INFINEON BIMM111

TECHNICAL DATA
BUS INTERFACE MODUL
BIM M111, BIM M115
d6
c6
b6
a6
Features
d1
c1
b1
a1
•EIB Bus Interface Module for piggyback-use
on PCBs
e2
e1
•MC68HC05B6 with mask programmed ROM,
contains the EIB System Software
•PEI *) and Port A, PLM A and PLM B for
applications available
•Smallest instabus EIB Bus Access Unit
Ordering Information
•Operating Temperature Range:
BIM M111: - 5 to + 45 °C
BIM M111
5WG1 111 8AA01
BIM M115
BIM M115: - 25 to + 70 °C
•EIBA certified part
*) = Peripheral External Interface
5WG1 115 8AA01
DESCRIPTION
The BIM M111 or the BIM M115 are members of Siemens instabus EIB BCU - family. They are
especially designed as small modules for piggyback use and can be fitted directly into PCBs. The
modules contain all functional parts of a EIB - BCU with the exception of shift register for the serial
synchronous interface. Additionally access to such microcontroller ports as Reset, PLMA, or Port A
is possible. These ports are directly accessible by the user. Additional pins for the connection of an
external programming button and a LED are available. For applications with the need of longer 'Bus
Buffer Time' the BIM allows to connect an additional capacitance at bus voltage level.
The reproduction, transmission or use of this document or it‘s contents is not permitted without express written approval. All rights,
including right created by patent grant or registration of a utility model or design, are reserved. Technical changes reserved.
25 15 14.41.03a
31.10.00
page 1
© Siemens AG 2000
BIM M111 / M115
Schematic Block Diagram
PEI
Port A
EIB
BIM M111,
BIM M115
PLMA
PLMB
Reset
Programming
LED
Button
Buffer Time
Absolute Maximum Electrical Ratings
Rating
Symbol
Bus Voltage
Microcontroller
Voltage
PEI,
Units
± 35
V
V...
GND - 0,5 to Vcc + 0,5
V
I
see Motorola Technical
V Bus
Input
Value
PLMA, PLMB, Reset, LED, Button
Microcontroller input or output current
per Pin
Data MC68HC05B6
Features of the Controller
•CPU
MC68HC05B6
•Operating Frequency
2,0 MHz (crystal frequency of 4,0 MHz)
•On-Chip RAM
176 Bytes ( 18 Bytes available for user )
•On-Chip EEPROM
256 Bytes (230 Bytes available for user)
•8-Bit A/D-converter (5 channels available for user)
•8-Bit pulse length modulator (PLM)
•Serial asynchronous communication interface
•Serial synchronous communication interface
•Watch dog
The reproduction, transmission or use of this document or it‘s contents is not permitted without express written approval. All rights,
including right created by patent grant or registration of a utility model or design, are reserved. Technical changes reserved.
25 15 14.41.03a
31.10.00
page 2
© Siemens AG 2000
BIM M111 / M115
HARDWARE BLOCK DIAGRAM
BIM M 111
BIM M 115
PA0
PA1
PA2
PA3
PA4
PA5
PA6
PA7
0
Port A
+
BUS
e2
-
7
Port B
a5
b3
a4
b2
a3
+5V
Programming
47k
2
BUTTON
c2
LED
7
PLMA
b1
PLMB
d6
TxD
d3
RxD
d4
CLK
c3
RTS
d5
CTS
c4
PC7
b6
PLMA
PLMB
PEISignalPins 1)
TYPE
Port D 4
+5V
c6
PEI
e1
MICROCONTROLLER
68HC05B6
TRANSFORMERMODULE
b5
a6
b4
c5
+5V
RType
47k5
3)
+5V
+20V
+5V
C35V
RESET
+5V
a2
2)
a1
VCC
VDD
d2
GND
c1
d1
Note: Use the C35V-pin only for extension of "Bus
Buffer Time". Do not draw current! Otherwise
the quality of bus transmission would be
affected.
1) For detailed description see "PEI" - table.
2) Additional capacitance (Vc=35V) for extended "Bus Buffer Time", e.g.100µF.
3) Additional capacitance (Vc=5V) for extended "Bus Buffer Time"., e.g. 470µF.
Memory Map
Address Range
Memory
Bytes
0000
001F
I/O, Register
32
0020
004F
ROM
48
0050
00BF
RAM
176
00C0
00FF
Stack
64
0100
0100
OPTR
1
0101
011F
EEPROM non protected
31
0120
01FF
EEPROM protected
224
0200
1FF1
ROM and unused areas
1FF2
1FFF
Special functions
The reproduction, transmission or use of this document or it‘s contents is not permitted without express written approval. All rights,
including right created by patent grant or registration of a utility model or design, are reserved. Technical changes reserved.
25 15 14.41.03a
31.10.00
page 3
© Siemens AG 2000
BIM M111 / M115
PEI (Physical External Interface)
PEI – Pin – Assignment
Pin
Power
Serial
I - Ports
Digital I /O
Mnemonics
Supply
Interface
or A / D –
- Ports
Async./sync.
Ports
_RESET
Remarks
a1
RESET
In-/Output
a2
C35V
a3
PA7
PA7
Digital Input / Output
a4
PA5
PA5
Digital Input / Output
a5
PA3
PA3
Digital Input / Output
a6
PA1
PA1
Digital Input / Output
b1
PLMA
PLMB
Pulse-Length-Mod.
b2
PA6
PA6
Digital Input / Output
b3
PA4
PA4
Digital Input / Output
b4
PA2
PA2
Digital Input / Output
b5
PA0
PA0
Digital Input / Output
b6
PC7
PC7
Digital Output (Input /
Buffer Capacitor
Output when PEI-Type17)
c1
GND
c2
BUTTON
c3
CLK
c4
Ground
PB2
Digital Input
PD6
PC4
Clock •
→
CTS
PD3
PC6
Clear to Send
c5
TYPE
PD4
c6
LED
d1
VDD
SCLK
•
←
PEI - Type
PB7
Vdd
Digital Output
2mA Current Limit.
(20V)
d2
VCC
Vcc (5V)
d3
TxD
TDO
PD5
PC3
Data •
→
d4
RxD
RDI
PD7
PC2
Data •
←
d5
RTS
PD2
PC5
Request to Send •
→
d6
PLMB
PLMB
Pulse-Length-Mod.
e1
+ Bus
Bus Line
e2
- Bus
Bus Line
The reproduction, transmission or use of this document or it‘s contents is not permitted without express written approval. All rights,
including right created by patent grant or registration of a utility model or design, are reserved. Technical changes reserved.
25 15 14.41.03a
31.10.00
page 4
© Siemens AG 2000
BIM M111 / M115
ELECTRICAL SPECIFICATION
See also EIBA Handbook for Development, Release 3.0
Bus Interface Characteristics:
Characteristics
Symbol
Operating Voltage
VBus
Current consumption
IBus
Reset conditions
Vcc
Min
21
Max
Typical
30
Unit
Remarks
V
4
< 4,6
mA
V
Reset generated by
transceiver
BCU-Buffer-Time
TBD
ms
Transmission Rate
9600
PEI-Load:50mW
bit/s
PEI DC-Characteristics:
Characteristics
Supply Output
Voltage +5V
Supply Output
Voltage +20V
Symbol
VCC
4.7
Max
5.3
VDD
18
20.5
V
Current Limitation
Data Output Voltage
Port A, Port B, Port C
Data Output Voltage
TDO, SCLK, PLMB
Data Output Voltage
Reset
Data Input Voltage
Port A, Port B, Port C
Reset, RDI
Analog Input Voltage
Range
I/O Ports Three-StateLeakage
Input Capacitance
IDD
VOL
VOH
VOL
VOH
VOL
2
5
0.4
mA
V
0.4
V
1,0
V
VIL
VIH
0
0.7 VCC
0.2 VCC
VCC
V
VAIL
VAIH
IOZ
0
CIN
Min
Typical
Unit
V
VCC-0,8
VCC-0,8
Remarks
Max. 10mA
load = 2mA
VBUS - VDD
> 1,5V
VBUS = 21V
... 30V
Iload=1,6mA
Iload=0,8mA
Iload=1,6mA
Iload=1,6mA
Iload=1,6mA
V
VCC
±10
µA
50
pF
The reproduction, transmission or use of this document or it‘s contents is not permitted without express written approval. All rights,
including right created by patent grant or registration of a utility model or design, are reserved. Technical changes reserved.
25 15 14.41.03a
31.10.00
page 5
© Siemens AG 2000
BIM M111 / M115
Timing
The timing of Save, Reset, VCC and VDD which are depending on VBUS are shown in the following
depiction:
+21V to 30V
min. 16V
max. 19.5V
0V
0.2V
VBUS
+5V
VCC min 4.6V
0V
+5V
SAVE 0V
+5V
RESET0V
VDD
+20V
resistive load
0V
+20V
capacitive load
VDD
0V
Environmental Conditions
Rating
Symbol
Value
Unit
Remarks
Operation Temperature Range BIM M111
TA
- 5 to + 45
°C
no condensation
Operation Temperature Range BIM M115
TA
- 25 to + 70
°C
no condensation
Storage Temperature Range BIM M111
TSTG
- 25 to + 55
°C
Storage Temperature Range BIM M115
TSTG
-25 to + 70
°C
5 to 93
%
Relative Humidity
no condensation
The reproduction, transmission or use of this document or it‘s contents is not permitted without express written approval. All rights,
including right created by patent grant or registration of a utility model or design, are reserved. Technical changes reserved.
25 15 14.41.03a
31.10.00
page 6
© Siemens AG 2000
BIM M111 / M115
SOFTWARE SPECIFICATION
See also EIBA Handbook for Development, Release 3.0
Application Hint
To avoid malfunctioning by EMI, it is recommended to shield the BIM. The connection for the
electric screen is shown in the figure below.
Soldering Side
BIM
Connection for electric screen (= Ground),
for information about the exact position see "Maßbild"
The data contained herein are subject to change without notice. Siemens does not warrant
for correctness or completeness of the documentation or that the products described are
qualified for certification.
The reproduction, transmission or use of this document or it‘s contents is not permitted without express written approval. All rights,
including right created by patent grant or registration of a utility model or design, are reserved. Technical changes reserved.
25 15 14.41.03a
31.10.00
page 7
© Siemens AG 2000
BIM M111 / M115
MECHANICAL SPECIFICATION (BIM M111)
The reproduction, transmission or use of this document or it‘s contents is not permitted without express written approval. All rights, including right created by patent grant or registration of a utility model or
design, are reserved. Technical changes reserved.
25 15 14.41.03a
31.10.00
page 8
© Siemens AG 2000
BIM M111 / M115
MECHANICAL SPECIFICATION (BIM M115)
The reproduction, transmission or use of this document or it‘s contents is not permitted without express written approval. All rights, including right created by patent grant or registration of a utility model or
design, are reserved. Technical changes reserved.
25 15 14.41.03a
31.10.00
page 9
© Siemens AG 2000