FUJI EDS11-160C

PX series
digital temperature
controller
MICRO-CONTROLLER X (96 × 96 mm)
DATA SHEET
PXG9
PXG9 is a compact size temperature controller of front panel
size 96 × 96 mm. To cope with any of versatile uses as a
temperature controller, it has many input/output points and
sophisticated control functions.
FEATURES
1. Wide variety and number of input / output
1. Digital input: Up to 5 points
2. Digital output: Up to 5 points
3. Control output: 4 types
Relay contact, SSR drive, voltage linear, current linear
4. Universal inputs: Thermocouple, resistance bulb, current, voltage, mV linear
5. Remote SV input function
6. Analog re-transmission output function (for current or
voltage)
7. Motorized valve control output
2. User interface of easy-to-see indication and easy-to-use
operation method
1. Easy-to-see, large display section
2. Parameters grouped by functions
3. User key to which you can assign a function
4. Password function provided for avoiding wrong operation and protecting settings
5. Front water-proof structure (IP66 in corformity)
3. Advanced control functions to meet various applications
1. Sampling cycle 200 ms (300 ms at position feedback
cotrol)
2. Input indication accuracy ± 0.3%FS
3. Manual control function
4. Control method selectable out of 8 different types:
ON/OFF control, PID control, fuzzy PID control, selftuning control, PID2 control, motorized valve control
(with/without position feedback)
5. Heating/cooling control selectable
6. Auto tuning function
4. A variety of functions extending the possibility of temperature controller
1. Guarantee soak function provided, 16 step ramp/soak
function
2. 8 PID setting pallets, 8 SV pallets capable of frequent
change of control
3. Soft start function that limits MV output when starting up
4. Ramp SV function enables graduate change of SV
5. Loop burnout alarm, heater burnout alarm and different event outputs are available in digital output (option)
6. Control standby function
7. Loader interface (RS232C)
8. RS485 communication (option)
SPECIFICATIONS
1. General Specifications
(1) Power supply :
100 V ( - 15%) to 240 V (+ 10%) AC,
50/60 Hz
24 V (± 10%) DC. 24 V (± 10%) AC,
50/60 Hz.
(2) Power consumption:
12 VA MAX.
(3) Insulation resistance:
20 MΩ MIN. (at 500 V DC)
(4) Withstand voltage:
Power source ⇔ all terminals
1500 V AC for 1 min
Relay contact output ⇔ all terminals
1500 V AC for 1 min
Between others
500 V AC for 1 min
(5) Approvals and certification:
UL(UL873), C-UL(CSA C22.2 No.24-93 or
equivalent), CE mark(LVD : EN61010-1,
EMC : EN61326-1)
EDS11-160c
Date
Apr. 1, 2011
PXG9
2. Input section
2.1 Process value input
(1) Number of inputs:
1 point
(2) Input setting: Programmable scale
(3) Input signal: See Table 1 (thermocouple, resistance
bulb, mV, voltage, current(With external
250Ω resistance) universal input)
(4) Standard measurement range and input type:
See Table 1
(5) Indication accuracy (at Ta = 23˚C) :
• Thermocouple input: ± 0.3%FS ± 1 digit
± 1˚C or ± 2˚C, whichever greater
*except:
Thermocouple B, 0 to 400˚C
± 5%FS ± 1 digit ± 1˚C
Thermocouple R, 0 to 500˚C
±1%FS ± 1 digit ± 1˚C
Thermocouple T, -200 to 0˚C
±0.5%FS± 1 digit ± 1˚C
• Resistance bulb input: ± 0.3%FS ± 1
digit or ± 0.5˚C, whichever greater
• mV input, voltage input, current input:
± 0.3%FS ± 1 digit
(6) Indication accuracy by change of temperature:
± 0.3%FS/10˚C
(7) Indication resolution:
See Table 1
(8) Input sampling cycle:
200 ms (300 ms at position feedback
control)
(9) Input impedance:
• Thermocouple, mV input: 1 MΩ MIN.
• Current input: 250 Ω
• Voltage input: About 1 MΩ
(10) Variation by signal source resistance:
• Thermocouple, mV input: ± 0.3%FS ±
1 digit per 100 Ω
• Voltage input: ± 0.3%FS ± 1 digit per
500 Ω
(11) Allowable wiring resistance:
• Resistance bulb: 10 Ω MAX. (per wire)
(12) Allowable input voltage:
• DC voltage input: Between +35 and
-10 V
• Current input: Within ± 25 mA
• Thermocouple, resistance bulb, mV input: Within ± 5 V
(13) Noise rejection ratio:
• Normal mode: 40 dB (50/60 Hz)
• Common mode: 120 dB (50/60 Hz)
From ground, at 220 V AC, 50/60 Hz
Between input and output, at 220 V AC,
50/60 Hz
(14) Input correction:
(a) User adjustment: Zero point, span
± 50%FS for each
(b) Process value shift: ± 10%FS
(c) Input filter: 0.0 to 120.0 sec (filter OFF
if set at 0.0)
(15) Overrange, underrange:
Beyond range of -5 to 105% (accuracy
not guaranteed between -5 and 0, and between 100 and 105%FS)
2
2.2 Auxiliary analog input (remote SV input)
(1) Number of inputs:
Up to 1 point
(2) Input signal: Voltage, 0 to 5 V DC /1 to 5 V DC
(3) Input impedance:
About 1 MΩ
(4) Sampling rate:
800ms (600ms at Position feed back
control)
2.3 Heater current detector (CT) input
(1) Input type:
Single phase CT Up to 1 point max.
For 1 to 30 A: CTL-6-S-H
For 20 to 50 A: CTL-12-S36-8F
(2) Range of detected current:
1 to 50A
(3) Detected current accuracy:
Setting ± 10%FS
(4) Detected current resolution:
0.1 A
(5) ON time necessary for detection:
800 ms MIN.
2.4 Digital input (DI)
(1) Number of points:
Up to 5 points (up to 3 points for motorized value control output)
(2) Specifications: No-voltage contact or transistor input
(3) Contact capacity:
30 V DC, about 3 mA (per point)
(4) Input judgment:
ON assumed at 1 kΩ or lower (contact) or
5 V DC or lower (transistor)
OFF assumed at 100 kΩ or higher (contact) or 18 V DC or higher (transistor)
(5) Sampling pulse width:
200 ms MIN. (300 ms MIN. at position
feedback control)
(6) Functions:
Remote mode selection, SV changeover,
control standby, AT startup, timer startup,
alarm unlatch, Program selection, start /
stop / reset, PID switching (normal/reverse), etc.
2.5 Valve position feedback signal
(potentiometer) input
(1) Resistance range:
100 Ω to 2.5 kΩ, 3 wire type
(2) Resolution:
0.5%FS
(3) Input accuracy:
± 1.0%FS
(4) Effect of temperture variation:
± 0.5%FS/10˚C
(5) Burnout detection:
none
3. Output section
3.1 Control output
(1) Number of points:
Up to 2 points (2 points: Heating/cooling
control)
(2) Type:
selected out of [1] to [5] below
[1] Relay contact output
• Proportional cycle: 1 to 150 sec
• Contact structure: 1 NO (SPST) contact
• Contact capacity
220 V AC/30 V DC, 3 A (resistive
load)
220 V AC/30 V DC, 1 A (inductive
load)
• Minimum Open/Close current: 100
mA (24 V DC)
• Mechanical life: 20 million operations
MIN. (100 operations/min)
• Electrical life: 100,000 operations
MIN. (rated load)
[2] SSR/SSC drive output
• Proportional cycle: 1 to 150 sec
• ON voltage: 20 V DC (18 to 24 V DC)
• OFF voltage: 0.5 V DC or lower
• Maximum current: 20 mA DC (for
each of outputs 1 and 2)
• Load resistance: 850 Ω MIN.
[3] Current output (0 to 20 mA DC/4 to
20 mA DC)
• Accuracy: ± 5%FS
• Linearity: ± 5%FS
• Load resistance: 600 Ω MAX.
[4] Voltage output (0 to 5 V DC/1 to 5 V
DC/0 to 10 V DC/2 to 10 V DC)
• Accuracy: ± 5%FS
• Linearity: ± 5%FS
• Load resistance: 10 kΩ MIN.
[5] Motorized value control output
• Contact structure: 2 NO (SPST) contacts
• Contact capacity: 220 V AC/30 V DC,
1A
• Minimum ON/OFF current: 100 mA
(24 V DC)
• Mechanical life: 20 million operations
MIN. (100 operations/min)
• Electrical life: 100,000 operations
MIN. (rated load)
• Output interlock: Output interlock
circuit provided
3.2 Digital output (DO)
(1) Number of outputs:
Relay contact output
Up to 3 points (shared common)
Up to 2 points (independent common)
Transistor output
Up to 2 points
(2) Output specifications:
(1) Relay contact output
Contact structure: 1 NO (SPST) contact
Contact capacity: 220 V AC/30 V DC,
1A
Minimum ON/OFF current: 100 mA
(24 V DC)
Mechanical life: 20 million operations
MIN. (100 operations/min)
Electrical life: 100,000 operations MIN.
(rated load)
(2) Transitor output
Contact type: Open collector
Rated values: 30 V DC, 100 mA
ON voltage: 1V or lower
(3) Output functions:
Alarm output (see "Alarm function")
Main unit control mode output, program
status output, etc.
(4) Output cycle: 200ms (300ms at Position feedback control)
3.3 Auxiliary analog output (re-transmission output)
(1) Number of points: 1 point
(2) Type:
Current/voltage output (0 to 20 mA DC/4
to 20 mA DC/0 to 5 V DC/1 to 5 V DC/
0 to 10 V DC/2 to 10 V DC)
• Guaranteed output range: 0 to 20.6 mA
DC/0 to 10.3 V DC
• Accuracy: ± 0.2%FS (± 5%FS at 1 mA
or smaller)
• Linearity: ± 0.2%FS (± 5%FS at 1 mA
or smaller)
• Resolution: 5000 MIN.
• Load resistance 600 Ω MAX. (current)
10 kΩ MIN. (voltage)
(3) Output update cycle:
200ms (Position feedback type: 300ms)
(4) Output contents:
PV, SV, DV, MV
(5) Additional function:
Scaling function
(6) Restriction: Cannot be selected when control output
2 or transmitter power supply output is
used.
3.4 Transmitter power supply output
(1) Number of points: 1 point
(2) Rated values: 19.5 to 24 V DC, 21.6 mA. Maximum load
resistance 400 Ω when transmitter is connected. (Short circuit protection provided;
30mA less at terminal shorted.)
(3) Restriction: Cannot be selected when control output
2 or auxiliary analog output is used.
3
PXG9
4. Indication/setting section
6. Alarm function
4.1 Display unit
6.1 Number of alarm setting points
(1) Type:
LED
(2) Indication contents:
Process value indication: 7 segments,
4 digits [red]
Setpoint indication: 7 segments, 4 digits
[green]
Indication status: 6 indicator lamps
• Up to 5 points (depends on number of DO)
4.2 Setting section
(1) Detectable range:
1 to 50 A
(2) Detected current resolution:
0.1 A
(3) Setting resolution:
0.1 A
(4) Hysteresis:
0.0 to 50.0 A
(1) Type:
Sheet type keys (with emboss)
(2) Number of keys: 4 keys.
SEL ,
,
plus user function
key
5. Control functions
6.2 Alarm type
• Process value (upper limit/lower limit, absolute/deviation, range), main unit error, etc.
(non-excitation, delay, latch, timer function option provided)
6.3 Heater burnout alarm function
7. Communication function
5.1 Control types
(1) 2-position control (set parameter P to 0%)
(2) PID control (fuzzy PID included)
• PID parameters determination: Auto tuning,
selftuning
(3) PID dual (heating, cooling) function (fuzzy PID included)
• PID parameters determination: Auto tuning
(4) Motorized valve control (position feedback or servo
control)
• Full stroke time: 30 sec MIN.
5.2 Control parameters
• Proportional band (P):
0.0 to 999.9%. 2-position control when
P = 0.
• Integral time (I): 0 to 3200 sec. Integral time control invalidated when I = 0.
• Differential time (D):
0.0 to 999.9 sec. Differential time control invalidated when D = 0.
• Control cycle: 200 ms (300 ms at position feedback
control)
• Anti-reset windup:
0 to 100% of measurement range
• Hysteresis band:
50% of measurement range (at 2-position control only)
• Number of SV and PID combinations:
8 combinations.
Changed by any of parameter setting,
digital input, communication and user
function keying
5.3 Control mode
(1) Mode type:
Auto, Manual, Remote
* In case of 2 position control in manual
mode, 2 positions correspond to
MV = 100 or 0%.
(2) Mode changeover:
Auto↔Manual: Balanceless · bumpless
Auto/Manual→Remote: Balance ·
bumpless
Auto/Manual←Remote: Balance ·
bumpless
4
7.1 RS-485 interface
(1) Number of points: 1 point
(2) Physical specifications: EIA RS485
(3) Protocol:
Modbus-RTU
(4) Communication method:
Half duplex bit serial, Asynchronous communication
(5) Code type:
Data length 8 data bits. Parity Odd, even,
none.
(6) Communication rate:
9600 bps, 19200 bps
(7) Connection status:
Up to 32 units connectable including multidrop master function
(8) Communication distance:
Up to 500 m (total connect extension)
8. Processing at power failure
• Memory protection:
Protect by non-volatile memory
9. Self-diagnosis
• Method:
Program error supervision by watchdog
timer
10. Operation and storage conditions
(1) Operating ambient temperature:
-10 to 50˚C
(2) Storage temperature:
-20 to 60˚C
(3) Operating/storage ambient humidity:
90%RH MAX. (no condensing)
(4) Warm-up time:
30 min MIN
(5) Vibration:
10 to 70 Hz, 9.8 m/s2 (1 G) MAX.
(6) Impact:
49 m/s2 (5 G) MAX.
11. Structure
(1) Mounting method:
Mounted with panel
(2) External terminals:
Screw terminals, M3
(3) Case:
• Material: ABS, and degeneration PPO
• Non-combustibility grade: UL94V-0
equivalent
• Color: Black
(4) Protection structure:
• Panel front side: IP66, NEMA-4X equivalent (if panel is mounted using our
genuine packing. Not water-proof if
mounted closely together.)
• Body: IP20 equivalent (slits on top and
bottom)
• Terminals: IP00 equivalent. Terminal
cover can be mounted optionally.
(5) Dimensions: 96 (W) × 96 (H) × 81.5 (D) mm
(6) Mass:
About 300 g
12. Scope of delivery
•
•
•
•
•
•
Controller:
Instruction manual:
Fixture:
Water-proof packing:
Shunt resistor:
Unit nameplate:
1
1
2
1
1
1
unit
copy
pcs
pc
pc
pc
13. User customize function
13.1 Program (ramp/soak) function
(1) Number of program steps
16 steps × 1 pattern,
8 steps × 2 patterns, or
4 steps × 4 patterns
(1 step = 2 segments)
(2) Control option:
Control by digital input
Status output by digital output
(3) Basic function:
[1] Segment time can be set in "Hour,
Minutes" or "Minutes, Seconds"
[2] Guarantee soak
[3] Repeat action
[4] PV start
[5] Delay start
[6] Power failure restoring function
(4) Memory backup:
EEPROM
13.2 User functions
• Pressing the user key can perform Auto/Manual change,
Standby ON/OFF change, remote SV change, ramp/soak
change or other function as assigned
13.3 Password function
• 3 level password function
5
PXG9
CODE SYMBOLS
Standard type
1 2 3 4 5 6 7 8
9 1011 12 13
P XG 9
Digit
Specifications
<Front panel size W × H>
4
96 × 96mm
<Output 1>
5
Relay contact
SSR drive
Current (0 to 20 mA DC/4 to 20 mA DC)
Voltage (0 to 5 V DC/1 to 5 V DC/0 to 10 V DC/2 to 10 V DC)
<Output 2>
6
None
Relay contact
SSR drive
Current (0 to 20 mA DC/4 to 20 mA DC)
Voltage (0 to 5 V DC/1 to 5 V DC/0 to 10 V DC/2 to 10 V DC)
Re-transmission output, current (0 to 20 mA DC/4 to 20 mA DC)
Re-transmission output, voltage (0 to 5 V DC/1 to 5 V DC/0 to 10 V DC/2 to 10 V DC)
Transmitter power supply
<Option 1>
7
None
RS485
Digital input (No.1) + Digital input (No.2)
Digital input (No.1) + RSV1
Digital input (No.1) + CT1
RS485 + Digital input (No.1)
RS485 + RSV1
RS485 + CT1
RS485 + Digital input (No.1) + RSV1
Digital input (No.1) + RSV1 +Digital input (No.2)
<Revision symbol>
8
Note
9
A
C
E
P
Note1
Note1
Note3
Note3
Note3
Note3
Note3
Note3
Note3
Note2
Note1
Note4 Note5
Note2
Note1
Note4 Note5
Note2 Note3
Note2 Note3
Y
A
C
E
P
R
S
T
Y
M
T
H
G
V
K
J
F
2
1
9
10
11
12
13
<Digital output> (relay contact output)
None
Digital output 1 point (No.1)
Digital output 2 points (No.1,2)
Digital output 3 points (No.1,2,3)
Digital output 2 points [independent common] (No. 1, 2)
<Power source, instruction manual>
100 to 240 V AC, no instruction manual
100 to 240 V AC, Japanese instruction manual
100 to 240 V AC, English instruction manual
24 V AC/DC, no instruction manual
24 V AC/DC, Japanese instruction manual
24 V AC/DC, English instruction manual
<Option 2>
None
Digital input (No.3,4,5) + CT2
Digital input (No.3,4,5)
Digital input (No.3,4,5) + digital output (No.4,5) [transistor output]
Digital input (No.3,4,5) + RSV2
None
Note4
N
Y
V
C
A
B
Note1
Note4 Note5
Note2
Note 1: If output 1 was for current or voltage output, option cannot be assigned to CT1 nor CT2.
(If 7th digit was assigned to G or J, or 11th digit to A, 5th digit cannot be assigned to E nor P.)
Note 2: RSV1 in option 1 and RSV2 in option 2 cannot be assigned simultaneously.
(If 7th digit was assigned to H, K, F, 2 11th digit cannot be assigned to D.)
Note 3: In case, in option 1, of DI 2 points + RSV1 or RS485 + DI 1 + RSV1, output 2 cannot be assigned.
(If 7th digit was assigned to F or 2, 6th digit cannot be assigned to A, C, E, P, R, S nor T.
Note 4: In case of CT1 in option 1, or CT2 in option 2, digital output cannot be assigned to None.
(If 7th digit was assigned to G or J, or 11th digit to A, 9th digit cannot be assigned to 0.)
Note 5: CT1 in option 1 and CT2 in option 2 cannot be selected simultaneously.
(If 7th digit was assigned to G or J, 11th digit cannot be assigned to A.)
6
0
1
F
M
J
Y
A
B
C
D
0 0
Digit
CODE SYMBOLS
Motorized valve control type
1 2 3 4 5 6 7 8
9 1011 12 13
Digit
P XG 9
Digit
Specifications
<Front panel size W × H>
4
96 × 96mm
<Output 1>
5
Motorized valve control output (Without PFB)
Motorized valve control output (With PFB)
<Output 2>
6
None
Auxiliary Digital output
Transmitter power supply
<Option 1>
7
None
Digital input (No.1,2,3) + RSV1
RS485 + Digital input (No.1,2,3)
RS485 + Digital input (No.1) + RSV1
<Revision symbol>
8
Note
9
S
V
Y
A
T
Y
E
U
F
1
9
10
11
12
13
<Digital output> (relay contact output)
None
Digital output 1 point (No.1)
Digital output 2 points (No.1,2)
Digital output 3 points (No.1,2,3)
Digital output 2 points [independent common] (No. 1, 2)
<Power source, instruction manual>
100 to 240 V AC, no instruction manual
100 to 240 V AC, Japanese instruction manual
100 to 240 V AC, English instruction manual
24 V AC/DC, no instruction manual
24 V AC/DC, Japanese instruction manual
24 V AC/DC, English instruction manual
<Option 2>
None
None
0
1
F
M
J
N
Y
V
C
A
B
Y
0 0
7
PXG9
OPTIONALLY ITEMS
Instruction manual for communication functionRS485 (Modbus)
Current detector for heater burnout alarm (CT)
1 to 30A
20 to 50A
Rear terminal cover
Shunt resistor 250Ω ± 0.1%
PC loader communication cable
Type:INP—TN514450—E
Type:ZOZ *CCTL—6—S—H
Type:ZOZ *CCTL12—S36—8F
Type:ZZPPXR1—B230
Type:ZZPPXR1—A190
Type:ZZP PXH1 *TK4H4563
TABLE 1
[1] Unit of temperature: ˚C
Input type
Input
code
JPt100Ω
Pt100Ω
J
Thermocouple
K
R
B
S
T
E
N
PLUnusable
DC voltage DC0 to 5V
DC1 to 5V
DC0 to 10V
DC2 to 10V
DC0 to 100mV
DC0 to 20mA
DC current
DC4 to 20mA
0
Resistance
bulb
1
2
3
4
5
6
7
8
12
13
14
15
16
17
18
19
15
16
Measurement range [˚C]
Max.
Min.
0 to 150
-150 to 600
-200 to 850
0 to 150
0 to 400
0 to 1000
0 to 1200
0 to 400
0 to 1600
0 to 1800
0 to 1600
-200 to 400
-200 to 200
-200 to 800
0 to 800
0 to 1300
0 to 1300
Indication/setting resolution [˚C]
Max.
Min.
1
0.1
1
1
1
0.1
0.1
0.1
1
1
1
0.1/1
1
0.1/1
1
1
-1999 to 9999
(Range where scaling is allowed)
1/1000 digit
[2] Unit of temperature: ˚F
Input type
Resistance bulb
Thermocouple
DC voltage
DC current
8
Pt100Ω
J
K
R
B
S
T
E
N
PLUnusable
DC0 to 5V
DC1 to 5V
DC0 to 10V
DC2 to 10V
DC0 to 100mV
DC0 to 20mA
DC4 to 20mA
Input
code
1
2
3
4
5
6
7
8
12
13
14
15
16
17
18
19
15
16
Measurement range [˚F]
Max.
Min.
-238 to 1562
32 to 302
32 to 752
32 to 1832
32 to 2192
32 to 752
32 to 3272
32 to 3272
32 to 2912
-328 to 752
-328 to 392
-328 to 1472
32 to 1472
32 to 2372
32 to 2372
-1999 to 9999
(Range where scaling is allowed)
Indication/setting resolution [˚F]
Max.
Min.
1
1
1
0.1
0.1
0.1
1
1
1
1
1
1
1
1/1000 digit
* Input a DC current to 1 to 5 V
DC or 0 to 5 V DC range via
external resistor of 250 Ω.
* Input type and ranges are
standardly factory set as follows.
K: 0 to 400˚C
Pt, JPt: 0 to 150˚C
Voltage, current: 0 to 100%
Standard input type is
thermocouple K.
OUTLINE DIAGRAM (Unit : mm)
Mounting bracket
94.5 (terminal cover included)
10
96
79.5
107.5
93.7 (terminal cover included)
96
91.5
2
t
Terminal cover (option)
Water-proof packing
Panel
PC loader interface
13-24 25-36
7
8
9
10
11
12
31
32
33
34
35
36
Panel cutout size
+0.8
92 0
Terminal screw M3
Rear view
116 MIN.
25
26
27
28
29
30
+0.8
1
2
3
4
5
6
920
1-12
6.2
37-48 49-60 61-72
100 MIN.
n units mounted
Mass about 0.3 kg
9
PXG9
OPTIONALLY ARRANGED ARTICLES
Heater current detector (CT)
. Specification : 20 to 50 A
. Type
: CTL-12-S36-8F
. Specification : 1 to 30 A
. Type
: CTL-6-S-H
21
φ2.36
30
2.8
7
9
15
40
2.5
10.5
25
φ5.8
10
φ12
φ3.5
M3,depth 4
30
40
Note 1) Detection is available only for single phase heater.
Note 2) Unusable for heater control by thyristor phase angle control.
10
7.5
40
15
30
EXTERNAL CONNECTION DIAGRAM
Standard type with communication
OPTION1
RS485,DI1,RSV1,CT1
RS485+DI+RSV1
RS485+RSV1/RS485+CT1/RS485+DI
1
1
RS485
RS485
2
DI1
3
DI-COM
4
OUT2
1
Output 2
1
RS485
RS485
2
2
2
5
5
5
3
3
DI1
3
6
6
6
4
DI-COM
4
RSV1
CT1
4
Re-Trans
(Current)
5
Re-Trans
(Voltage)
Transmitter
power supply
RSV1
6
5
5
5
5
6
6
6
6
SSR Drive output
Current output
Voltage output
Contact output
TOP
1
25
2
26
3
27
4
28
5
29
6
TOP
30
25
DI3
25
DI3
25
DI3
26
DIOCOM
26
DIOCOM
26
DIOCOM
27
DI4
27
DI4
27
DI4
28
DI5
28
DI5
28
DI5
31
29
8
32
30
9
33
10
34
11
35
12
36
7
DI3,DI4,DI5,DO4,DO5,CT2,RSV2
OPTION2
29
30
Power supply
11
12
11
12
100-240VAC 24VAC/24VDC
50/60Hz
50/60Hz
DO
DO1, DO2, DO3
DO1COM
7
DOCOM
DO1
8
DO2COM
DO2
30
Output 1
31
31
31
31
32
32
32
32
SSR Drive output
Current output
Voltage output
Contact output
PS
29
DO5
RSV2
CT2
OUT1
DO4
PV
Process value input
(Note 1)
7
33
33
33
33
33
DO1
8
34
34
34
34
34
9
DO2
9
35
35
35
35
35
10
DO3
10
36
36
36
36
36
R.T.D.
DC Voltage
(V)
DC Voltage
(mV)
T.C.
DC Current
(mA)
Note 1: Connect the furnished resistor to 33 and 36 .
11
PXG9
Standard type without communication
OPTION 1
DI1,DI2,RSV1,CT1
DI1+DI2+RSV1
DI1+RSV1/DI1+CT1/DI1+DI2
DI1
1
DI1
DI-COM
2
DICOM
DI2
3
1
DI1
2
DICOM
3
RSV1
4
OUT 2
Output 2
1
DI1
1
2
DICOM
2
5
5
5
3
DI2
3
6
6
6
CT1
4
4
4
Re-Trans
(Current)
5
RSV1
Re-Trans
(Voltage)
Transmitter
power supply
6
5
5
5
5
6
6
6
6
SSR Drive output Current output
Contact output
TOP
TOP
1
25
2
26
3
27
4
28
5
29
6
30
DI3,DI4,DI5,DO4,DO5,CT2,RSV2
OPTION 2
25
DI3
25
DI3
25
DI3
26
DIOCOM
26
DIOCOM
26
DIOCOM
27
DI4
27
DI4
27
DI4
28
DI5
28
DI5
28
DI5
31
29
8
32
30
9
33
10
34
11
35
12
36
7
29
30
OUT 1
11
12
100-240VAC
50/60Hz
11
12
24VAC/24VDC
50/60Hz
DO
DO1, DO2, DO3
DO1COM
7
DOCOM
DO1
8
DO2COM
9
DO2
10
PV
30
Output 1
31
31
31
32
32
32
32
SSR Drive output
Current output
Voltage output
Process value input
(Note 1)
7
33
33
33
33
33
DO1
8
34
34
34
34
34
DO2
9
35
35
35
35
35
DO3
10
36
T.C.
36
36
R.T.D.
DC Voltage
(V)
Note 1: Connect the furnished resistor to 33 and 36 .
12
29
DO5
31
Contact output
Power supply
DO4
RSV2
CT2
PS
Voltage output
36
DC Voltage
(mV)
36
DC Current
(mA)
Motorized valve control type with communication
OPTION 1
RS485,DI1,DI2,DI3,RSV1
RS485+DI+RSV1
RS485+DI1+DI2+DI3
1
1
RS485
RS485
2
2
DI1
3
DI1
3
DI-COM
4
DI-COM
4
5
DI2
5
6
DI3
6
RSV1
Control output
for motorized valve
PO
25
Close
26 COM
TOP
1
25
2
26
3
27
4
28
5
29
6
30
7
31
27 Open
Position feedback input
FB
28
29
TOP
30
8
32
9
33
10
34
11
35
12
36
I
IO
PFB
I
DO/ AUX contact
XPS output
Transmitter
power supply
31
31
32
32
AUX Contact
Output
PS
Power supply
11
12
100-240VAC
50/60Hz
11
12
24VAC/24VDC
50/60Hz
DO
DO1,DO2,DO3
PV
Transmitter
Power Supply
Process value input
(Note 1)
DO1COM
7
DOCOM
7
DO1
8
DO1
8
34
34
34
34
34
DO2COM
9
DO2
9
35
35
35
35
35
DO2
10
DO3
10
36
36
36
36
36
33
T.C.
33
R.T.D.
33
DC Voltage
(V)
33
DC Voltage
(mV)
33
DC Current
(mA)
Note 1: Connect the furnished resistor to 33 and 36 .
13
PXG9
Motorized valve control type without communication
OPTION 1
DI1,DI2,DI3,RSV1
DI1+DI2+DI3+RSV1
DI1
1
DICOM
2
DI2
3
DI3
4
5
RSV1
6
Control output
for motorized valve
PO
25
Close
26 COM
TOP
1
25
2
26
3
27
4
28
5
29
6
30
7
31
27 Open
Position feedback input
FB
I
28
29
TOP
30
8
32
9
33
10
34
11
35
12
36
IO
PFB
I
DO/ AUX contact
XPS output
Transmitter
power supply
31
31
32
32
AUX contact
output
PS
Power supply
11
12
100-240VAC
50/60Hz
11
12
24VAC/24VDC
50/60Hz
DO
DO1,DO2,DO3
PV
Transmitter
power supply
Process value input
(Note 1)
DO1COM
7
DOCOM
7
DO1
8
DO1
8
34
34
34
34
34
DO2COM
9
DO2
9
35
35
35
35
35
DO2
10
DO3
10
36
36
36
36
36
33
T.C.
33
R.T.D.
33
DC Voltage DC Voltage
(V)
(mV)
Note 1: Connect the furnished resistor to 33 and 36 .
14
33
33
DC Current
(mA)
ISOLATED BLOCK DIAGRAM
Internal Circuit
Power supply
Process value input
Valve position feedback signal input
Control output 1 (relay contact)
or
OPEN output
Auxiliary analog input (remote SV input)
Heater current detector input
Control output 1 (SSR drive, current, voltage)
Control output 2 (relay contact)
or
CLOSE output
Control output 2 (SSR drive, current, voltage),
or
auxiliary analog output (re-transmission output)
or
Transmitter power supply
Digital output 1
(relay contact)
Digital input 1 to 5
Digital output 1 to 3
(relay contact)
Digital output 4, 5 (transistor output)
Digital output 2
(relay contact)
Communication (RS485)
When the 9th digit of the
code symbols = J
(DO1, 2 independent common)
When the 9th digit of the
code symbols = Other than J
(DO1 to 3 shared common)
: Basic insulation (1500 V AC)
: Functional insulation (500 V AC)
: Non-insulation
15
PXG9