS 6000 Ex d, MASS 6000 19" Ex and SIFLOW FC070 Ex can not be used with MC2 Ex sensors. ■ Application Coriolis mass flowmeters are suitable for measuring all liquids. The measurement is independent of changes in process conditions/parameters such as temperature, density, pressure, viscosity, conductivity, and flow profile. Due to this versatility the meter is easy to install and the Coriolis flowmeter is recognized for its high accuracy in a wide turndown ratio which is paramount in many applications. Hazardous area Zone 1 + 2 Safe area MC2 sensors are not designed or approved for flow measurement of gaseous process media. The product is manufactured by ABB Automation Products GmbH and distributed by Siemens. Siemens FI 01 · 2015 US Edition 3/225 3 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MC2 Avoid cross talk ■ Function The measuring principle is based on the Coriolis effect. See “System information Coriolis mass flowmeters”. ■ Integration Installation guidelines MC2 DN 100 and DN 150 Installation of sensor The optimal installation orientation is a vertical installation with an upward flow as shown in the following figure. This has the advantage that any solids contained in the fluid will settle downward and gas bubbles will move upward out of the meter tube when the flow rate is zero. Additionally, it is easy to drain the meter tube. Deposits can thereby be avoided. Installation in a drop line Mount with reduction (A) or orifice (B) to prevent partially draining (min. back pressure: 0.2 bar). Vertical orientation: A B Vertical installation self-draining (upward flow) Horizontal orientation, self-draining α 3 Rigid mounting brackets must be used when installing the sensor. The brackets must be installed as close to the sensor as possible, attached to the piping outside the process connections. Installation in a drop line Avoid vibrations 3/226 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MC2 ■ Technical specifications 150 (6) Inside pipe diameter mm (inch) 43.1 (1.69) 76.1 (2.99) Pipe wall thickness mm (inch) 2.6 (0.10) 3.2 (0.13) Fraction e.g. Brix °Brix 10 0 0.5 ... 3.5 (0.18 ... 0.126) DN g/cm3 (lb/inch3) 602 000 (1 327 181) 100 3 (6 ˝ ) Density 203 500 (448 640) p [mbar] 1000 0 ... 100 (on request) Not possible DN Mass flow measurkg/h ing range at pressure (lb/h) drop of 2 bar (29 psi) at 1 g/cm3 (0.036 lb/inch3) Pressure drop (4˝ ) 100 (4) 150 Versions (mm (inch)) Temperature Standard-version -50 ... +200 °C (-58 ... +392 °F) Ex-version -50 ... +200 °C (-58 ... +392 °F) 10 1 10 100 1000 10000 0DVVIORZ>NJPLQ@ Liquid pressure measuring pipe Stainless steel (DIN 2413, 20 °C (68 °F)) bar (psi) 40 (580) 40 (580) Materials Measuring pipe Stainless steel AISI 316Ti/1.4571 or Hastelloy C4/2.4610 IP67 Enclosure Enclosure material/ connection box AISI 304 (1.4301)/aluminum, max. pressure 40 bar (580 psi) Process connections See dimensional drawings Electrical connections Screw terminals, M 20 5 x 2 x 0.35 mm2 twisted and screened in pairs, ext. Ø 12 mm Cable 10, 25, 75 or 150 m (32.8, 82, 246 or 492 ft.) Cable length Ex-version ATEX 1443X Weight approx. II 2G Ex em [ib] IIC T2-T6 kg (lb) 91 (201) 261 (573) For accuracy specifications see „System information Coriolis mass flowmeters“. Siemens FI 01 · 2015 US Edition 3/227 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MC2 Selection and Ordering data Article No. Ord. code SITRANS F C flow sensors MC2 7 ME 4 3 0 0 7 77 7 7 - 777 7 77 7 Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Dairy MLFB example MC2 sensor Article No. 7 ME 4 3 0 0 - 77777 - 7777 Sensor size DN 100. AISI 316Ti/1.4571 Nominal pressure: Clamps DIN 11851, DN 100, PN 25 1D F 43 Nominal diameter Stainless steel AISI 316Ti/1.4571 1D 1E DN 100 DN 150 3 2D 2E DN 100 DN 150 Nominal pressure PN 40 Class 150 Class 300 Clamps/screwed-connections 1 Configuration/calibration type: flow and density (5 kg/m3 [0.31 lb/ft3]) Without Ex appproval No cable Standard calibration Hastelloy C4/2.4610 A C D F Selection and Ordering data A A 1 Order code Additional information Please add “-Z“ to Article No. and specify Order code(s) and plain text. Process connections Pressure testing certificate PED: 97/23/EC C11 Flange EN 1092-1 DN 80 (PN 40, PN 100) DN 100 (PN 40) DN 150 (PN 40) Material certificate EN 10204-3.1 C12 Material certificate according to NACE C16 Tag name plate, stainless steel Y17 Tag name plate, plastic self-adhesive Y18 Customer-specified, matched pair (5 x 2) On request Customer-specified calibration (5 x 2) On request Customer-specified, matched pair (10 x 1) On request Customer-specified calibration (10 x 1) On request Flange ASME/ANSI B16.5 3“ (class 150/300/600) 4“ (class 150/300) 6“ (class 150/300) Dairy screwed connection to DIN 11851 DN 80 (PN 25) DN 100 (PN 25) 22 23 24 32 33 34 42 43 Operating instructions for SITRANS F C MC2 Dairy clamp connection DIN 32676 (ISO 2852) Tri-clamp 81 mm clamp (PN 10) 100 mm clamp (PN 10) 52 53 Aseptic nut flange DIN 11864-2 form A for pipes dimensioned by DIN 11866 DN 80 (3“) DN 100 (4“) 63 64 Configuration Flow (0.15% of rate) and density (5 kg/m3 [0.31 lb/ft3]) Flow (0.15% of rate) and density (1 kg/m3 [0.06 lb/ft3]) Ex-approval and cable gland Non-Ex, M20 x 1.5 ATEX, M20 x 1.5 Cable No cable All literature is also available for free at: http://www.siemens.com/flowdocumentation 1 5 A B A Calibration Standard 3/228 This device is shipped with ABB documentation and an installation/connection instruction in four languages (Article No. A5E34730442). 1 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MC2 ■ Dimensional drawings Remote design, flanged construction, DIN EN/ANSI $ 3 ) * )ODQJHV (1 $16,% ,62 )ORZGLUHFWLRQ / % Process L connec- [mm (inch)] tion size inch DN inch DN DIN 11864-2 form A 4 100 3 80 1618 (63.70) 4 100 1463 (57.60) 6 150 N/A 6 150 6 150 N/A G1) F B A Weight [mm [mm [mm [kg (lb)] [mm (inch)] (inch)] (inch)] (inch)] Meter size 1) EN 1092-1 PN 40 1640 (64.57) 1480 (58.27) 1778 (69.92) 2040 (80.31) EN 1092-1 PN 100 1680 (66.14) 1530 (60.24) N/A N/A ANSI B16.5 CL 150 1660 (65.35) 1500 (59.06) 1806 (71.10) 2070 (81.50) ANSI B16.5 CL 300 1680 (66.14) 1520 (59.84) 1826 (71.89) 2090 (82.28) ANSI B16.5 CL 600 1702 (67.01) 500 1568 (61.73) (19.69) N/A N/A 613 (24.13) 215 (8.46) 131 (5.16) 170 (6.69) 285 190 (11.22) (7.84) 260 (9.84) 84 (185) 91 (201) 120 (265) 260 (573) For Ex add 54 mm Remote design, food industry fittings, DIN 11851 Food industry fittings DIN 11851 Ø80 Ø80 Threaded stubs Threaded stubs F A G R Flow direction L B Meter size Process connection size inch 4 inch 3 4 1) DN 100 g DN 80 100 Rd 110 x 1/6 Rd 130 x ¼ L [mm (inch)] g [mm (inch)] 1618 (63.70) 8 (0.31) 1463 (57.60) 10 (0.39) L G1) [mm (inch)] F [mm (inch)] 500 (19.69) 215 (8.46) 131 (5.16) 170 (6.69) 401 (15.79) 314 (12.36) B [mm (inch)] A [mm (inch)] R [mm (inch)] Weight [kg (lb)] 82 (180) 86 (190) For Ex add 54 mm Siemens FI 01 · 2015 US Edition 3/229 © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MC2 Remote design, Tri-clamp DIN 32676 (ISO 2852) 80 80 G R F A 3 Flow direction L B Dimensions in mm (inch) L G1) F B A R [mm (inch)] 3 [mm (inch)] [mm (inch)] [mm (inch)] [mm (inch)] [mm (inch)] Weight [kg (lb)] 80 1598 (62.91) 440 (17.32) 71 (157) 100 1448 (57.01) 365 (14.37) 69 (152) Meter size Process connection size inch DN inch DN 4 100 3 4 1) For Ex add 54 mm 3/230 Siemens FI 01 · 2015 US Edition 500 (19.69) 215 (8.46) 131 (5.16) 170 (6.69) © Siemens AG 2015 Flow Measurement SITRANS F C Flow sensor MC2 The max. allowable operating pressure is a function of the process connection type, the fluid temperature, the bolts and the gaskets. 3UHVVXUH>EDU@ Pressure/temperature curves Process Connections • Flanges EN 1092-1/ANSI B16.5 • Tri-Clamp DIN 32676 (ISO 2852) - DN 100: Series 1 • Food Industry fittings DIN 11851 80 40 PN 40 3 20 PN 16 0 -50 Housing as secondary containment • Max. 40 bar Pressure Equipment Directive 97/23/EG • Conformity evaluation category III, fluid group 1 PSmax. at 20 °C (68 °F) TSmax. TSmin. 3UHVVXUH>EDU@ Material strength for process connections Size 0 50 100 150 7HPSHUDWXUH>r&@ DIN-Flanges stainless steel AISI 316Ti/1.4571 to DN 100 (4”) Corrosion resistance of measuring pipe material to measuring medium has to be considered. 120 100 80 60 DN inch bar (psi g) °C (°F) 100 4 25 (363) 140 (284) -40 (-40) Tri-Clamp acc. 100 DIN 32676 4 10 (145) 120 (248) -40 (-40) Thread acc. DIN 11851 100 60 PN 63 Pressure Rating • PN 16, PN 40 Class 150, Class 300 Process connection 120 °C (°F) 40 20 300 lb 150 lb 0 -50 0 50 100 150 7HPSHUDWXUH>r&@ ASME-Flanges stainless steel AISI 326Ti/1.4571 to DN 100 (4”) For further information on the PED standard and requirements, see page 9/6. Siemens FI 01 · 2015 US Edition 3/231