FUJI EDS13-18B

SAFETY BARRIER
DATA SHEET
PWX
This safety barrier is used for intrinsic safety explosionproofing of electronic instrumentation systems to ensure safe
operation in the process of generating explosive gases.
It is used in combination with field instruments installed in
hazardous area as an intrinsic safety explosion-proof system.
SPECIFICATIONS
Explosion-proof
Applicable gas:
structure:
Intrinsic safety explosion-proof
FCX transmitter gas (3aG4)
Optical switch signal converter gas
(3aG4 and 2G4)
Optical repeater gas (3aG4 and 2G4)
Optical fiber type multi-point temperature converter gas (3aG4 and 2G4)
FCX-AII, AIII series transmitter (Ex ia
IICT4)
Safety hold rating:
250V AC and 250V DC
Combination instrument:
FCX Series transmitter, optical repeater,
optical switch signal converter, optical fiber type multi-point temperature
converter (Inspection guarantee No. of
safety barrier should be attached to instrument)
FCX-AII, AIII series transmitter (Device
Certification)
Ambient temperature of combination instrument:
60˚C or less
Modification of combination instrument:
Modification is prohibited (unit can be
replaced).
Grounding:
Class A grounding
Mounting method:
Safety barrier should be installed in
non-hazardous area using the supplied
clip screw.
Terminal structure:
Input/output terminal; rod type plug-in
system [up to 4mm2(12AWG)]
Earth; M4 screw terminal (with nut)
Rated operating voltage:
25.8V DC ±0.5%
Total resistance: Terminal 1 to 3 ... 340Ω
Terminal 2 to 4... [0.9V+20Ω] or short
Intrinsic safety max. voltage:
28V
Intrinsic safety max. current:
93mA
Fuse:
50mA
External wiring condition:
Combination
instrument
FCX transmitter
Optical switch
signal converter
Optical repeater
Allowable external Allowable external Allowable external
Applicable
wiring resistance wiring static capacity wiring inductance
gas
(less than )
(less than F )
(less than mH )
Note)
3aG4
3aG4
2G4
16
0.059
1
under application under application
under application
3aG4
86
0.022
1
2G4
86
0.22
5
86
0.022
1
86
0.22
5
30
0.0504
Optical fiber
3aG4
type multi-point
temperature
2G4
converter
FCX-AII, AIII
series transmitter ExiaIICT4
1.91
Note) Indicates allowable resistance of external wiring terminal when input
resistance 250Ω of upper distributor is substracted.
Explosion-proof structure:
Intrinsic safety explosion-proof
Allowable common mode voltage:
AC 0.5Vrms
Error:
0.01% or less
Ambient temperature:
5 to 95% RH
Error:
0.01% or less
Dimensions (H×W×D):
61.5×93.5×14.2mm
Mass:
About 125g
Indoor installation structure, plastic case
Structure:
Code symbols
1 2 3 4 5 6 7 8
PWX
Description
A 0 01
A
B
C
D
A
Application
FCX transmitter (4 to 20mA, 2-wire system), 3aG4
Optical switch signal converter, 3aG4 (under application)
Optical switch signal converter, 2G4 (under application)
Optical repeater, 3aG4
Optical repeater, 2G4
Optical fiber type multi-point temperature converter,3aG4
Optical fiber type multi-point temperature converter,2G4
Entity, ia IIC (FCX-AII, AIII transmitter can be combined.)
Object
TIIS Intrinsic safety explosion-proofing
Scope of delivery
Main unit, mounting clip
EDS13-18b
Date
Apr. 1, 2011
PWX
Outline diagram (Unit: mm)
Non-hazardous area terminal
4
2
3
1
Hazardous area terminal
25.0
7.5 11.5 7.5
Earth terminal (M4 screw with nut)
1
49.2
61.5
9
2
85.0
93.5
14.2
Mounting clip
plug-in hole
Mounting method
(supplied mounting clip used)
95
M4 screw
Use of combination instrument
Hazardous area
+
Intrinsic
safety
–
instrument
Non-hazardous area
Safety barrier
3
PWX
4
1
2
Class-1 grounding
General-use
instrument
Operating voltage
should be 250V AC/250V DC
or less.
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan