OMRON MGCOV

Heavy Duty Power Relay
MGN
30 Amp Heavy Duty Relay
• Class F coil insulation system for 155°C (311°F)
®
• Coil molded in DuPont Rynite for environmental
protection
• Rugged construction rivets terminals to base
• CULUS Listed
• Short Circuit Current Rating (SCCR) of 5kA, 600VAC
u u
c
Ordering Information
To Order: Select part number and add the desired coil voltage rating (e.g. MGN1C-AC24)
Base size
Contact Form
Model
Short
SPDT
MGN1C
SPST-NO
MGN1A
SPST-NO-DM
MGN1X
SPST-NO
MGN1AM (see note)
SPST-NC
MGN1B
DPST-NO
MGN2A
DPDT
MGN2C
DPDT
MGN2CM (see note)
Long
MG series dust cover
MGCOV
Note: Magnetic blow-out version
Specifications
■ Contact Data
Materials
All versions 5/16” diameter Ag-Alloy
Contact UL ratings
30 amp or 1-1/2 hp @ 120 or 240 VAC, 2 hp @ 240 VAC, 3,600w @ 120 or 240 VAC (ballast),
30 amp @ 240 VAC, 100,000 cycle (resistive), 20 amp @ 600 VAC, 30 amp @ 28 VDC
UL file number
E41643
Note: Magnetic Blow-out versions also have a 20 amp @ 125 VDC (resistive) load rating.
Heavy Duty Power Relay
MGN
349
■ Coil Data
AC
Nominal
voltage
Resistance in
Ohms ± 10%
Nominal coil
power
Coil
voltages
Coil treatment Insulation
resistance
Pick up voltage
at 25°C (77°F)
9.5 VA
Up to 600
volts/60 Hz
Molded Rynite® 100 megohms
min.
Std. Class F
85% or less
of nominal
Resistance in
Ohms ± 10%
Nominal coil
power
Coil
voltages
Coil treatment Insulation
resistance
Pick up voltage
at 25°C (77°F)
6 VDC
18
2W
12 VDC
72
Up to 125 volts Molded Rynite® 100 megohms
min.
Std. Class F
6 VAC
0.85
12 VAC
2.85
24 VAC
11.5
120 VAC
295
240 VAC
1,170
480 VAC
4,860
DC
Nominal
voltage
24 VDC
290
48 VDC
1,150
110 VDC
6,050
75% or less
of nominal
■ Characteristics
Operate time
Approximately 30 ms
Release time
Approximately 30 ms
Operating ambient temperature
AC:
-45° to 80°C (-49° to 176°F) @ 30 amps
DC:
-45° to 115°C (-49° to 239°F) @ 30 amps
Coil temperature rise
Life
expectancy
25°C ambient-continuous duty
AC:
70°C (158°F) approx. @ 60 Hz (use at 50 Hz will cause slight increase in coil rise)
DC:
35°C (95°F) approx.
Electrical at
rated load
100,000 operations (minimum)
Mechanical
1,000,000 operations
Dielectric strength
2,200 VRMS, 60 Hz between contacts
2,200 VRMS, 60 Hz between other elements
Terminals
Screw type
Weight
Short base version: approx 227 g (8 oz)
Long base version: approx 283 g (10 oz)
350
Heavy Duty Power Relay
MGN
Dimensions
Unit: mm (inch)
7.93 (0.312) recess
(See note)
■ MGN (Long Base)
7.93 (0.312) recess
(See note)
4.78 (0.188) dia., 2 holes
7
5
3
5
4.78 (0.188) dia., 2 holes
3
■ MGN (Short Base)
47.63
(1.875)
47.63
(1.875)
63.50
(2.50)
20.03
(0.789)
42.04
(1.655)
63.50
(2.50)
55.88
(2.20)
3.18 (0.125)
(See note)
Note: Recess for screw mounting on units with 300--600 VAC coils
4
6
4
6
8
63.50
(2.50)
84.33
(3.32)
60.45
(2.38)
Blow-Out
Magnet
3.18 (0.125)
(See note)
Note: Recess for screw mounting on units with 300--600 VAC coils
■ MG Series Dust Cover (Optional)
Sealed knock-out holes for standard conduit fittings.
Relay mounts on pre-drilled base. Constructed of
Aluminum. Snap-action cover release.
127W x 76.2H x 101.6D mm (5W x 3H x 4D in)
Heavy Duty Power Relay
MGN
351
All sales are subject to Omron Electronic Components LLC standard terms and conditions of sale, which
can be found at http://www.components.omron.com/components/web/webfiles.nsf/sales_terms.html
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
OMRON ON-LINE
OMRON ELECTRONIC
COMPONENTS LLC
Global - http://www.omron.com
USA - http://www.components.omron.com
55 E. Commerce Drive, Suite B
Schaumburg, IL 60173
847-882-2288
Cat. No. X301-E-1b
09/11
Heavy Duty Power Relay
Specifications subject to change without notice
MGN