typ TA45-3RAU

TA45-3RAU
Thermal (T- and TA-Line)
www.schurter.com/PG17_18_19
Circuit Breaker for Equipment thermal, 3 pole, Rocker actuation, with auxiliary contact, with undervoltage
Description
-Thermal circuit breaker
-2 pole thermal overload protection
-Positively trip-free release
-High configurability
-Rocker non-illuminated or illuminated
-Snap-in version
-Quick connect terminal 6.3 x 0.8 mm or screw clamp terminal M3.5 x
6 mm (lineside P1, P2)
Approvals
Applications
-Power tools
-Industrial appliances
-Power supplies
Weblinks
pdf-datasheet, html-datasheet, General Product Information,
Approvals, CE declaration of conformity, RoHS, CHINA-RoHS, REACH,
SCHURTER-Stock-Check, Distributor-Stock-Check, Detailed request for
product, Product News
-Approval Reference Type: TA45
-IEC Standard: IEC 60934
-GB Standard: GB 17701
Technical Data
Rated Voltage AC
Rated current range AC
Degree of Protection
Dielectric Strength
Insulation resistance
Endurance typical
␣
400 V
0.05 - 12 A
from front side IP 40 acc. to IEC 60529
4 kVAC
500 VDC > 100 MΩ
mechanical: 50'000 switching cycles
AC: 1 x Ir:
50'000 switching cycles
Overload
Ambient temperature
Vibration Resistance
Shock Resistance
Possible Tripping Types
Actuation type
Weight
AC: min. 40 trips
@ 6 x Ir
-10 °C to 55 °C
± 0.75 mm @ 10 - 60 Hzacc. to IEC
60068-2-6, test Tc10 G @ 60 - 500
Hzacc. to IEC 60068-2-6, test Tc
30 G / 18 msacc. to IEC 60068-2-27,
test Ea
Thermal Undervoltage release Remote trip Mechanical lock-out latch
Rocker 55 - 60 g
Circuit Breakers
1
TA45-3RAU
Thermal (T- and TA-Line)
www.schurter.com/PG17_18_19
Dimension
Undervoltage release, remote trip release, auxiliary contact
36.5
16
23.7
9
43.6
11
10.8
12
11
1.5
9
10.6
10
69
7
34.7
34
3.5
12.5
48
15.5
6
A)
22
10.8
21.5
6.3
5.3 11.6 7.6 7.5 8.4
33
B)
A) Quick connect terminal, IEC 61210, A6.3-0.8 mm
B) Quick connect terminal, IEC 61210, A2.8-0.8 mm
Cut-out and pin-out
Cut-out snap-in type
a (1.0 – 5.0)
33.2 – 0.0
+0.2
Pin-out
b
a
b
1.0
1.5
2.0
2.5
3.0
4.0
5.0
44,5...45,0
44,5...45,0
44,7...45,2
44,7...45,2
44,8...45,3
44,9...45,4
45,0...45,5
P2
7
b
U-Relais
*)
a
10
11
c
4
1)
6
12
3
9
5
2)
1) Assemble
2) edge must be sharp
2
P1
*) Auxiliary contact / 3 pole
Circuit Breakers
TA45-3RAU
Thermal (T- and TA-Line)
www.schurter.com/PG17_18_19
Diagrams
Without thermal overload protection, 2pole thermal overload protection,
Auxiliary contact
Auxiliary contact
2pole thermal overload protection,
Auxiliary contact, Shunt terminal
Undervoltage release
P2
P2
P1
6
5
7 11 10
9
12
P2
P1
4
3
7 11 10
6
9 12
P2
P1
4
3
7 11 10
P1
7
5
9
U<
6
5 9 12
Undervoltage release with additional Undervoltage release with 2 additio- Remote trip release
contact
nal contacts
P1
P2 b
P2 b a P1
7
7
6
9
U<
U<
6
P2 c P1
7
5
6
9
5
5
9
Time-Current-Curves
[ min ] [ sec ]
10'000
[ min ] [ sec ]
10'000
60
30
20
10
Type
TA45
Type
Rated current
In <3 A
Rated current
60
3 pole switch
2 pole protected
2`000
Ambient temp.
1`000
30
20
+23ºC
10
500
5
Ambient temp.
1`000
+23ºC
500
200
100
Time in Seconds
Time in Seconds
3 A > In <12 A
3 pole switch
2 pole protected
2`000
5
200
1
TA45
50
20
10
100
1
50
20
10
5
5
2
2
1
1
0,5
0,5
0,3
0,3
0,2
0,2
0,1
0,1
1,05 1,32
2
3
4
5
8
10
1,05 1,32
Multiple of Rated Current In
Multiple of Rated Current In
Reference Temperature +23°
Reference Temperature +23°
2
3
Circuit Breakers
4
5
8
10
3
TA45-3RAU
Thermal (T- and TA-Line)
www.schurter.com/PG17_18_19
Effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C. To determine the rated current for a lower or higher ambient temperature, use a correction factor (typical value) from
the table below:
Ambient temperature [°C]
Correction factor
-10
0.89
-5
0.91
0
0.92
+23
1.00
+30
1.03
+40
1.08
+55
1.16
Example: Rated current = 5 A; Environmental temperature = 40 °C; --> Correction factor =
1.08; Resulting current = 5.5 A --> Fount to next higher rated current: 6 A
Auxiliary contact (changeover)
Rated Voltage
28 VDC
60 VDC
240 VAC
Rated current
max. 10 A resistive load
max. 2 A resistive load
max. 2 A cos φ 0.7
Undervoltage release
Max. operating voltage
1.1 Ue
Rated operating voltage Ue
Current consumption (± 10%)
1)
5V
12 V
24 V
48 V
120 V
240 V
400 V
10.5 mA
16.5 mA
17.0 mA
3.2 mA
3.7 mA
3.1 mA
2.65 mA
Highest reset level
0.85 Ue
Lowest trip level
0.20 Ue
Trip delay
20 ms - 50 ms
≥4 kV
Impulse withstand voltage (1.2 / 50 µs)
1) only for 3pole
Remote trip
Permissible impuls duration of the make contact (no)
Between terminal C and P1
Electrical load of the make contact (no)
Current max. 12 mA / power max. 1.1 W
unlimited
Config. Code
TA45|-|AK2|W|F|120|A2|-|AZM11|
The characters are placeholders for the correspondingly keys of selections from the key tables.
TA45|-| AK2 |W|F|120|A2|-|AZM11| = Basic function
Basic function
Basic function
Configuration
key
Configuration
key
3-pole, rocker, 2p overload protection, auxiliary contact and shunt terminal,
flat connection, momentary switch, without illumination
AWG
3-pole, rocker, auxiliary contact, screw connection, illuminated 380 V...400
V
A1S
3-pole, rocker, 2pole overload protection, auxiliary contact and shunt terminal, flat connection, illuminated 380 V...400 V
AX1
3-pole, rocker, 2pole overload protection, auxiliary contact, screw connection, illuminated 380 V...400 V
A1W
3-pole, rocker, auxiliary contact, screw connection, without illumination
AXC
AXD
3-pole, rocker, 2pole overload protection, auxiliary contact and shunt terminal, screw connection, illuminated 380 V...400 V
A1X
3-pole, rocker, 2pole overload protection, auxiliary contact, screw connection, without illumination
AS1
2-pole, rocker, 1pole overload protection, auxiliary contact and shunt terminal, screw connection, without illumination
AXG
3-pole, rocker, auxiliary contact, flat connection, illuminated 380 V...400 V
3-pole, rocker, auxiliary contact, flat connection, without illumination
AVC
AYC
3-pole, rocker, 2pole overload protection, auxiliary contact, flat connection,
without illumination
AVD
3-pole, rocker, auxiliary contact, screw connection, momentary switch,
without illumination
AVG
3-pole, rocker, 2pole overload protection, auxiliary contact, screw connection, momentary switch, without illumination
AYD
3-pole, rocker, 2pole overload protection, auxiliary contact and shunt terminal, flat connection, without illumination
AW1
3-pole, rocker, 2p overload protection, auxiliary contact and shunt terminal,
screw connection, momentary switch, without illumination
AYG
3-pole, rocker, 2pole overload protection, auxiliary contact, flat connection,
illuminated 380 V...400 V
3-pole, rocker, auxiliary contact, flat connection, momentary switch, without illumination
AWC
3-pole, rocker, 2pole overload protection, auxiliary contact, flat connection,
momentary switch, without illumination
AWD
4
Circuit Breakers
TA45|-|AK2| W |F|120|A2|-|AZM11| = Actuator colour
TA45-3RAU
Thermal (T- and TA-Line)
www.schurter.com/PG17_18_19
Actuator colour
Configuration
key
Rated current
Configuration
key
Clear transparent
1
1.0 A
J10
Red transparent
3
1.1 A
J11
Green transparent
4
1.2 A
J12
Orange transparent
6
1.3 A
J13
Black
B
1.4 A
J14
Green
G
1.5 A
J15
Red
R
1.6 A
J16
White
W
1.7 A
J17
Orange
X
1.8 A
J18
Yellow
Y
1.9 A
J19
2.0 A
J20
2.1 A
J21
2.2 A
J22
2.3 A
J23
2.5 A
J25
TA45|-|AK2|W| F |120|A2|-|AZM11| = Legend
F
0
embossed
Configuration
key
I
Legend
white printed
OFF
ON
ON
I
black printed
H
K
L
0
white printed
OFF
M
0
black printed
I
white printed
I
P
0
black printed
I
R
0
ON
I
0
OFF
white printed
S
ON
I
0
OFF
T
black printed
TA45|-|AK2|W|F| 120 |A2|-|AZM11| = Rated current
Rated current
2.8 A
J28
3.0 A
030
3.5 A
035
4.0 A
040
4.5 A
045
5.0 A
050
6.0 A
060
6.5 A
065
7.0 A
070
7.5 A
075
8.0 A
080
9.0 A*
090
10.0 A*
100
11.0 A*
110
12.0 A*
120
Other rated currents on request
* The approved current range is 0.05 to 12 A. We recommend to limit the range to
max. 8 A at AC 400 V.
For the current range 9 to 12 A the voltage should be limited to AC 240 V.
TA45|-|AK2|W|F|120| A2 |-|AZM11| = Release / lock-out latch
Release / lock-out latch
Configuration
key
Configuration
key
Remote trip release, rated voltage 400 V AC
A1
whithout release / lock-out latch
C0
without thermal overload protection / temporarily without VDE approval
C00
Undervoltage release with additional contact, rated voltage 400 V AC
E1
0.05 A
Z05
Undervoltage release with additional contact, rated voltage 240 V AC
E2
0.1 A
J01
Undervoltage release with additional contact, rated voltage 230 V AC
E3
0.2 A
J02
Undervoltage release, rated voltage 400 V AC
U1
0.3 A
J03
Undervoltage release with 2 additional contacts, rated voltage 400 V AC
Z1
0.4 A
J04
Undervoltage release with 2 additional contacts, rated voltage 240 V AC
Z2
0.5 A
J05
Undervoltage release with 2 additional contacts, rated voltage 230 V AC
Z3
0.6 A
J06
Undervoltage release with 2 additional contacts, rated voltage 120 V AC
Z4
0.7 A
J07
Undervoltage release with 2 additional contacts, rated voltage 48 V AC / DC
Z6
0.8 A
J08
Undervoltage release with 2 additional contacts, rated voltage 24 V AC / DC
Z7
0.9 A
J09
Undervoltage release with 2 additional contacts, rated voltage 12 V AC / DC
Z8
Undervoltage release with 2 additional contacts, rated voltage 5 V AC / DC
Z9
Other rated currents on request
* The approved current range is 0.05 to 12 A. We recommend to limit the range to
max. 8 A at AC 400 V.
For the current range 9 to 12 A the voltage should be limited to AC 240 V.
TA45|-|AK2|W|F|120|A2|-| AZM11 | = Accessories
Circuit Breakers
5
TA45-3RAU
Thermal (T- and TA-Line)
www.schurter.com/PG17_18_19
Factory mounted accessories
Configuration
key
Without cover
For subsequent fitting accessories see:
http://www.schurter.ch/pdf/english/typ_TA45-ACC.pdf
Packaging Unit 1 Pcs Accessories
Description
TA45-ACC
Accessories to TA45
06.06.2016
6
Circuit Breakers
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.