FUJI EDS11-105E

FC SERIES SETTER (CONTINUOUS OUTPUT TYPE)
DATA SHEET
PNF1
The FC series setter is used for remote setting of a controller or variable constant setting of various types of computing elements.
This instrument uses a solid state indicator and a
pushbutton operation system to provide reliable monitoring
and operating functions.
FEATURES
1. High reliability
This instrument is designed with few mechanical parts.
It is mainly composed of electronic parts such as a solid
state indicator which was formerly consisted of mechanical parts.
2. International standards
This instrument is compact in size, conforming to international standards IEC. It operates on 24V DC power to
deliver 1 to 5V DC signals as recommended by IEC
standards.
100 and 200V AC power are also available for convenience of operation.
3. Front panel operation
Process values and set points can be read accurately with
digital indications on panel front. Various parameter settings and setting operations are also possible from the
front panel of the instrument.
FUNCTIONAL DIAGRAM
PV
Linearize
Square-root
extraction
SV
Local mode
output (LS)
Remote request
(R-REQ)
Filter
Process value
nput (PV)
External set point
nput (CAS or PI)
1 to 5V DC,
pulse width,
or pulse number)
Compensated
process
value signal
(KPV)
Limiter
H
Set point
output signal
(SV)
R
L
L
FAULT
SV
Remote
acknowledege
signal (R-ACK)
FLT output
High alarm
output (H)
KPV
ALM
Low alarm
output (L)
EDS11-105e
Date
Jul. 1, 1994
PNF1
SPECIFICATIONS
1. Input signal
(1) Process value input signal:
One input selectable from the following
Voltage input signal
current input signal
I+
I0
I–
1 to 5V DC
Input resistance,
1MΩ or more
4 to 20mA DC
24V ± 2V DC can be Allow. error
supplied to transmit- ± 0.2%/FS
ter only when AC
power is used
Allow. error
± 0.2%/FS*
Note: * FS: Full scale
(2) Analog input signal: 1 point
External set point CAS
input signal
1 to 5V DC Input resistance, 1MΩ or more
Allow. error ± 0.2%/FS
(3) Digital input signal: 1 point
Remote
acknowledge
signal
R-ACK
Contact input
(photo-coupler
insulation)
ON 0V, OFF 24V
( input current, approx.
11mA/24V DC)
Contents of indication:
Process value (industrial value), set point
(industrial value), high/low alarm, etc.
Indication contents are selectable by F/S ,
,
keys on front panel.
Setting method: By using F/S ,
,
,
, ST keys
on front panel
(4) Setting functions
Fixed value setting method:
By using of
,
pushbuttons on front
panel.
Setting speed, approx. 40 sec/FS
Remote setting method:
By use of external set point signal
(voltage or pulse width input)
Tracking speed setting range; 0 to 900
sec/FS
(5) Operation mode changeover
By using of R/L pushbutton on front panel
R
R
(4) Pulse width or pulse number input signal: 1 set (either one)
Balanceless bumpless
L changeover
L changeover
Voltage signal*
Balance bumpless
Pulse width signal
Balanceless bumpless
Note: * Balanceless bumpless by setting tracking speed
Pulse width input
signal
Pulse number input signal
Contact input
(photo-coupler
insulation)
PI+
PI–
ON 0V, OFF 24V
(input current, approx.
11mA/24 DC)
ON 0V, OFF 24V
(approx. 11mA/24V DC)
max. input frequency
500Hz
2. Output signal
(1) Analog output signal: 2 points
Compensated process
value signal
KPV
Set point output
signal
SV
1 to 5V DC
Output resistance, 1Ω
or less
Allow. error ± 0 2%/FS
(2) Digital output signal: 5 points
Fault output
FLT
Open-collector
LS
Remote request signal R-REQ output (photocoupler insulaHigh alarm output
H
tion)
Low alarm output
L
Local mode output
Rated output,
30V x 0.1A DC,
max.
3. Indication, setting, operating functions
(1) Bargraph indication
PV indicator
SV indicator
Indication method
LED (red)
LED (green)
No. of segments
101 + 2
101 + 2
Range
0 to 100%, linear
0 to 100%, linear
Resolution
1 %/FS
1%/FS
Scale length
100mm
100mm
Indicating mode
0 to 100% bargraph indication,
0 to 100% reverse bargraph indication,
dot indication, –50 to +50% deviation
indication
(2) Operation mode indication
Indicating method:
LED (green)
Green: L(local), R(remote)
(3) Numerical value indication, setting
Indication method:
LED (red), name in 3 digits + numerical
value in 5 digits (negative code included)
2
(6) Alarm functions
High/low alarm settable in industrial values for process value
input signal.
4. Power failure processing functions
Power failure detection:
Setting output held at power failure detection.
During power failure:
Data backed up by capacitor up to 5
minutes. Initial value of set point stored
in non-volatile memory (10 years expected
at ambient temperature of 50°C or less).
Power failure recovery:
Initial or continuous start mode can be
set within 5 minutes of power failure.
Recovery from power failure lasting
longer than 5 minutes is initial. **
Note: ** Operation mode set at initial can be registered
L: Local mode or R: Remote mode
5. Self-diagnosis functions
Input signal abnormality:
FLT lamp lights, FLT output contact "ON"
Indication of abnormal contents:
Cause of abnormality indicated in numerical values on front panel.
6. Transmission functions
(1) Transmission items
Supervisory items:
PNF
host
Process variable, set point, operation
mode, alarm information, fault information, various limiter values, constants, etc.
Setting operation items:
Host
PNF
Set point, operation mode, various limiter
values, constants, etc.
(2) Transmission setting inhibit:
Parameter setting enable/inhibit can be designated by
transmission from the host. Designation is done by keys
on the front panel key.
(3) Communication interface
(a) T-link: Private interface
Transmission speed: 500Kbps
No. of units connectable: 32 max.
Transmission distance: 1km max.
Transmission form: Multi-drop
Control method: I/O transmission and message
(b) RS-422A/485: Universal interface
Transmission speed: 2400, 4800, 9600 or 19200bps
configurable
No. of units connectable: 31 max.
Transmission distance: 1km max.
Transmission form: Multi-drop
Control method: Polling/selecting
(c) CC data line: Private interface
Transmission speed: 19.2Kbps
No. of units connectable: 15 max.
Transmission distance: 500m max.
Transmission form: Multi-drop
Control method: Polling/selecting
CODE SYMBOLS
1 2 3 4 5 6 7 8
9 10
5 - 0
PNF 1
Description
Process value input signal
1 to 5V DC
4 to 20mA DC
A
B
Setting method
L type
R-L type
A
B
Power supply
24V DC (20 to 30V DC)
100V AC (85 to 132V/47 to 63Hz AC)
200V AC (187 to 264V/47 to 63Hz AC)
1
2
3
Y
T
R
S
C
Transmission functions
None
T-link
RS-422A
RS-485
CC data line
7. Other functions
Data protective function by pass code
8. Operating conditions
Power supply:
Select from 3 types
24V DC (20 to 30V DC)
100V AC (85 to 132V/47 to 63Hz AC)
200V AC (187 to 264V/47 to 63Hz AC)
Power consumption:
Approx. 11W (DC)
Approx. 20VA (AC)
Dielectric strength:
1500V AC, 1 min.
Insulation resistance:
500V DC, 100MΩ or more
Ambient temperature:
0 to 50°C
Ambient humidity:
90% RH or less
Enclosure:
Steel case
Rating plate (Name plate):
100 (H) x 70 (W) mm, white acryl
Dimensions:
144 (H) x 72 (W) x 391 (D) mm, IEC
(DIN) standard
Mass (weight): Approx. 2.9kg
Mounting method:
Flush indoor mounting; vertical mounting.
Mountable on tilted surface angle "α"
α=0° to 90°
Finish color:
Munsell N 1.5 for both front panel and
case
Scope of delivery: Setter and mounting bracket
3
PNF1
OUTLINE DIAGRAM
(Unit:mm)
Panel thickness 8mm or less
16
144
Terminal
Terminal cover
Support
bracket
140
36
Mounting
bracket
200min.
72
355
Panel cutout
+1
0
250min.
When mounting "n" units
68
4
+0.7
0
138
138
+1
0
200min.
When mounting 1unit
(72.2n – 4)
+1
0
No. of units
n 2
CONNECTION DIAGRAM
Block terminals (M4 screw)
AI
Process value input
I+
(PV)
I–
(SC)
11
12
13
DO
(Local mode)
LS
14
15
AC
16
31
Io
32
PI+
33
PI–
34
FLT
35
AC
(Pulse width
input or pulse
number input)
DO
(FLT output)
AO
(Compensated process
value signal)
AO
(Set point output
signal)
AI, AO
Common bus
DO
(High alarm)
DO
(Low alarm)
Instrument power
supply (24V DC, AC
power)
DI, DO
24V power supply
Earth
Instrument power (AC)
KPV
51
71
SV
52
72
53
73
54
74
55
75
56
76
SC
57
77
R-REQ
H
58
78
R-ACK
L
59
79
PC*
60
80
PCD
61
81
VP*
G
62
82
VPD
SC
–
–
CAS
AI
(External set point)
AI, AO
Common bus
DO
(Remote request)
DI
(Remote acknowledge)
+ Instrument power supply
(24V DC, AC power)
+
DI, DO
24V power supply
Note: * Symbols for AC instrument power are VPO, PCO,
approx. 24V DC (0.1A max.) output.
Connection for process value input terminals
1 to 5V DC
+
11
–
12
+
+
11
–
–
12
+
11
–
12
31
The 5th digit of
code symbols
A
4 to 20mA DC
The 5th digit of
code symbols
B
4 to 20mA DC
with inner DC
power supply
of CC-S
The 5th digit of
code symbols
B
31
+
–
31
PC
60
5
PNF1
COMMUNICATION CONNECTOR
1 SIG GND
6
2 SHLD(SD)
7
8 RXD +
9 RXD –
3 INH
4 TXD+(T1)
1 SIG GND
6
2 SHLD(SD)
Black
7
White
8 RXD +
9 RXD –
5 TXD–(T2)
Green
3 INH
4 TXD+(T1)
5 TXD–(T2)
Yellow
Note:Symbol in ( ):
T-link terminal symbol
Brown
Red
6
7
8 RXD +
9 RXD –
1 SIG GND
1 SIG GND
6
2 SHLD(SD)
7
3 INH
8 RXD +
4 TXD+(T1)
9 RXD –
5 TXD–(T2)
LINE
TERMINATION
RESISTOR
2 SHLD(SD)
Black
3 INH
White
4 TXD+(T1)
5 TXD–(T2)
Green
Yellow
Red
Brown
Terminal station
HOST
MASTER
CONTROLLER
First station
Host
Termination
Resistor
Communication cable
PNF1
PNF1
PNF1
PNF1
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan
http://www.fesys.co.jp/eng
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http: //www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan