PROGRAM CONTROLLER X (96mm)
DATA SHEET
PVX
The program controller X (PVX) is a high performance controller designed on the basis of many years of Fuji’s successful
experience and advanced technologies.
FEATURES
1. Display of 3 different datas
Three different datas such as measured value (PV), set
value (SV) and time can be monitored simultaneously.
2. 20-segment program patterns (9 patterns)
Program patterns can be linked in series or repeated.
3. Full multi-input type
The program controller accepts a large number of inputs
(full multi-input). Up to 11 kinds of thermocouples, 1 resistance bulb, 6 different voltage inputs and a current input
can be connected.
4. Wide input/output functions (option)
The program controller is able to expand the input/output
functions up to 8 points of digital inputs, 11 points of digital outputs and 2 points of auxiliary analog outputs.
SPECIFICATIONS
96 × 96mm
Full multi-input
• Thermocouple: J, K, R, B, T, E, S, N, U,
WRe5-26, PL-II
• Platinum resistance bulb: Pt100
• DC voltage/current
Input accuracy: ± 0.2% of full scale, ± 1 digit
Input sampling cycle: 100ms
Control action: PID with auto-tuning
Control output: • Relay contact
• Voltage pulse output (for SSR drive)
• Current output
Alarm output:
2 points (ALM1, ALM2)
Program function: • Number of patterns: 9 patterns (max.)
• Number of segments/patterns: 20 segments
• Multi-memory (PID, etc.): 9 sets
• Pattern linkage/repeat function: possible
• Time setting: hour/minute or minute/
second
Panel size:
Input:
Operation mode: • Program operation
• Fixed value (FIX) operation
• Manual (MAN) operation
Digital input/output:
Option:
Power source:
• Time signal output: 4 points (TS1, TS2,
TS3, TS4)
• External command input: 4 points (Reset, Run, Hold, Advance)
• Pattern select input: BCD 1 digit (23, 22,
21, 20)
• Status output (Output informations): 3
points (Reset, Run/Hold, End)
• Auxiliary analog output: 2 points (AO1,
AO2)
• Expansion digital output: 2 points (TS5,
TS6 or ALM3, ALM4)
Flexible supply voltage: 100 to 240V AC
EDS11-124d
Date
Jan. 31, 1997
PVX
3. Program setting
FUNCTIONS AND PERFORMANCE
1. Input
(1) Input accuracy:
± 0.2% of full scale, ± 1 digit (under standard condition), cold junction compensation error: ± 1°C
(2) Input:
Thermocouple
(range code setting)
J
J
K
K
K
R
B
T
T
E
E
S
N
U
WRe5-26
PL-II
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
0
0
0
0
0
0
0
–199.9
–150
0
–199.9
0
0
–199.9
0
0
400°C
800°C
400°C
800°C
1200°C
1600°C
1800°C
200°C
400°C
800°C
800°C
1600°C
1300°C
400°C
2300°C
1300°C
(R: ± 1% within the range of
0 to 400°C)
(B: ± 5% within the range of
0 to 500°C)
Pt100Ω(*):
0
0
0
0
–50
–100
–199.9
–199.9
JPt100(*)Ω:
0
0
0
0
–50
–100
–199.9
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
150°C
300°C
500°C
600°C
100°C
200°C
600°C
850°C
150°C
300°C
500°C
600°C
100°C
200°C
600°C
Pattern selection, program reset, start, stop and skip are
possible with front panel key, digital input.
(4) Time setting
Setting of hour/minute or minute/second
Hour/minute: 0 (hr) 0 (min) to 99 (hr) 59 (min)
Minute/second: 0 (min) 0 (sec) to 99 (min) 59 (sec)
4. Control action
(1) Auto-tuning PID action
P: 0.0 to 999.9% (ON/OFF control, P=0)
I: 0 to 3200sec (integral action OFF, I=0)
D: 0.0 to 900.0sec (derivative action OFF, D=0)
(2) Multi-memory
PID, etc; up to 9 sets
°F display; possible
0.1°C/°F display; possible
(1000°C/°F span or less)
DC voltage/current (full programmable scale; –999 to 9999)
0 to 10mV DC, 0 to 100mV DC, 0 to 1V DC, 0 to 5V DC
1 to 5V DC, 0 to 10V DC, 4 to 20mA DC
Note: * Pt100…IEC Pub751-1983
(3) Input sampling cycle: 100ms
5. Digital input/output
(1) Digital input
Usual specification :
16V DC, 15mA
External command input :
Reset: Program reset
Run: Program start
Hold: Program stop
Advance: Segment feed
Pattern select input :
2. Output
(1) Control output
Relay contact output :
220V AC/30V DC, 3A (resistive load)
SPDT contact
Electrical expected life: more than 105 operations
Minimum ON/OFF current: 0.1A (24V
DC)
SSR drive output :
ON: 10 to 18V DC
OFF: max. 0.5V
Max. current: 20mA DC
Current output :
4 to 20mA DC (allowable load: 600Ω or
less)
(2) Alarm output (ALM1, ALM2)
Relay contact output :
2 points
220V AC/30V DC, 1A (resistive load)
SPST contact
Electrical expected life: more than 105 operations
Minimum ON/OFF current: 0.1A(24V DC)
2
Program operation
Fixed value (FIX) operation
Manual (MAN) operation
(3) Program operation
Resistance bulb
(range code setting)
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
(1) Program function
Number of patterns: 9 patterns (max.)
Number of segments/patterns: 20 segments
Multi-memory (PID, etc.): 9 sets
(2) Operation mode
BCD input; 1 digit (23, 22, 21, 20)
(2) Digital output
Time signal output (TS1, TS2, TS3, TS4)
Open-collector output: 4 points, 24V DC, 50mA
Status output :
Open-collector output: 3 points, 24V DC, 50mA
Reset: Program reset status
Run/Hold: Program start/stop status
End: Program end status
6. Option output
(1) Expansion digital output
Expansion alarm output (ALM3, ALM4) or expansion time signal output (TS5, TS6)
Open-collector output: 2 points, 24V DC, 50mA
(2) Auxiliary analog output
Output points : 1 or 2 points
Output data : Measured value, set value or manipulated
value
Output accuracy : ± 0.2% of full scale
Kinds of output :
1 to 5V DC
0 to 5V DC
0 to 10V DC
Additional function : Scaling
7. Operating conditions, etc.
Power supply voltage: 100 ( -15%) to 240 (+10%) VAC, 50/
CODE SYMBOLS
60Hz
Power consumption: 30VA or less
Ambient temperature: 0 to 50°C
Ambient humidity: 90%RH or less (free from condensation)
Memory backup: Lithium battery
(5 years expected: 0 to 40°C)
Dimensions (H × W × D): 96 × 96 × 173.5mm
Mass{weight}: 1kg (approx.)
Mounting angle: Backward inclination within 15°
1 2 3 4 5 6 7 8
PVX
9 10 11 12 13
T S 1 -
Y
E
Description
Control output
Relay contact output
SSR/SSC drive output
Current output (4 to 20mA DC)
1
2
3
Digital input
External command input (4 points)
Pattern select input (4 points)
External command input
+Pattern select input
C
P
D
Time signal output, 1 to 4
T
Output status
S
Expansion digital output
(open-collector output, 2 points)
Without
Used as time signal (TS5, 6)
Used as alarm (ALM3, 4)
Y
T
A
Auxiliary analog output signal
Without
Voltage output, 1 point
Voltage output, 2 points
Note:Prior to delivery from
factory: 0 to 10V DC
0
1
2
Communication function
Without
With T-link
Y
T
E
Front panel indication and
instruction manual (option)
English
Note : If the range is not designated on order, the product will be delivered
with the following range selected.
K thermocouple 0 to 400°C.
3
PVX
FUNCTIONAL BLOCK DIAGRAM
DI
Reset
External
command
input
Reset
Run
External command input
Hold
Pattern select input
Advance
Status output
Run/Hold
End
Reset
3 points
Run/Hold
23
Pattern
select
input
22
Status
output
End
21
20
9 patterns
9 sets
Fixed value,SV
Program setting,
20 segments
Ficed
value
(FIX)
Sensor input
AI
Control
parameter
Program
SV
PV
Filter
Auto
MV
PID with
auto-tuning
Control output
Man
Full multi-input
Manual operation
Guarantee soak function
PV start function
Pattern linkage function
Pattern repeat function
(99,max.)
Auxiliary analog
output, 1/2 points
(PV/SV/MV)
Time signal output,
4 points (+2 points) (Note)
Alarm output,
2 points (+2 points) (Note)
AO
(Option)
DO
Communication function
with T-Link (Note)
Power supply,
100 to 240V AC
4
Note :+2 points···Either time signal or
alarm output can added (option).
:Communication function with
T-link can be added (option).
OUTLINE DIAGRAM
(Unit:mm)
12
173.5
115
90.5
96
Panel mounting bracket
Panel cutout
116 min.
92 +0.8
0
100 min.
92 +0.8
0
Connection diagram
Control output 1
(Contact output,
4 to 20mA DC,
SSR/SSC drive output)
MV1-COM
+
-
1
2
MV1-1
MV1-2
TS1
TRX-COM
9
10
TS2
11
TS3
12
TS4
13
ALM1
3
Alarm output 1
ALM2
4
Alarm output 2
5
Power supply,
100 to 240V AC
6
ALMCOM
8 G
Time
signal
1-4
output
Alarm 3-4
output
or
time signal
5-6 output
19
20
21
TRX1 27
ALM3/TS5
A02 29
A01 30
ALM/TS-COM
22 DI-23
A
TRX2 28
ALM4 /TS6
A0-COM 31
RTD
Input signal,
PV + +
Aux.
mV
TC
analog
output
- -
+
4~20mA
DORESET
DOAC
RUN/HOLD
7 AC
18
14
15
DO-END
16
DO-COM
17
Status
output
Pattern
select
input
23 DI-22
32
1
33
DIRESET
24 DI-2 DIRUN
25 DI-20 DIHOLD
26 DICOM DIADVANCE
34
35
External
command
input
V
+
250Ω
(Note)
B
36
37
38 SC
39
40
41
42
Note:A resistor(250Ω± 0.1%) should
be used for 4 to 20mA DC input.
SCOPE OF DELIVERY
Main unit and panel mounting bracket
5
PVX
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan
http://www.fesys.co.jp/eng
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http: //www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan