Datenblatt

For more information, please visit the product page.
date
07/22/2013
page
1 of 4
SERIES: VMS-100 │ DESCRIPTION: AC-DC POWER SUPPLY
FEATURES
•
•
•
•
•
•
•
•
•
•
•
up to 100 W continuous power
industry standard 3” x 5” footprint
universal input (90~264 Vac)
single output from 5 to 48V
no load power consumption < 0.5W
over voltage and short circuit protections
full medical approvals
built-in active PFC function
built-in remote sense function
no minimum load required
efficiency up to 91%
RoHS
MODEL
VMS-100-5
VMS-100-9
output
voltage
output
current
output
power
ripple and
noise1,2
efficiency
(Vdc)
max
(A)
max
(W)
max
(mVp-p)
typ
(%)
5
20
100
100
85
9
11.2
100
90
88
VMS-100-12
12
8.4
100
120
89
VMS-100-15
15
6.7
100
150
89
VMS-100-18
18
5.6
100
180
90
VMS-100-24
24
4.2
100
240
91
VMS-100-28
28
3.6
100
280
91
VMS-100-36
36
2.8
100
360
91
VMS-100-48
48
2.1
100
480
91
Notes:
1. VMS-100-5: Measured at 20MHz, with 0.1μF ceramic and 220μF electrolytic capacitors
2. All other models: Measured at 20MHz, with 0.1μF ceramic and 10μF electrolytic capacitors
PART NUMBER KEY
VMS-100 - XX
Base Number
Output Voltage
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: VMS-100 │ DESCRIPTION: AC-DC POWER SUPPLY
date 07/22/2013
page 2 of 4
INPUT
parameter
conditions/description
min
voltage
frequency
inrush current
typ
90
47
at 240 Vac
max
units
264
Vac
63
Hz
80
A
max
units
OUTPUT
parameter
conditions/description
line regulation
low line to high line, full load
load regulation
10% to 100% full load
min
typ
±0.5
temperature coefficient
hold-up time
%
±1
%
±0.05
%/°C
16
adjustability
switching frequency
80
ms
±5
%
100
kHz
PROTECTIONS
parameter
conditions/description
over voltage protection
recycle ac input to restart
short circuit protection
hiccup mode, recovers automatically
min
typ
max
units
min
typ
max
units
SAFETY & COMPLIANCE
parameter
conditions/description
isolation voltage
input to output
5,656
Vdc
safety approvals
IEC 60601-1, EN 60601-1, UL 60601-1
EMI/EMC
EN 55024, EN 61000-6-1, EN 61204-3, EN 60601-1-2, EN 61000-3-2 Class (A, B, C, D), EN 61000-3-3,
EN 55011 Class B, EN 55022 Class B, FCC Part 15 Class B
leakage current
0.3
RoHS compliant
yes
MTBF
MIL-HDBK-217F, GB, at 25°C, 115 Vac
200,000
mA
hrs
ENVIRONMENTAL
parameter
conditions/description
operating temperature
see derating curve
min
storage temperature
operating humidity
typ
max
units
-20
70
°C
-20
85
°C
93
%
max
units
non-condensing
MECHANICAL
parameter
conditions/description
min
dimensions
127.00 x 76.20 x 26.67 (5.00 x 3.00 x 1.05 inch)
weight
cooling method
typ
mm
270
free air convection (see derating curves below)
cui.com
g
For more information, please visit the product page.
CUI Inc │ SERIES: VMS-100 │ DESCRIPTION: AC-DC POWER SUPPLY
date 07/22/2013
page 3 of 4
DERATING CURVES
output power vs. ambient temperature
Load (%)
100
80
60
100 LFM
40
20 LFM (natural convection)
20
-20
-10
0
10
20
30
40
50
60
70
Ambient Temperature (°C)
MECHANICAL DRAWING
units: mm [inch]
tolerance: mm: ±0.5
inch: ±0.02
127.00 5.000
5.70 0.224
Molex 5273
connector
CN1
1
1
2
3
4
5 64.90 2.555
6
7
8
RSRS+
AC Line
2
No pin
3
AC Neutral
76.20 3.000
CN2
1
-Vo
2
-Vo
3
-Vo
4
-Vo
5
+Vo
6
+Vo
7
+Vo
8
+Vo
CN3
RS-
Remote Voltage
Sense -
RS+
Remote Voltage
Sense +
Note:
VR
Molex 5227
connector
115.48 4.546
26.67 1.050
max
1.60 0.063
3.00 0.118
max
1. All specifications measured at 25°C, 115/230Vac input voltage, and 75% load unless otherwise noted.
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: VMS-100 │ DESCRIPTION: AC-DC POWER SUPPLY
date 07/22/2013
page 4 of 4
REVISION HISTORY
rev.
description
date
1.0
initial release
11/03/2011
1.01
V-Infinity branding removed
08/22/2012
1.02
updated spec
07/22/2013
The revision history provided is for informational purposes only and is believed to be accurate.
Headquarters
20050 SW 112th Ave.
Tualatin, OR 97062
800.275.4899
Fax 503.612.2383
cui.com
[email protected]
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical
component is any component of a life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to
affect its safety or effectiveness.