FUJI EDS9-52

FFI SYSTEM
OPTICAL-PNEUMATIC CONVERTER
DATA SHEET
ZLD···3
The optical-pneumatic converter is used for converting
optical signal to pneumatic signal proportional with the set
value given from master station in order to operate a pneumatic final control element such as pneumatic positioner
or diaphragm valve.
A fiber optical cable used for the signal transmission line
forms an optical field instrumentation system together with
an optical star coupler and a master station.
FEATURES
1. Resistive to noise and lightning
Optical signal ensures a reliable signal transmission,
because it is not affected by external noise and inductive lightning. Use of a nonmetallic optical (fiber) cable
prevents propagation of inductive lightning through the
cable, so a signal transmission immune to lightning can
be realized.
2. Reliability due to redundant configuration
Host system can be duplicated by using two optical cable
trunk lines (between an optical star coupler and host
system). This enhances reliability of users’ systems.
3. Intrinsic safety type explosion-proof
Each equipment with a built-in battery can be constructed
so as to be an intrinsic safety type individually (intrinsic
safety type barrier unnecessary).
SPECIFICATIONS
Functional specifications
Input:
Optical digital signal
Output:
Pneumatic signal within 20 to 100 kPa
Air supply pressure:
140 kPa
Power supply: Built-in lithium battery (2 cells), expected
life; about 3 years/cell
Explosion-proof: Intrinsic safety type, JIS ib IIC T3
Self-diagnosis: Displayed on indication unit (option) and
transmitted to master station.
Item
Host system Indication unit
Deviation error
Detecting unit failure
Amplifier abnormal
Battery voltage
Battery voltage low alarm
–
Remote control function
(Items readable and setting from hand-held communicator)
Item
Reading Setting
Output value
Control constant
Battery voltage
Emergency operation
○
○
○
○
–
○
–
○
Error indication
○
–
Description
Read-back value
P and I parameters
Voltage of built-in battery
Direction of emergency
operation
Detector error and
deviation error
Emergency operation:
Operating direction of output air pressure
when input turns off.
Selectable among the following operations. ... Refer to CODE SYMBOLS.
• Holding of the latest normal value
• Scale out below 0% (5 kPa or less)
• Scale out above 100% (120 kPa or
more)
Optical cable:
Code set type, silica fiber ... core/clad diameter 100/140 µm
Optical connector:
FC connector
Transmission distance:
1.5 km max. (when transmission loss of
optical cable is 4 dB/km)
Ambient temperature:
-20 to +60°C
-10 to +60°C for intrinsic safety explosion-proof type
Storage temperature:
-30 to +70°C
EDS9-52
Date
May. 20, 2004
ZLD···3
CODE SYMBOLS
Performance specifications
Accuracy rating: ± 0.5% of full scale (Output ripple about
± 0.1%)
Response speed:3 sec or less (90% response time at load
capacity 0.5 L)
Input/output characteristic:
Linear
Air consumption:
Standard (output constant); 8 NL/min
Maximum (output under sudden change);
60 NL/min
Physical specifications
Environmental protection:
JIS C0920 splash-proof type (equivalent
to IEC IP54)
Air piping connection:
Rc 1/4 or 1/4-18NPT
Optical cable connection:
G1/2 or 1/2 -14NPT
Mounting method:
Mounted on horizontal or vertical 50A (2B)
pipe with U-bolt
Finish:
Epoxy-polyurethane double coat,
Color: silver (blue for amplifier case cover)
Mass:
Approx. 5.3 kg
External dimensions:
See OUTLINE DIAGRAM.
Optional specifications
Indication unit: 5-digit LCD indication, % or real scale
indication (as specified by code symbol)
SYSTEM BLOCK DIAGRAM
Host system
Master station
Control room
Star coupler
Field
Pneumatic final control element
P/P
O/P
SUP
SUP
2
Optical-pneumatic
converter ZLD
1 2 3 4 5 6 7 8
Z LD 1 F 3
9 10 11
Description
Output signal/supply pressure (4th digit)
20 to 100 kPa/140 kPa
1
Air piping connection/
cable lead-in port (5th digit)
Rc1/4 / G1/2
1/4-18NPT / 1/2-14NPT
S
T
Indicator (7th digit)
Not provided
Digital, % indication
Digital, real scale indication
A
L
P
Explosion-proof (9th digit)
Non-explosion proof
Intrinsic safety, JIS
A
G
Emergency operation
(when input turns off)(10th digit)
Holding of the latest normal value
Scale out below 0%
Scale out above 100%
A
B
C
Y
A
Air set (11th digit)
Without
With air set
OUTLINE DIAGRAM
ZLD1
(Unit : mm)
3-
Y
225
Mounting pipe
JIS 50A (2B)
64.5
108
70
91
U-bolt
(M8)
191
130
214
SUP
OUT
25
Indicator (option)
27
64
Pressure gauge (output)
B
39
47
2 air piping connections
Optical cable lead-in port
15
3
ø15
D
Type
ZLD1S
ZLD1T
Air piping connections
Rc 1/4
1/4-18NPT
Optical cable lead-in port D
G 1/2
1/2-14NPT
Details of “B”
3
ZLD···3
SCOPE OF DELIVERY
Instrument body and pipe fixture
ORDERING INFORMATION
1. Model type
2. Indication scale for real scale specification
3. Others
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan
http://www.fesys.co.jp/eng
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http: //www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan