TRACOPOWER TIS150-148

Industrial Power Supplies
TIS Series
75 - 600 Watt
Features
Switch mode power supplies for
DIN-rail mounting
4 power ranges with 3, 6, 12 and 24 A
output current (24 VDC models)
Selectable 115/ 230 VAC input
Very low ripple and noise
EMI complies with EN50081-2 and
EN50082-2
Conducted EMI to EN55011 class B
For system operation available with
built-in functions:
RED: Redundancy module for N+1
systems with true current sharing.
SIG: Signal module with AC-Powerfail, DC- OK Signal and
The switching power supplies of the TIS series have been particulary deexternal ON/OFF control
signed for applications in industrial process control systems and machine
tools. Excellent specifications and high immunity against electrical disturUDS: DC-UPS module for uninterbances guarantee reliable power for sensitive loads in rugged industrial
ruptable battery backed-up
environments. With help of optional function modules specific requirements
power systems.
for system applications can be met by a standard product. With the UDS
Worldwide Safety Approvals
module the power supplies can be extended to a perfect DC-UPS with autoEasy snap-on mounting on DIN-rails matic battery- backup. This function is very often required in applications
or chassis mounting
where a time delayed shutdown of a system is necessary. To monitor and
2 Year Product Warranty
control the power supply a signal module can be installed. For parallel
operation with active power sharing a redundancy option is available. This
flexibility makes the TIS series power supplies a cost effective solution for
many industrial applications.
Models
Ordercode
(includes terminal plugs)
Input Voltage
Output Power
max.
Output Voltage
nom.
Output Current
max.
6.0 A
3.0 A
1.5 A
TIS 75-112
TIS 75-124
TIS 75-148
115 / 230 VAC
selectable
75 W
12 VDC
24 VDC
48 VDC
TIS 150-124
TIS 150-148
115 / 230 VAC
selectable
150 W
24 VDC
48 VDC
6.0 A
3.0 A
TIS 300-124
TIS 300-148
TIS 300-172
115 / 230 VAC
selectable
300 W
24 VDC
48 VDC
72 VDC
12 A
6.0 A
4.2 A
TIS 500-124
230 VAC
500 W
24 VDC
20 A
TIS 600-124
TIS 600-128
TIS 600-148
TIS 600-172
115 / 230 VAC
selectable
600 W
24
28
48
72
VDC
VDC
VDC
VDC
24 A
22 A
12 A
8.5 A
TIS 300-124 DCI
300 - 800 VDC
300 W
24 VDC
12 A
http://www.tracopower.com
Page 1
Industrial Power Supplies
TIS Series
75-600 Watt
Input Specifications
Input voltage range – TIS 75, TIS 150, TIS 300, TIS 600
– TIS 500
– TIS 300 DCI
93 – 132 VAC / 187 – 264 VAC
187 – 264 VAC
300 – 800 VDC
Input frequency
47 – 63 Hz
Input current at full load (typ.)
– TIS 75
– TIS 150
– TIS 300
– TIS 500
– TIS 600
115 VAC
1.7 A
3.0 A
5.4 A
230 VAC
0.9 A
1.7 A
3.3 A
5.5 A
6.4 A
10.5 A
Inrush current (< 2 ms)
– TIS 75
– TIS 150
– TIS 300
– TIS 500
– TIS 600
115 VAC
< 16.5 A
< 35 A
< 35 A
< 70
A
230 VAC
< 33 A
< 70 A
< 70 A
< 70 A
< 80 A
Output Specifications
Output voltage adj. range
–
–
–
–
–
12
24
28
48
72
VDC
VDC
VDC
VDC
VDC
models
models
models
models
models
Regulation – Input variation
– Load variation (10 – 90 %)
12
24
28
48
60
–
–
–
–
–
14
28
32
52
76
VDC
VDC
VDC
VDC (48 – 55 VDC on request))
VDC
± 0.2 % max.
– TIS 75, TIS 150
– TIS 300, TIS 500, TIS 600
± 1.0 % max.
± 0.3 % max.
(± 1.5 % in parallel operation)
Ripple and Noise (20MHz Bandwidth)
< 50 mV pk-pk
Electronic short circuit protection
current limitation at 110 % typ.
(constant current, automatic restart)
Overvoltage protection, triggerpoint at
140 % typ. Vout nom.
Hold-up time
– TIS 75 ... TIS 300
– TIS 500
– TIS 600
115 VAC
min. 25 ms
min. 15 ms
230 VAC
min. 30 ms
min. 40 ms
min. 25 ms
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com
Page 2
Industrial Power Supplies
TIS Series
75-600 Watt
General Specifications
Temperature ranges – Operating (ambient temp.)
– Derating above 50 °C
– Storage (non operating)
– 25 °C…+70 °C max.
2% /°C
– 25 °C…+ 85 °C
Humidity (non condensing)
95 % rel H max.
Temperature coefficient
0.02 % / °C
Switching frequency
80 kHz typ. (Pulswidth modulation)
Efficiency
– TIS 75 ... TIS 300
– TIS 500
85 % typ.
90 % typ.
– TIS 600
88 % typ.
Isolation
according to EN 60950, UL 1950, UL 508C
Reliability, calculated MTBF (MIL-HDBK-217 E) – TIS 75 /150
– TIS 300 /500
– TIS 600
450000 h @ +25°C/ 420000 h @ +25°C
360000 h @ +25°C/ 340000 h @ +25°C
300000 h @ +25°C
Safety standards
IEC 60950, EN 60950 (SELV),
UL/cUL 1950, UL 508C
Safety approvals
UL/cUL 1950 recognized, File E18138
UL/cUL 508C listed, File E210002
UL/cuL 1604 listed, File E213613 (Class I,Division
2, Groups A, B, C and D hazardous locations)
CB-Scheme
Electromagnetic compatibility (EMC), Emissions
– Conducted RI suppression on input
EN 50081-1 / EN 50081-2
EN 55011 class B, EN 55022 class B,
FCC part 15, level B
EN 55011 class A, EN 55022 class A,
FCC part 15, level A
– Radiated RI suppression
Electromagnetic compatibility (EMC), Immunity
– Electrostatic discharge (ESD)
– Radiated RF field immunity
– Electrical fast transient / burst immunity
– Surge immunity
– Immunity to conducted RF disturbances
– Power frequency field immunity
EN 50082-2
IEC / EN 61000-4-2
IEC / EN 61000-4-3
IEC / EN 61000-4-4
IEC / EN 61000-4-5
IEC / EN 61000-4-6
IEC / EN 61000-4-8
Safety class
Degree of Protection 1 (IEC 536)
Case protection
IP 20 (IEC 529)
Environment
– Vibration
– Shock
4 kV / 8 kV
10 V / m
2 kV
2 kV / 4 kV
10 V
30 A / m
IEC 60068-2-6,1 gn, 200 sweeps, each axis
IEC 60068-2-27, 15 gn, 11 ms, each axis
Enclosure material
Aluminium (chassis) / stainless steel (cover)
Mounting (snap-on with selflocking spring)
for 35 mm DIN-rails as per EN 50022
Connection
Plugable screw terminals (plugs included)
(TIS 600: screw terminal blocks)
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com
Page 3
Industrial Power Supplies
TIS Series
75-600 Watt
Optional
Power
Supplies
Mounting
withSystems
Redundancy
Dimensions
Function
mm (inches)
With this option a parallel operation of up to 5 units is possible. Decoupling diodes and current share lines allow to build
true N +1 redundant systems with active current sharing for all units. This function also includes an alarm relay to signal
a single unit failure.
This option is available for TIS 150 W, TIS 300 W and TIS 600 W models. Please note: A combination with other
options is not possible.
Models
Output Power
max.
Output Voltage
nom.
Output Current
max.
TIS 150-124 RED
TIS 150-148 RED
115 / 230 VAC
selectable
150 W
24 VDC
18 VDC
6.0 A
12 A
TIS 300-124 RED
TIS 300-148 RED
115 / 230 VAC
selectable
300 W
24 VDC
48 VDC
12 A
6.0 A
TIS 600-124 RED
TIS 600-148 RED
115 / 230 VAC
selectable
600 W
24 VDC
48 VDC
24 A
12 A
L
N
Con1
Pin3
Con1
Pin2
Con2 - Pin3/4
AC
Bus
Indicator
DC
Con2 - Pin1/2
+Vout
24/48VDC
Input Voltage
115/230VAC
Ordercode
(includes terminal plugs)
-Vout
Con1
Pin1
I-Sense
V-Sense
Con3 - Pin4
Con3 - Pin3
Con3 - Pin2
Con3 - Pin1
Regulator
Current
Shareline
Unit OK
Common
Unit OK
Unit
OK
Specifications
Raiting per relay contact
60 VDC /0.36 A max.
Specifications can be changed without notice
http://www.tracopower.com
Page 4
Industrial Power Supplies
TIS Series
75-600 Watt
Power Supplies with Powerfail Functions
These models provide 3 functions required in many process control system applications:
• AC-Powerfail signal (relay contact)
• DC-OK signal (relay contact)
• Remote ON/OFF
Models
Output Power
max.
Output Voltage
nom.
Output Current
max.
115 / 230 VAC
selectable
150 W
24 VDC
48 VDC
6.0 A
3.0 A
TIS 300-124 SIG
TIS 300-148 SIG
115 / 230 VAC
selectable
300 W
24 VDC
48 VDC
12 A
6.0 A
TIS 600-124 SIG
TIS 600-148 SIG
115 / 230 VAC
selectable
600 W
24 VDC
48 VDC
24 A
12 A
L
N
Con1
Pin3
Con2 - Pin3/4
AC
Con1
Pin2
+Vout
24/48VDC
TIS 150-124 SIG
TIS 150-148 SIG
Output
OK
DC
Con2 - Pin1/2
Con1
Pin1
Con3 - Pin2
+
Con3 - Pin1
Remote
ON/OFF
-
Con3 - Pin7
Con3 - Pin6
Mains
Fail
Detection
-Vout
Remote
ON/OFF
Input Voltage
115/230VAC
Ordercode
(includes terminal plugs)
Common
AC-Powerfail
Mains OK
(Relay A)
Con3 - Pin5
Con3 - Pin4
Con3 - Pin3
DC-OK
Detection
(Relay B)
DC-OK
Common
DC-OK
DC-OK
Specifications
DC-OK signal trigger point – Models with 24 Vout
– Models with 48 Vout
> 22.8 VDC ± 0.5 V
> 45.6 VDC ± 1.0 V
relay B closed (pin 4 – pin 3)
relay B closed (pin 4 – pin 3)
AC-Powerfail signal
Vin < 93 resp. < 187 VAC relay A closed (pin 7 – pin 6)
Raiting per relay contact
60 VDC /0.36 A max.
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com
Page 5
Industrial Power Supplies
TIS Series
75-600 Watt
DC-UPS-System
In addition to the standard power supply function, these
models include a professional battery management system
to charge and monitor an external battery. In case of a
power failure the battery is switched automatically and
without any interruption to the DC-output. If mains power
is available again, the battery is switched off. The hold-up
time is limited only by battery capacity and load. Charge
current and voltage can be adjusted to values as required
by battery type. Power fail and low battery alarm signals
are available via two independent relay contacts. During
normal operation the battery status is monitored by
periodically loading the battery for short time. If a cell
resistance is high, there is a relay alarm available. The
battery is fully protected under any operational conditions.
The power supply is short circuit protected even in batterybackup operation, however for safety reason the battery
should be fused with a fast blow fuse. Battery mode can
be activated by connection of Pin 7 and 8.
Complete external battery modules (3.2 Ah or 7 Ah standard) with lead batteries are available on request.
Models
Ordercode
(includes terminal plugs)
Input Voltage
Output Power
max.
Output Voltage
nom.
Output Current
max.
TIS 300-124 UDS
115 / 230 VAC
selectable
300 W
24 VDC
12 A
TIS 600-124 UDS
115 / 230 VAC
selectable
600 W
24 VDC
24 A
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com
Page 6
Industrial Power Supplies
TIS Series
75-600 Watt
DC-UPS-System
Battery +
Con3 - Pin2
V Battery Charger
L
N
I
Con1
Pin3
AC
Con1
Pin2
Con2 - Pin3/4
Output
OK
DC
Con2 - Pin1/2
Con1
Pin1
+Vout
24VDC
115/230VAC
Battery -
Con3 - Pin1
-Vout
VBat>18V
Bat ON/OFF
Mains Fail
Battery Switch
Logic
Con4
Pin8
Battery
ON/OFF
Con4 - Pin3
Con4 - Pin2
Con4 - Pin1
Mains
Fail
Detection
Con4
Pin7
AC-Powerfail
Common
AC-Power OK
AC-Powerfail
(Relay A)
Con4 - Pin6
Con4 - Pin5
Con4 - Pin4
Battery
Test
Battery Low / failure
Common
Battery OK
Low Battery
(Relay B)
Specifications
Charging current (factory set)
– TIS 300-124 UDS
– TIS 600-124 UDS
1.2 A
2.4 A
Adjustment range of charging current – TIS 300-124 UDS
– TIS 600-124 UDS
0.15...1.5 A
0.25...2.5 A
Holding current for charging battery atvoltage 27.3 VDC
< 50 mA
Overload at short circuit during battery operation
system switches off
AC-Powerfail signal
Vin < 93 resp. < 187 VAC
relay A closed (pin 2 – pin 3)
Low battery signal
Battery voltage below 22 V
relay B closed (pin 5 – pin 6)
Raiting per relay contact
During battery charge operation
60 VDC /0.36 A max.
output current reduction by 1.4 x battery charge current
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com
Page 7
Industrial Power Supplies
TIS Series
75-600 Watt
Battery-Pack for DC-UPS Systems
The Battery Pack contains high quality, maintenance free lead-acid batteries with 3.2 Ah resp. 7.0 Ah capacity. The
batteries are fixed together with a re-settable electronic fuse on a solid mounting frame. Together with power supply
models TIS 300-124 UDS or TIS 600-124 UDS the battery pack provides a complete and reliable DC-UPS system.
Backup time is depending on load current and battery capacity.
Models
Ordercode
Battery Voltage
Battery Capacity
(25°C, 20h-rate)
Permissable Charge
Current max.
TIS 24-32 AP
TIS 24-70 AP
24 VDC
24 VDC
3.2 Ah
7.0 Ah
1.2 A
2.4 A
Specifications
Max. charge voltage
27...27.6 VDC
Temperature coefficient
– 36mV /°C
Temperature range
– at charge operation
– at load operation
– Storage
– 15 °C...+50 °C
– 20 °C...+60 °C
– 20 °C...+60 °C
Average lifetime on standby operation at tA =20 °C
4...5 years
Cable length
1.0 m
Cable diameter
– TIS 24-32 AP
– TIS 24-70 AP
2.5 mm2 (AWG 12)
4.0 mm2 (AWG 11)
Weight
– TIS 24-32 AP
– TIS 24-70 AP
4.6 kg (10.1 lb)
5.9 kg (13.0 lb)
Recommended combinations – TIS 24-32 AP
(power supplies)
– TIS 24-70 AP
TIS 300-124 UDS
TIS 600-124 UDS
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com
Page 8
Industrial Power Supplies
TIS Series
75-600 Watt
Optional Mounting Systems Dimensions mm (inches)
TIS 150
TIS-75-124
24VDC / 3 A
OUTPUT
Output
Nom. Voltage: 24 VDC
Nom. Current: 3 A
Output
O
K
CAUTION
53.7
Do not open.
Risk of high voltage.
Read instruction manual.
Check line selection switch
before connection.
+–
Industrial Switching
Power Supply
TIS150-124
24VDC / 6 A
Output
Input
Nom. Freq.: 50/60 Hz
Nom. Voltage: 115/230 VAC
Nom. Current: 3,7/1,7 A
NL
56.7 (2.23)
90 (3.54)
Nom. Voltage: 24 VDC
Nom. Current: 6 A
Output O
K
CAUTION
Do not open. Risk of high voltage.
Read instruction manual.
Check line selection switch before connection.
53.7
Industrial Switching
Power Supply
+–
114.6 (4.51)
adj
Nom. Freq.: 50/60 Hz
Nom. Voltage: 115/230 VAC
Nom. Current: 1,7/0,9 A
(2.11)
114.6 (4.51)
L N
INPUT
(2.11)
TIS 75
56.7 (2.23)
157 (6.18)
45 (1.77)
38.5
80 (3.15)
(0.27)
6.8
56.7 (2.23)
(0.27)
6.8
56.7 (2.23)
(1.52)
Weight:
TIS 75
0.48 kg (1.06 lb)
TIS 150 0.80 kg (1.76 lb)
TIS 300
TIS 300-124
24VDC / 12A
Output
Input
Nom. Freq.: 50/60 Hz
Nom. Voltage: 115/230 VAC
Nom. Current: 5,4/3,3 A
NL
Output O
K
CAUTION
Do not open. Risk of high voltage.
Read instruction manual.
Check line selection switch before connection.
53.7
Industrial Switching
Power Supply
(2.11)
114.6 (4.51)
++ – –
Nom. Voltage: 24 VDC
Nom. Current: 12 A
207 (8.15)
38.5
83 (3.27)
130 (5.12)
(0.27)
6.8
83 (3.27)
(1.52)
Weight:
TIS 300
Specifications can be changed without notice
http://www.tracopower.com
1.4 kg (3.09 lb)
Tolerances: ± 0.5 mm (±0.02)
Page 9
Industrial Power Supplies
TIS Series
75-600 Watt
Optional Mounting Systems Dimensions mm (inches)
TIS 500
TIS 500-124
24VDC / 20A
++ – –
NL
Nom. Freq.: 50/60 Hz
Nom. Voltage: 230 VAC
Nom. Current: 5,3 A
Input
75 (2.95)
130 (5.12)
CAUTION
Do not open. Risk of high voltage.
Read instruction manual.
Industrial Switching
Power Supply
Nom. Voltage: 24VDC
Nom. Current: 20 A
Output
83 (3.27)
220 (8.66)
46 (1.81)
130 (5.12)
(0.27)
83 (3.27)
6.8
Weight:
TIS 500
1.9 kg (4.19 lb)
TIS 600
177.2 (6.98)
Industrial Switching
Power Supply
Input
TIS 600-124
24VDC / 24A
– – ++
Nom. Voltage: 72 VDC
Nom. Current: 8 A
Output
CAUTION
Do not open. Risk of high voltage.
Read instruction manual.
Check line selection switch before connection.
120.2 (4.73)
NL
Nom. Freq.: 50/60 Hz
Nom. Voltage: 115/230 VAC
Nom. Current: 10,5/6,4 A
243 (9.57)
32
82.6 (3.25)
179 (7.05)
(1.26)
Specifications can be changed without notice
http://www.tracopower.com
(0.27)
6.8
82.8 (3.26)
Weight:
TIS 600
2.0 kg (4.41 lb)
Tolerances: ± 0.5 mm (±0.02)
Page 10
Industrial Power Supplies
TIS Series
75-600 Watt
Optional Mounting Systems Dimensions mm (inches)
Wall mounting
A
B
7.5
4.6
Models
Order code
(0.30)
E
D
C
(0.18)
A
B
C
D
E
TIS 75W
MK-75
37 (1.46)
14.5 (0.57)
–
134.5 (5.30)
150.5 (5.93)
TIS 150W
MK-150
132 (5.20)
13.5 (0.53)
105 (4.13)
134.5 (5.30)
150.5 (5.93)
TIS 300W
MK-300
132 (5.20)
13.5 (0.53)
105 (4.13)
134.5 (5.30)
150.5 (5.93)
TIS 500W
MK-500
132 (5.20)
13.5 (0.53)
105 (4.13)
134.5 (5.30)
150.5 (5.93)
TIS 600W
MK-600
190 (7.48)
37.5 (1.48)
115 (4.53)
197.0 (7.76)
207.0 (8.15)
Rugged DIN-Rail mounting
A
B
Models
countersink M4
25 (0.98)
50.1 (1.97)
4.2 (0.17)
C
Order code
A
B
C
TIS 150W
RMK-150
t.b.a.
t.b.a.
t.b.a.
TIS 300W
RMK-300
t.b.a.
t.b.a.
t.b.a.
TIS 500W
RMK-500
t.b.a.
t.b.a.
t.b.a.
TIS 600W
standard
180 (7.09)
165 (6.50)
15.0 (0.59)
Specifications can be changed without notice
http://www.tracopower.com
Tolerances: ± 0.5 mm (±0.02)
Page 11
Industrial Power Supplies
TIS Series
75-600 Watt
Outline Dimensions mm (inches)
204 (8.03)
TIS-24-32 AP
14
184 (7.24)
(0.55)
Detail A
7
7
12
Detail B
9
(0.28)
69 (2.72)
(0.47)
5.8
B
(0.35)
B
135 (5.14)
A
100 (3.94)
A
(0.23)
(0.28)
Weight (incl. batteries):
TIS-24-32 AP
4.6 kg (10.1 lb)
TIS-24-70 AP
5.9 kg (13.0 lb)
272 (10.71)
TIS-24-70 AP
A
B
B
69 (2.72)
100 (3.94)
A
152 (5.98)
252 (9.92)
Specifications can be changed without notice
Tolerances: ± 0.5 mm (±0.02)
Rev. 05/01
Jenatschstrasse 1 • CH-8002 Zurich • Switzerland
Tel. +41-1284 2911 • Fax +41-1201 1168 • e-mail: [email protected] • internet: http://www.tracopower.com
Page 12