Specification Sheet

SM6000 Series
L A B O R A T O R Y P O W E R S U P P LY
FEATURES
• 6000W Laboratory Supply
• Ranges 0-15V to 0-600V and 0-10A to 0-400A
• Designed for long life at full power
• Excellent dynamic response to load changes
• Protected against all overload and short circuit conditions
• EMC surpasses CE requirements for low emissions and
high immunity
• Low audible noise - fans are temperature controlled
• Master/Slave parallel and series operation with voltage and
current sharing
• High power system configuration from multiple units
• 19" rack mounting for for laboratory use (feet included)
• Stacking is allowed & space between units is not required
SPECIFICATIONS
INPUT
STANDARDS & APPROVALS
Input voltages
342 - 457Vac 3Ph
Input Frequency
48 - 62Hz
Power Factor
400V 3Ph, full load
0.98, with 100% load
0.97 with 50% load
Input Current
10.2A rms (400Vac 3ph)
Internal Fuse
15 AT
Standby input power
55W Vo = 0
110W Vo = max
ENVIRONMENTAL
Turn on delay
200ms (after mains switch on)
Operating Temperature
-20°C to +50°C (100% load)
Derate output to 75% at 60°C
Inrush Current
20A (electronic limit)
Temperature Coefficient
0.02%./°C
Phase Loss
Output shuts down in case of phase loss
6ms 100% load Vin=3x380Vac
15ms 50% load Vin=3x380Vac
Storage temperature
-40°C to 85°C.
Programming Connector
15 pole D-connector at rear panel (FEMALE)
Hold-up time
Safety
cTUVus / EN60950 / EN61010
Power Supply Standard
EN61204-3
Emission residential light industrial
environment CISP22 Class B
Immunity - industrial environment
General Emission
EN61000-6-3 residential, light industrial
environment EN55022B
EN61000-6-2, industrial environment
Thermal Protection
OUTPUT
Output Voltage Range
0-15V to 0-600V
Auto ranging models
See Selection Table
Output Current Range
0-10A to 0-400A
Auto ranging models
See Selection Table
Output Power Range
0 to 6000W
See Selection Table
Humidity
Output shuts down in case of insufficient
cooling
max 95% RH, non condensing up to 40°C
max 75% RH, non condensing up to 50°C
MECHANICAL
Mounting
-20°C to +50°C (100% load)
Derate output to 75% at 60°C
Input Connector
Screw terminals for cable 2.5 - 4.0mm2
3 phase + earth (no neutral required)
Output Terminals
0-15V: M12 bolts
0-30V, 0-45V, 0-60V,0-70V M10 bolts
0-120V, 0-300V, 0-600V; M8 bolts
Programming Connector
15 pole D-connector at rear panel (FEMALE)
Enclosure
IP20 Protection
Dimensions
177x 443 x 500mm Behind front panel
(feet removed)
177 x 483mm, Front panel
(19" 4U)
Weight
27kg
www.powerbox.com.au - 1800 251 380
www.powerbox.co.nz - 0800 104 480
Doc. No. SM6000 Rev.A 3-12-15
SM6000 Series
L A B O R A T O R Y P O W E R S U P P LY
SPECIFICATIONS
PROGRAMMING
Programming Inputs: CV
Programming Inputs: CC
Monitoring Outputs: CV
Monitoring Outputs: CC
Reference voltage
+12V Output
OPERATING
Input Range: 0 - 5V
Accuracy: +/-0.2%
Offset: -0.1...+1.3mV (on 5V)
Temp. coeff. offset:: 10uV/C
Input Impedance: > 1Mohm
Input Range: 0 - 5V
Accuracy: +/-0.5%
Offset: 0...+2.2mV (on 5V)
Temp. coeff. offset:: 50uV/C
Input Impedance: > 1Mohm
Input Range: 0 - 5V
Accuracy: +/-0.2%
Offset: -1.1..0mV (on 5V)
Temp. coeff. offset:: 3uV/C
Output Impedance:
> 2 ohm / max 4mA
Input Range: 0 - 5V
Accuracy: +/-0.5%
Offset: -1.1..0mV (on 5V)
Temp. coeff. offset:: 60uV/C
Output Impedance:
> 2 ohm / max 4mA
Vref: 5.114V +/-15mV (Ro = 2ohm, max
4mA)
TC: 20ppm
Vo: 12V+/-0.23V
Imax: 0.2A
Ro: 3ohm
Series Operation
Max total voltage 600V
Master / Slave operation yes
Parallel Operation
Max total current - No limit
Master / Slave operation - max 4 units (including master)
Remote Sensing
Max volt, drop per load lead: 2V
Potentiometers & Encoders
Standard: Front panel control with knobs
Resolution: 0.03%
Screwdriver adjustment
Option P001
Digital encoders
Option P002
Remote Shutdown
with +5V, 1mA or relay contact
Interlock
Contact at rear panel
Indicators
Voltage meter, Amp meter, AC-Fail, DC-Fail, Over
Temperature, Power Sink Overload, Remote Shutdown,,
Remote-CV, Remote-CC, Output On,CV-limite, CV- and
CC- mode
Controls
Mains on/off switch, CV and VV potmeter, CV and CC limit
potmeter, Displlay Settings button, Display limits button,
Remote/Local button, Output On/off button, Fron panel
lock button
Efficiency
87% Typical
Isolation
Input - Output: 3750Vrms(1 min)
Creepage clearance; 8mm
Input - Case: 2500Vrms
Output - Case: 600VDC
MTBF
500,000hrs
SELECTION TABLE
OUTPUT
SM 15-400
SM 30-200
SM 45-140
SM 60-100
SM 70-90
SM 120-50
SM 300-20
SM 600-10
Output Voltage Range
0 - 15V
0 - 30V
0 - 45V
0 - 60V
0 - 70V
0 - 120V
0 - 300V
0 - 600V
Output Current Range
0 - 400A
0 - 200A
0 - 140A
0 - 100A
0 - 90A
0 - 50A
0-20A
0-10A
Meters
3.5 digit
3.5 digit
3.5 digit
3.5 digit
3.5 digit
3.5 digit
3.5 digit
3.5 digit
Scale voltage
0 - 15.00 V
0 - 30.0 V
0 - 45.0 V
0 - 60.0 V
0 - 70.0 V
0 - 120 V
0 - 300 V
0 - 600 V
Scale current
0 - 400 A
0 - 200 A
0 - 140A
0 - 100A
0 - 90A
0 - 50A
0-20A
0-10A
Accuracy
0.5% + 2 digit 0.5% + 2 digit 0.5% + 2 digit 0.5% + 2 digit 0.5% + 2 digit 0.5% + 2 digit 0.5% + 2 digit 0.5% + 2 digit
PROGRAMMING SPEED
STANDARD VERSION
SM 15-400
SM 30-200
SM 45-140
SM 60-100
SM 70-90
SM 120-50
Rise time (10 - 90%)
Output voltage step
Time, (100 % load)
Time, (10 % load)
0 - 15 V
7 ms
7 ms
0 - 30 V
7 ms
7 ms
0 - 45 V
7 ms
7 ms
0 - 70 V
7 ms
7 ms
0 - 120 V
7 ms
7 ms
0 - 300 V
7 ms
7 ms
Fall time (90 - 10%)
Output voltage step
Time, (100 % load)
Time, (10 % load)
15 - 0 V
7 ms
32 ms
30 - 0 V
7 ms
58 ms
45 - 0 V
87 ms
29 ms
70 - 0 V
8 ms
82 ms
120 - 0 V
7 ms
39 ms
300 - 0 V
11 ms
91 ms
Programming bandwidth
Small signal
Large signal,(100 % load)
Large signal,(10 % load)
50 Hz
50 Hz
5 Hz
50 Hz
50 Hz
5 Hz
50 Hz
50 Hz
5 Hz
50 Hz
50 Hz
5 Hz
50 Hz
50 Hz
5 Hz
50 Hz
50 Hz
5 Hz
www.powerbox.com.au - 1800 251 380
www.powerbox.co.nz - 0800 104 480
SM 300-20
SM 600-10
-
-
-
-
-
-
Doc. No. SM6000 Rev.A 3-12-15
SM6000 Series
L A B O R A T O R Y P O W E R S U P P LY
TECHNICAL ILLUSTRATIONS
www.powerbox.com.au - 1800 251 380
www.powerbox.co.nz - 0800 104 480
Doc. No. SM6000 Rev.A 3-12-15