FUJI EDS25-1A

Optical Fieldbus System
System Composition Devices
DATA SHEET
Fieldbus is used for digital transmission of the next generation, which takes over the conventional 4 to 20mA analog current
transmission. The optical fieldbus using optical fiber as a fieldbus signal transmission line, has features of optical transmission
such as noise-resistance and thunder-resistance, in additions to the features of fieldbus.
The optical fieldbus system is composed of field devices, such as a pressure transmitter, a differential pressure transmitter,
temperature transmitter, and optical star coupler for blanching optical signals, and a host control system.
Example of system configuration
(single system)
Fieldbus configuration tool
FOCUS system
(or another manufacture's system)
FOCUS
operator station
Control LAN (Ethernet)
Controller ICS-2000
Electrical fieldbus
Control room
Fieldbus connecting unit
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Field
Optical cable
(optical fieldbus)
Wiring cable
(electrical fieldbus)
Optical star
coupler
Optical fieldbus
Transmission
distance; max.
1.2km
Electrical fieldbus
Electrical fieldbus devices
Optical fieldbus devices
Devices of this data sheet
FEATURES
Common specifications for system
1. Noise-resistance, thunder-resistance
Regulations:
Specifications of Fieldbus Foundation
Transmission speed:
31.25kbps
Transmission cycle (macro-cycle):
Standard; 1sec (400ms, min.)
Optical cable:
Composite cord, non-metallic cable
Silica fiber... Core/cladding dia. 100/
140µm or PCF fiber ... Core/cladding dia.
200/230µm
Optical connector:
FC connector or ST connector
Transmission distance:
Silica; 1.2 km (at transmission loss of optical cable, 4dB/km)
PCF; 0.7km (at transmission loss of optical
cable, 6dB/km)
Ambient temperature:
Silica; -30 to +70˚C, PCF: -20 to +60˚C, as
noted in specifications for each devices
Number of units connected:
Up to 16 units including host and field devices (for 1 unit of star coupler)
Optical signals are free from effects of external noise and
inductive thunder, providing highly reliable transmission.
The use of non-metallic cables eliminates the propagation
of inductive thunder, ensuring excellent thunder-proof
transmission.
2. Reliability with redundancy
Duplex host devices are available by using 2 optical cables
(between star coupler and control room) to improve the
system reliability.
3. Intrinsic safety explosion-proof
Built-in power (battery) devices can be designed for intrinsic safety explosion-proof (intrinsic safety barrier is not required).
Restriction of current flowing into the signal bus need not
be taken into account, so any number of devices can be
connected to one bus.
EDS25-1a
Date
Nov. 24, 1999
Optical fieldbus equipment
Contents
1. FFX-P series transmitter ................................................................................................................... 3
1)
Pressure transmitter
Type: FBB
2)
Absolute pressure transmitter
Type: FBH
3)
Differential pressure/flow transmitter
Type: FFG
4)
Remote seal type pressure transmitter
Type: FBF
5)
Remote seal type differential pressure transmitter
Type FFH
6)
Level transmitter
Type: FPL
2. FFX-T series temperature transmitter .......................................................................................... 22
1)
Temperature transmitter (integrated type)
Type: FUP
2)
Temperature transmitter (separated type)
Type: FUT
2
3. FFX-T series multi-point temperature converter
Type FRM ................................. 27
4. FFX-Z series optical-pneumatic converter
Type: ZLK ................................. 30
5. Optical star coupler
Type FXB .................................. 33
Optical fieldbus equipment
FFX-P SERIES TRANSMITTERS
DATA SHEET
These transmitters are capacitance type high accuracy transmitters used for measuring the pressure, etc. of various fluids. The
transmission unit incorporates a microprocessor for digitizing signals, thereby achieving
a high accuracy and an intelligent transmitter.
The signal transmission path adopts an optical fiber and composes an optical fieldbus system in combination with an optical star
coupler and host system.
Model Configuration
Absolute pressure transmitter (type: FBH)
Pressure transmitter (type: FBB)
Reference page
Reference page
Tr-2
Common specifications
Individual specifications
Tr-3
Individual specifications
Tr-3
Code symbols
Tr-6
Code symbols
Tr-7
Outline diagram
Tr-13
Outline diagram
Tr-14
Common specifications
Differential pressure/flow transmitter (type: FFG)
Tr-2
Remote seal type pressure transmitter (type: FBF)
Reference page
Reference page
Common specifications
Tr-2
Common specifications
Tr-2
Individual specifications
Tr-3
Individual specifications
Tr-4
Code symbols
Tr-8
Code symbols
Tr-10
Outline diagram
Tr-15
Outline diagram
Tr-16
Remote seal type differential pressure transmitter (type: FFH) Level transmitter (type: FPL)
Reference page
Reference page
Common specifications
Tr-2
Common specifications
Individual specifications
Tr-4
Individual specifications
Tr-4
Code symbols
Tr-11
Code symbols
Tr-12
Outline diagram
Tr-18
Outline diagram
Tr-19
(Tr-1)
Tr-2
3
FFX-P series transmitter
Optical fieldbus equipment
SPECIFICATIONS
(1) Common specifications
Structure and Material
Function and Performance
• Service:
• Output:
Liquid, gas or vapor
Optical digital signal, Fieldbus
Foundamation specification
• Power supply: Built-in lithium battery
Service life: Approx. 2 years under the
following conditions
 Macro cycle; 1 sec

 Status read cycle; 4 sec 


 Token go-round; 0.25 sec 
 Voltage read cycle; 1 hr 
• Explosion protection:
Intrinsic safety type, JIS ib II C T3 (under
application)
CENELEC ib II C T4 (under application)
• Ambient temperature:
-30 to +70˚C
-10 to +60˚C for intrinsic safety type
-10 to +60˚C for fluorinated oil specification
• Storage temperature:
-40 to +80˚C
• Ambient humidity:
95% RH max.
• Self-diagnosis: Display on indicator and transmission to
host system
Item
Host system
• Casing structure:
Immersion-proof type JIS C 0920
(IEC IP67, NEMA 4X or equivalent)
• Process connections:
Rc1/4 or 1/4-18NPT (as specified in code
symbol)
Screw for oval flange; 7/16-20UNF
• Optical cable connections:
G1/2 or 1/2-14NPT (as specified in code
symbol)
• Mounting:
On 50A (2B) pipe using U-bolt or wall
mounting
• Coating:
Epoxy/polyurethane double-coating
Color; silver (Case cover is blue.)
• External dimensions:
Entered in outline diagram.
• Material:
Refer to code symbols.
Optional Specifications
• Indicator:
5-digit LCD, % or real-scale indication (as
specified in code symbol)
Operating temperature range; -20 to
+70˚C
• Oxygen no-oil treatment:

Fluorinated oil filled in, 
process wetted parts 

cleaned by degreasing  Varies with ma terial. So refer to
• For chlorine measurement:

Fluorinated oil filled in  code symbols.

• NACE specification:
Treatment against H2S 

complying with NACE 

specification
Indicator
Measuring range error
Detection unit error
Amplifier error
Battery voltage
—
Battery voltage drop alarm
• Remote setting: The following items can be read and set
from the host system.
Item
Reading
Setting
Tag No.
Serial No.
—
Range limit
—
Measuring range
Damping constant
Low cut point
Unit of measured value
Measured value
—
• Zero point deviation:
Zero point can be shifted within -100 to
+100% of span limit.
• Response time: Same as communication cycle ... at damping 0 (zero)
• Standard:
Fieldbus Foundation specification (basic
device, device type 411, AI function
block)
4
(Tr-2)
FFX-P series transmitter
Optical fieldbus equipment
(2) Individual specifications
Pressure Transmitter
Differential Pressure/Flow Transmitter
• Span, range and overrange limit:
Type
Range limit
[kPa]
• Static pressure span, and overrange limit:
Span limit [kPa]
Min.
Max.
Overrange
limit [kPa]
Type
Static pressure
[kPa]
Span limit [kPa]
Min.
Max.
Overrange
limit [kPa]
±1
FBB
01
-64 to +64
1.6
64
100
FFG
11
-100 to +3200
0.1
1
FBB
02
-100 to +500
12.5
500
1500
FFG
22
-100 to +10000
0.15
6
±6
FBB
03
-100 to +3000
75
3000
9000
FFG
23
0.8
32
± 32
FBB
04
-100 to +10000
250
10000
15000
FFG
24
1.6
64
± 64
FBB
05
-100 to +50000
1250
50000
75000
FFG
25
3.25
130
± 130
FFG
26
12.5
500
± 500
FFG
33
0.8
32
± 32
FFG
34
1.6
64
± 64
FFG
35
3.25
130
± 130
FFG
36
12.5
500
± 500
FFG
38
75
3000
± 3000
FFG
43
0.8
32
FFG
44
1.6
64
± 64
FFG
45
3.25
130
± 130
FFG
46
12.5
500
± 500
FFG
47
50
2000
± 2000
• Process temperature and negative pressure tolerance limit:
(For details, see Fig. 1.)
Filled oil
13th code
Y.G.N
W.A.D
Process
temperature
-40 to +120˚C
-20 to +80˚C
Negative pressure
tolerance limit
2.7 kPa abs
Atmospheric pressure
Silicone oil
Fluorinated oil
Silicone oil
R
-15 to +120˚C
2.7 kPa abs
• Accuracy rating:• 0.1 x URL min.; ± 0.1%
• Below 0.1 x URL;
± (0.05 + 0.005 x URL/CR)%
URL; Upper range limit, CR; Calibration
range
• Temperature effect:
Zero shift; ± (0.2 + 0.05 x URL/CR)%/55˚C
Total effect;
± (0.25 + 0.05 x URL/CR)%/55˚C
Note) Double the effects for material
code (7th digit in code symbols) other than
V and W.
• Overrange effect:
Zero shift at URL
± 0.2%/overrange limit
• Mass:
4.5 to 5 kg
Filled oil
Span limit [kPa abs]
Min.
Max.
1
0 to 16
1.6
16
FBH
2
0 to 130
3.25
130
500
FBH
3
0 to 500
12.5
500
1500
FBH
4
0 to 3000
75
3000
9000
± 32
Silicone oil (*1)
Y.G.N
Process
temperature
-40 to +120˚C
Fluorinated oil
Silicone oil
W.A.D
R
-20 to +80˚C
-15 to +120˚C
Negative pressure
tolerance limit
2.7 kPa abs
Atmospheric pressure
2.7 kPa abs
47 cannot be used at a
• Accuracy rating:Linear output
• 0.1 x URL min.; ± 0.1%
• Below 0.1 x URL; ±(0.05 + 0.005 x URL/CR)%
URL; Upper range limit, CR; Calibration
range
Square root output
• 0.1 x URL min.;
Output 50% min. ... ± 0.1%
Output 20% min. and below 50% ...
± 0.25%
Output 10% min. and below 20% ...
± 0.5%
• Below 0.1 x URL;
Output 50% min. ... ± (0.05 + 0.005 x
URL/CR)%
Output 20% min. and below 50% ...
± 2.5 x (0.05 + 0.005 x URL/CR)%
Output 10% min. and below 20% ... ± 5 x
(0.05 + 0.005 x URL/CR)%
• Temperature effect:
Overrange
limit [kPa]
FBH
13th code
Note(*1): Types FFG 38 and FFG
negative pressure.
• Span, range and overrange limit:
Range limit
[kPa abs]
-100 to +42000
• Process temperature and negative pressure tolerance limit:
(For details, see Fig. 1.)
Absolute Pressure Transmitter
Type
-100 to +16000
500
• Process temperature and negative pressure tolerance limit:
Process temperature; -40 to +85˚C
Negative pressure; Depends on measuring range.
• Accuracy rating:• 0.1 x URL min.; ± 0.2%
• Below 0.1 x URL; ± (0.1 + 0.01 x URL/
CR)%
URL; Upper range limit, CR; Calibration
range
• Temperature effect:
Zero shift; ± (0.25 + 0.2 x URL/CR)%/55˚C
Total effect; ± (0.3 + 0.2 x URL/CR)%/55˚C
Note) Double the effects for material
code (7th digit in code symbols) other than
V and W.
• Overrange effect: Zero shift at URL
± 0.2% overrange limit
• Mass:
4.5 kg
Linear output
URL; 32 kPa min.
Zero shift;
± (0.2 + 0.05 x
Square root output
± (0.5 + 0.125 x
URL/CR)%/55˚C
URL/CR)%/55˚C
Total effect;
± (0.25 + 0.05 x
URL/CR)%/55˚C
URL; 1 kPa,
6 kPa
Zero shift;
± (0.25 + 0.2 x
URL/CR)%/55˚C
± (0.6 + 0.5 x
URL/CR)%/55˚C
Total effect;
± (0.3 + 0.2 x
URL/CR)%/55˚C
Note 1
Change at 20% point
Note 1; Double the effects for material code (7th digit in
code symbols) other than V and W.
(Tr-3)
5
FFX-P series transmitter
Optical fieldbus equipment
• Overrange and static pressure effects:
Overrange effect: Zero shift at URL (linear
output)
URL; 1, 6kPa...± 0.3%/1, 3.2MPa
URL; 32kPa... ± 0.3%/10, 16MPa,
± 0.5%/42MPa,
Note; Double the effects for material
code (7th digit in code symbols) other
than V and W.
Static pressure effect (linear output)
URL; 1, 6kPa
Remote Seal Type Differential Pressure
Transmitter and Level Transmitter
• Span, range and overrange limit:
Level transmitter (FPL), remote seal type differential pressure transmitter (FFH)
Type
URL; 32kPa ~
FPL
3 Flange rating
FFH
3 pressure
FPL
4
Zero
± 0.2%/ 1, 3.2MPa
± 0.1%/ 10MPa
FFH
4
Span
-0.15± 0.15%/3.2MPa
-0.15± 0.15%/10MPa
FPL
5
FFH
5
FPL
6
FFH
6
• Mass:
5.3 to 5.5 kg
Remote Seal Type Pressure Transmitter
Type
Range limit
[kPa]
Span limit [kPa]
Filled oil
Overrange
Min.
Max.
limit [kPa]
FBF
01
Flange rating
1.6
64
100
FBF
02
pressure
12.5
500
1500
FBF
03
75
3000
4500
FBF
04
250
10000
15000
FBF
05
1250
50000
75000
Fluorinated oil
Silicone oil
• Process temperature and negative pressure tolerance limit:
Filled oil
Fluorinated oil
Silicone oil
13th code
Span limit [kPa]
Min.
Max.
Overrange
limit [kPa]
0.8
32
± 32
1.6
64
± 64
3.25
130
± 130
12.5
500
± 500
• Process temperature and negative pressure tolerance limit:
• Span, range and overrange limit:
W.A.D
H
Process
temperature
-20 to +120˚C
-15 to +250˚C
J
Y.G
+85 to +300˚C
-40 to +120˚C
S
T
-15 to +250˚C
+85 to +300˚C
See Fig. 2.
K
-15 to +200˚C
0.13 kPa abs
See Fig. 3.
13th code
W.A.D
Process
temperature
-20 to +120˚C
H
J
-15 to +250˚C
+85 to +300˚C
Y.G
S
-40 to +120˚C
-15 to +250˚C
T
K
+85 to +300˚C
-15 to +200˚C
Negative pressure
tolerance limit
Atmospheric pressure
2.7 kPa abs
See Fig. 2.
0.13 kPa abs
See Fig. 3.
• Accuracy rating:• 0.1 x URL min.; ± 0.2%
• Below 0.1 x URL; ± (0.1 + 0.01 x URL/
CR)%
URL; Upper range limit, CR; Calibration
range
• Temperature effect:
Zero shift; ± (0.7 x URL/CR)%/55˚C
Total effect; ± (1.0 x URL/CR)%/55˚C
Notes)1. Level transmitter; Double the effects for material code (7th digit
in code symbols) other than V
and W.
2. Remote seal type differential
pressure transmitter; Double the
effects for material code (7th
digit in code symbols) other than
W, A, B, C and D.
• Overrange effect:
Zero shift at URL
± 0.3%/flange rating pressure
Note; Double the effects for material code
(7th digit in code symbols) other than V
(level transmitter), W, A, B, C and D (remote seal type differential transmitter).
• Static pressure effect:
Zero shift; ± 0.2%/1 MPa
Span shift; -0.15 ± 0.15%/flange rating
pressure
Note; Zero shift is a change in URL.
Span shift is a change in CR.
• Mass:
Remote seal type differential pressure
transmitter; 15 to 33 kg
Level transmitter; 10.5 to 19.5 kg
Negative pressure
tolerance limit
Atmospheric pressure
2.7 kPa abs
• Accuracy rating:• 0.1 x URL min.; ± 0.2%
• Below 0.1 x URL;
± (0.1 + 0.01 x URL/CR)%
URL; Upper range limit, CR; Calibration
range
• Temperature effect:
Zero shift; ± (0.7 x URL/CR)%/55˚C
Total effect;
± (1.0 x URL/CR)%/55˚C
Note) Double the effects for material
code (7th digit in code symbols) other than
W, A, B and C.
• Overrange effect:
Zero shift at URL
± 0.2%/flange rating pressure
• Mass:
10.5 to 13.5 kg
6
Range limit
[kPa]
(Tr-4)
FFX-P series transmitter
Optical fieldbus equipment
[kPa abs]
Filled fluid: Silicone oil (code Y, G, N)
Filled fluid: Silicone oil (code K)
Filled fluid: Silicone oil (code R)
Operating pressure
[kPa abs]
Operating pressure
101
53.3
Operating area
4
101
Operating area
Nonoperating
area
0.27
0.13
2.7
–15
Non-operating area
–40 –15
60 85 120 [°C]
100
Process temperature
200
[°C]
Fig. 3 Relation between process temperature
and operating pressure (remote seal type
pressure, remote seal type differential
pressure and level transmitters)
Process temperature
Fig. 1 Relation between process temperature
and operating pressure (pressure and
differential pressure/flow transmitters)
Filled fluid: Silicone oil (code Y, G)
[kPa abs]
Filled fluid: Silicone oil (code S)
Filled fluid: Silicone oil (code T)
Operating pressure
101
53.3
Operating area
13.3
2.7
Non-operating area
–40 –15
60 85 120
200 230250
Process temperature
300
[°C]
Fig. 2 Relation between process temperature
and operating pressure (remote seal type
pressure, remote seal type differential
pressure and level transmitters)
SCOPE OF DELIVERY
Transmitter main frame and bracket for pipe mounting (as
specified)
ACCESSORIES
• Oval flange:
Used as a connection flange of pressure
leading pipe connection port.
For details, refer to DATA SHEET (EDS610) of the oval flange.
• Equalizing valve: Refer to DATA SHEET (EDS6-10).
(Tr-5)
7
FFX-P series transmitter
Optical fieldbus equipment
CODE SYMBOLS
1) Pressure transmitter
1 2 3 4 5 6 7 8
FBB
0
9 10 11 12 13
1 -
14 15
-
Description
Connections (4th code)
Process connection
Opt.cable connection
Rc1/4
G1/2
1/4-18NPT
1/2-14NPT
S
T
Measurement span (6th code)
1.6........... 64kPa
12.5....... 500kPa
7.5....... 3000kPa
250.... 10000kPa
1250.. 50000kPa
1
2
3
4
5
Material (7th code)
Process cover
Diaphragm
SCS14
SUS316L
SCS14
Hastelloy C
SCS14
Monel
SCS14
Tantalum
Hastelloy C lining Hastelloy C
Monel lining
Monel
Tantalum lining
Tantalum
V
H
M
T
B
L
U
Indicator (9th code)
None
Digital, % indication
Digital, actual scale indication
A
L
P
Explosion-proof (10th code)
None (for ordinary locations)
JIS, intrinsic safety (under application)
CENELEC, intrinsic safety (under application)
A
G
K
Side vent/drain and mounting bracket (11th code)
Side vent/drain Mounting bracket
None
None
None
Yes (stainless steel)
Yes
Except when
None
Yes
7th code is B, L or U
Yes (stainless steel)
A
C
D
F
Optical connector (12th code)
FC type
ST type
F
S
Treatment and filled fluid (13th code)
Treatment
Filled fluid
None
Silicone oil
None
Fluorinated oil
Degreasing
Silicone oil
Oxygen no-oil treatment Fluorinated oil ... Only for 7th code V
Chlorine service
Fluorinated oil ... Except when 7th code is V, M or L
NACE specification
Silicone oil ... Except when 6th code is 5 or 7th code is T or U
None
Silicone oil (for vacuum)
Y
W
G
A
D
N
R
O-ring material (for process cover)(14th code)
Viton
Teflon
Square Teflon.... Except when 7th code is B, L or U
A
B
C
C
D
E
F
8
Other wetted parts
SUS316
Hastelloy C
Monel
Tantalum
Except when
Hastelloy C
6th code is 5
Monel
Tantalum
Bolt/nut (15th code)
NACE bolt/nut (ASTM A193 B7M/ A194 2HM
Except when
NACE bolt/nut (ASTM A320 L7M/ A194 2HM
6th code is 5
SUS304/ SUS304... (For general application)
SUS630/ SUS304... Specify when 6th code is 5.
(Tr-6)
FFX-P series transmitter
Optical fieldbus equipment
CODE SYMBOLS
2) Absolute pressure transmitter
1 2 3 4 5 6 7 8
F BH
0
9 10 11 12 13
1 -
14 15
-
Description
Connections (4th code)
Process connection
Opt.cable connection
Rc1/4
G1/2
1/4-18NPT
1/2-14NPT
S
T
Measurement span (6th code)
1.6........... 64kPa abs
32.5....... 130kPa abs
12.5....... 500kPa abs
75........ 3000kPa abs
1
2
3
4
Material (7th code)
Process cover
Pressure receiving diaphragm
SCS14
SUS316L
SCS14
Hastelloy C
SCS14
Monel
SCS14
Tantalum
V
H
M
T
Other wetted parts
SUS316
Hastelloy C
Monel
Tantalum...Except when 6th code is 1
Indicator (9th code)
None
Digital, % indication
Digital, actual scale indication
A
L
P
Explosion-proof (10th code)
None (for ordinary locations)
JIS, intrinsic safety (under application)
CENELEC, intrinsic safety (under application)
A
G
K
Side vent/drain and mounting bracket (11th code)
Side vent/drain Mounting bracket
None
None
None
Yes (stainless steel)
Yes
None
Yes
Yes (stainless steel)
A
C
D
F
Optical connector (12th code)
FC type
ST type
F
S
Treatment and filled fluid (13th code)
Treatment
Filled fluid
None
Silicone oil
Degreasing
Silicone oil
NACE specification
Silicone oil ... Except when 7th code is T
Y
G
N
O-ring material (for process cover)(14th code)
Viton
A
C
D
E
Bolt/nut (15th code)
NACE bolt/nut (ASTM A193 B7M/ A194 2HM)
NACE bolt/nut (ASTM A320 L7M/ A194 2HM)
SUS304/ SUS304... (For general application)
(Tr-7)
9
FFX-P series transmitter
Optical fieldbus equipment
CODE SYMBOLS
3) Differential pressure/flow transmitter
1 2 3 4 5 6 7 8
F FG
9 10 11 12 13
1 -
S
T
1
2
3
3
3
3
3
4
4
4
4
4
2
2
2
2
14 15
-
Description
Connections (4th code)
Process connection
Opt. cable connection
Rc1/4
G1/2
1/4-18NPT
1/2-14NPT
Static pressure and measurement span (5th and 6th codes)
Static pressure
Measurement span
-0.1~+3.2 MPa
0.1.......... 1 kPa
-0.1~+10 MPa
0.15........ 6 kPa
-0.1~+3.2 MPa
0.8........ 32 kPa
1.6........ 64 kPa
3.25.... 130 kPa
12.5........ 500 kPa
75........... 3000 kPa
-0.1~+4.2 MPa
0.8.......... 32 kPa
1.6.......... 64 kPa
3.25...... 130 kPa
12.5...... 500 kPa
50....... 2000 kPa
-0.1~+10 MPa
0.8.......... 32 kPa
1.6.......... 64 kPa
For material codes B, L and U 3.25...... 130 kPa
12.5...... 500 kPa
1
2
3
4
5
6
8
3
4
5
6
7
3
4
5
6
Material (7th code)
Process cover
Diaphragm
V
SCS14 or SUS316
SUS316L
Other wetted
parts
SUS316
H
SCS14 or SUS316
Hastelloy C
Hastelloy C
M
SCS14 or SUS316
Monel
Monel
T
W
B
L
U
SCS14 or SUS316
SCS14 or SUS316
Hastelloy C lining
Monel lining
Tantalum lining
Tantalum
Hastelloy C
Hastelloy C
Monel
Tantalum
Tantalum
SUS316
Hastelloy C
Monel
Tantalum
Indicator and output (9th code)
Indicator
Output
None
Linear
None
Square root
Digital, % indication
Linear
Digital, actual scale indication Linear
Digital, % indication
Square root
Digital, actual scale indication Square root
V
A
L
P
Q
S
A
G
K
10
Explosion-proof (10th code)
None (for ordinary locations)
JIS, intrinsic safety (under application)
CENELEC, intrinsic safety (under application)
(Tr-8)
Application
(5/6th codes)
11, 22, 33, 34, 35, 43,
44, 45
11, 22, 33, 34, 35, 36,
43, 44, 45, 46
33, 34, 35, 36, 43, 44,
45, 46
33, 34, 35, 36
36, 38, 46, 47
23, 24, 25, 26
FFX-P series transmitter
Optical fieldbus equipment
CODE SYMBOLS
1 2 3 4 5 6 7 8
F FG
9 10 11 12 13
1 -
14 15
-
Description
Side vent/drain and mounting bracket (11th code)
Side vent/drain
Mounting bracket
None
None
None
Yes (stainless steel)
Except when
Yes
None
7th code is B, L or U
Yes
Yes (stainless steel)
A
C
D
F
Optical connector (12th code)
FC type
ST type
F
S
Treatment and filled fluid (13th code)
Treatment
Filled fluid
None
Silicone oil
None
Fluorinated oil
Degreasing
Silicone oil
Oxygen no-oil treatment Fluorinated oil ... Only for 7th codes V and W
Chlorine service
Fluorinated oil ... Except when 7th code is V, M or L
NACE specification
Silicone oil ... Except when 7th code is T or U
None
Silicone oil (for vacuum)
Y
W
G
A
D
N
R
O-ring material (for process cover) (14th code)
Viton
Teflon
Square Teflon ... Except when 7th code is B, L or U
A
B
C
C
D
E
F
Bolt/nut (15th code)
NACE bolt/nut (ASTM A193 B7M/ A194 2HM)
Note 1
NACE bolt/nut (ASTM A320 L7M/ A194 2HM)
SUS304/ SUS304..... (For general application) ... Note 2
SUS630/ SUS304..... Specify when 5th code is 3 or 4
Note 1; Static pressure is limited to 10 MPa at maximum.
Note 2; Allowed for 5th codes 1, 2 and 3. However, static pressure is limited
to 10 MPa at maximum.
(Tr-9)
11
FFX-P series transmitter
Optical fieldbus equipment
CODE SYMBOLS
4) Remote seal type pressure transmitter
1 2 3 4 5 6 7 8
FBF
9 10 11 12 13
1 -
Description
Opt.cable connection (4th code)
G1/2
1/2-14NPT
S
T
Flanges (5th code)
Material
0
1
2
3
4
5
P
Q
R
K
SUS304
None (wafer type)
Screw-in type
Rating
JIS 10K 80A
JIS 10K 100A
JIS 30K 50A
ANSI/JPI 150LB 3B
ANSI/JPI 150LB 4B
ANSI/JPI 600LB 2B
For JIS 80A, ANSI/JPI 3B
For JIS 100A, ANSI/JPI 4B
For JIS 50A, ANSI/JPI 2B
JIS G1 thread
Applicable 6th code
1, 2
1, 2
3
1, 2
1, 2
3
1, 2
1, 2
3
4, 5
Measurement span (6th code)
1.6............ 64kPa
12.5........ 500kPa
75......... 3000kPa...... Available only with 7th codes W, A, B, C, D, H, M and T
250..... 10000kPa
Applicable to 5th code K
1250... 50000kPa
Specify W as 7th code.
1
2
3
4
5
Material and diaphragm extension (7th code)
Other wetted parts
Seal diaphragm
SUS316
SUS316L
SUS316L
SUS316
SUS316L
SUS316
SUS316L
SUS316
SUS316L
SUS316
Hastelloy C
Hastelloy C
Hastelloy C
Hastelloy C
Hastelloy C
Hastelloy C
Hastelloy C
Hastelloy C
Hastelloy C
Hastelloy C
Monel
Monel
Tantalum
Tantalum
Titanium
Titanium
Zirconium
Zirconium
W
A
B
C
D
H
F
G
K
L
M
T
P
R
Diaphragm extension (mm)
0
50
When these codes
100 are used in
150 combination with
200 13th code S, T or K,
0
only 5th codes 1, 4
50
and Q are available.
100
150
200
0
0
Available only with 6th code
0
2 and 5th code 0, 3 or P
0
Indicator (9th digit)
None
Digital, % indication
Digital, actual scale indication
A
L
P
Explosion-proof (10th code)
None (for ordinary locations)
JIS, intrinsic safety (under application)
CENELEC, intrinsic safety (under application)
A
G
K
Capillary length (11t code)
1.5m
3m
5m
6m
7m
8m
Available for 5th code 0, 1, 3, 4, P or Q and 13th code Y, W, G, A or D
10m
A
B
G
C
H
J
K
Optical connector (12th code)
FC type
ST type
F
S
Y
W
G
A
D
H
J
S
T
K
Treatment and filled fluid (13th code)
Treatment
Filled fluid
None
Silicone oil
None
Fluorinated oil
Degreasing
Silicone oil
Oxygen no-oil treatment Fluorinated oil ... Available for 7th code W, A, B, C or D
Chlorine service
Fluorinated oil ... Available for 7th code H, F, G, K, L or T
None
Silicone oil (for high temperature) *1
None
Silicone oil (for high temperature)
None
Silicone oil (for high temperature and vacuum)
None
Silicone oil (for high temperature and vacuum) *2
None
Silicone oil (for high temperature and high vacuum)
*1: Available for 6th code 1, 2 or 3 and 7th code W, A, B, C or D
*2: Available for 6th code 2 and 7th code W, A, B, C or D
12
(Tr-10)
FFX-P series transmitter
Optical fieldbus equipment
CODE SYMBOLS
5) Remote seal type differential pressure transmitter
1 2 3 4 5 6 7 8
F FH
9 10 11 12 13
1 -
Description
Opt.cable connection (4th code)
G1/2
1/2-14NPT
S
T
Flanges (5th code)
Material
0
1
2
3
4
5
6
7
P
Q
SUS304
None
(wafer type)
Rating
JIS 10K 80A
JIS 10K 100A
JIS 30K 80A
JIS 30K 100A
ANSI/JPI 150LB 3B
ANSI/JPI 150LB 4B
ANSI/JPI 300LB 3B
ANSI/JPI 300LB 4B
For JIS 80A, ANSI/JPI 3B
For JIS 100A, ANSI/JPI 4B
Measurement span (6th code)
0.8............ 32kPa
1.6............ 64kPa
3.25........ 130kPa
12.5........ 500kPa
3
4
5
6
Material and diaphragm extension (7th code)
Other wetted parts
Seal diaphragm
SUS316
SCS316L
SCS316L
SUS316
SCS316L
SUS316
SCS316L
SUS316
SCS316L
SUS316
Hastelloy C
Hastelloy C
Hastelloy C
Hastelloy C
Hastelloy C
Hastelloy C
Hastelloy C
Hastelloy C
Hastelloy C
Hastelloy C
Monel
Monel
Tantalum
Tantalum
Titanium
Titanium
Zirconium
Zirconium
W
A
B
C
D
H
F
G
K
L
M
T
P
R
Diaphragm extension (mm)
0
50
When these codes
100 are used in
150 combination with
200 13th code S, T or K,
0
only 5th codes 1, 3, 5, 7
50
and Q are available.
100
150
200
0
0
Available only with 5th code
0
0, 2, 4, 6 or P
0
Indicator (9th digit)
None
Digital, % indication
Digital, actual scale indication
A
L
P
Explosion-proof (10th code)
None (for ordinary locations)
JIS, intrinsic safety (under application)
CENELEC, intrinsic safety (under application)
A
G
K
Capillary length (11t code)
1.5m
3m
5m
6m
7m
8m
Available for 13th code Y, W, G, A or D
10m
A
B
G
C
H
J
K
Optical connector (12th code)
FC type
ST type
F
S
Y
W
G
A
D
H
J
S
T
K
Treatment and filled fluid (13th code)
Treatment
Filled fluid
None
Silicone oil
None
Fluorinated oil
Degreasing
Silicone oil
Oxygen no-oil treatment Fluorinated oil ... Available for 7th code W, A, B, C or D
Chlorine service
Fluorinated oil ... Available for 7th code H, F, G, K, L or T
None
Silicone oil (for high temperature)
None
Silicone oil (for high temperature)
None
Silicone oil (for high temperature and vacuum)
*1
None
Silicone oil (for high temperature and vacuum)
None
Silicone oil (for high temperature and high vacuum)
*1: Available for 7th code W, A, B, C or D
(Tr-11)
13
FFX-P series transmitter
Optical fieldbus equipment
CODE SYMBOLS
6) Level transmitter
1 2 3 4 5 6 7 8
FPL
9 10 11 12 13
1 -
Description
Connections (4th code)
Low pressure connection
RC1/4
1/4-18NPT
S
T
Flanges (5th code)
Material
0
1
2
3
4
5
6
7
SUS304
Rating
JIS 10K 80A
JIS 10K 100A
JIS 30K 80A
JIS 30K 100A
ANSI/JPI 150LB 3B
ANSI/JPI 150LB 4B
ANSI/JPI 300LB 3B
ANSI/JPI 300LB 4B
Measurement span (6th code)
0.8............ 32kPa
1.6............ 64kPa
3.25........ 130kPa
12.5........ 500kPa
3
4
5
6
Material (7th code)
High pressure side (flange side)
Diaphragm
Other wetted
part
SCS316L
SUS316
Hastelloy C
Hastelloy C
Monel
Monel
Tantalum
Tantalum
V
H
M
T
Low pressure side
Diaphragm
Process cover
SCS316L.....*1
Hastelloy C
Monel
Tantalum
SCS14
SCS14
SCS14
SCS14
Indicator (9th digit)
None
Digital, % indication
Digital, actual scale indication
A
L
P
Explosion-proof (10th code)
None (for ordinary locations)
JIS, intrinsic safety (under application)
CENELEC, intrinsic safety (under application)
A
G
K
Diaphragm extension (mm)(11th code)
0...... For any 7th code
50
100
7th code V only
150
200
50
100
7th code H only
150
200
Y
A
B
C
D
E
F
G
H
Optical connector (12th code)
FC type
ST type
F
S
Y
W
G
A
D
H
J
S
T
K
Treatment and filled fluid (13th code)
Treatment
Filled fluid
None
Silicone oil
None
Fluorinated oil
Degreasing
Silicone oil
Oxygen no-oil treatment Fluorinated oil ... Available for 7th code V
Chlorine service
Fluorinated oil ... Available for 7th code H or T
None
Silicone oil (for high temperature)
None
Silicone oil (for high temperature)
None
Silicone oil (for high temperature and vacuum)
None
Silicone oil (for high temperature and vacuum)
None
Silicone oil (for high temperature and high vacuum)
*1: Hastelloy C for 6th code 6
*2: Available for 7th code V
14
Opt.cable connection
G1/2
1/2-14NPT
(Tr-12)
*2
FFX-P series transmitter
Optical fieldbus equipment
OUTLINE DIAGRAM (Unit: mm)
1) Pressure transmitter
P
241
80
FBB S 0
T
108
70
V
H
M 1–
T
Mounting pipe
JIS 50A (2B)
A
C
U-bolt
(M8)
70
ø102
225
8
290
54
15
B
Optical cable connection
Indicator (option)
Vent/drain plug
A
Pressure connection
41.3
FBB S 0
T
B
L 1–
U
31 27
47
A
C
4–7/16-20UNF
Screw depth 13
300
41.3
ø102
27
View from arrow P
ø7
54
D
E
A
Pressure connection
2.5
15 3
8
ø15
ø18.5
Details of area B
40
27
47
2–7/16–20UNF
Screw depth 10
Details of area A
ø16
+0.2
+0.1
FBBS
FBBT
D
Rc1/4
1/4–18NPT
E
G1/2
1/2–14NPT
ø4
ø2
Type
0
- 0.1
1
ø12
Details of area A
(Tr-13)
15
FFX-P series transmitter
Optical fieldbus equipment
OUTLINE DIAGRAM (Unit: mm)
2) Absolute pressure transmitter
FBH S 0
T
P
V
H
M 1–
T
A
C
241
Mounting pipe
JIS 50A (2B)
80
108
70
U-bolt
(M8)
70
ø102
225
8
290
54
15
B
Optical cable connection
Indicator (option)
Vent/drain plug
31 27
47
41.3
A
Pressure connection
4–7/16-20UNF
Screw depth 13
27
View from arrow P
ø7
Details of area B
16
D
2.5
3
15
E
Type
FBHS
FBHT
D
Rc1/4
1/4–18NPT
E
G1/2
1/2–14NPT
8
ø15
ø18.5
Details of area A
(Tr-14)
FFX-P series transmitter
Optical fieldbus equipment
OUTLINE DIAGRAM (Unit: mm)
3) Differential pressure/flow transmitter
P
FFG S
T
241
80
108
70
V
H
M 1–
T
W
A
C
Mounting pipe
JIS 50A (2B)
U-bolt
(M8)
70
ø102
225
8
290
54
15
B
Optical cable connection
Indicator (option)
Vent/drain plug
A
Low pressure
connection
A
High pressure
connection
41.3
LH
B
L 1–
U
FFG S
T
37 27
47
A
C
A
Pressure connection
8–7/16-20UNF
Screw depth 13
300
41.3
27
28
ø102
View from arrow P
ø7
3
8
ø15
E
2.5
15
54
D
4-7/16-20UNF
Screw depth 10
ø18.5
Details of area B
40
Vent/drain plug
Details of area A
27
47
ø16
D
Rc1/4
1/4–18NPT
E
G1/2
1/2–14NPT
+0.2
ø12 +0.1
ø4
0
FFGT
2 –0.1
FFGS
1
Type
Details of area A
(Tr-15)
17
FFX-P series transmitter
Optical fieldbus equipment
OUTLINE DIAGRAM (Unit: mm)
4) Remote seal type pressure transmitter
241
80
108
70
1
225
8
131
0
1 1
S
2
FBF
T 3 2
3
4
5
øF
t
70
S
L
20
Mounting pipe
JIS 50A (2B)
Inner diameter
of gasket seat
øK
øJ
øH
U-bolt
(M8)
15
B
Indicator (option)
Optical cable connection
View from arrow Q
Type
FBF * * * W1
FBF * * * H1
FBF * * * M1
FBF * * * T1
FBF * * * P1
FBF * * * R1
FBF * * * A1
FBF * * * F1
FBF * * * B1
FBF * * * G1
FBF * * * C1
FBF * * * K1
FBF * * * D1
FBF * * * L1
ø102
288
Q
54
N-øh
Hole
29 27
47
P 1
FBF S Q 2
T R 3
P
øG
L
Mass (kg)
0
10.5
50
11.5
100
12.5
150
13
200
13.5
1
288
3
15
ø102
E
Type
ø15
FBFS
G1/2
FBFT
1/2-14NPT
54
E
Details of area B
P
29 27
47
2-M6 Depth 9
øJ
øK
t
P
N-øh
FBF * 0 * * 1
185 150 126 100
73
38
116
8-19
JIS-10k-80A
FBF * 1* * 1
210 175 151 103
96
38
141
8-19
JIS-10k-100A
FBF * 2 * * 1
165 130 84
48
42
50
8-19
JIS-30k-50A
FBF * 3* * 1
191 152.5 126 100
73
44
116
4-20
ANSI / JPI 150lb 3B
FBF * 4 * * 1
229 190.5 151 103
96
44
141
8-20
FBF * 5* * 1
165 127 84
48
8-20
Type
øF
øG
øH
52
52
45.5 50
FLANGE
126 100
73 38
116 80A, 3B
ANSI / JPI 150lb 4B
FBF * Q 12 * 1
151 103
96 38
141 100A, 4B
ANSI / JPI 600lb 2B
FBF * R 3 * 1
84
48 45.5 50 50A, 2B
Note) "S" depends on code specification.
18
FLANGE
Type
FBF * P 12 * 1
(Tr-16)
øH
øJ
52
øK
t
P
FFX-P series transmitter
Optical fieldbus equipment
OUTLINE DIAGRAM (Unit: mm)
4) Remote seal type pressure transmitter
FBF S K 4 W1
T 5
241
80
131
108
70
Mounting pipe
JIS 50A (2B)
70
225
8
S
15
B
Indicator (option)
Optical cable connection
View from arrow Q
U-bolt
(M8)
288
Q
15
ø102
3
ø15
-0.1
ø30 -0.2
-0.1
ø23.6 -0.2
E
Details of area B
54
Packing
G1
29 27
47
Type
FBFS
FBFT
2
2
18
53
E
G1/2
1/2-14NPT
Note) "S" depends on code specification.
20
47
100
(Tr-17)
19
FFX-P series transmitter
Optical fieldbus equipment
OUTLINE DIAGRAM (Unit: mm)
5) Remote seal type differential pressure transmitter
Low pressure side
131
S
FFH S
T
0
1
2
3
4
5
6
7
241
80
1
108
70
70
225
8
131
L H
S
øF
15
B
Indicator (option)
Optical cable connection
View from arrow Q
L
20
t
High pressure side
Mounting pipe
JIS 50A (2B)
Inner diameter
of gasket seat
øK
øJ
øH
Type
U-bolt
(M8)
ø15
15
3
FFH * * * W1
FFH * * * H1
FFH * * * M1
FFH * * * T1
FFH * * * P1
FFH * * * R1
FFH * * * A1
FFH * * * F1
FFH * * * B1
FFH * * * G1
FFH * * * C1
FFH * * * K1
FFH * * * D1
FFH * * * L1
288
ø102
E
Q
Details of area B
54
L
Mass (kg)
0
15 to 20.5
50
16 to 31.5
100
16.5 to 32
150
17 to 32.5
200
17.5 to 33
Note) "S" depends on code specification.
N- øh
Hole
29 27
47
P
øG
FFH S P
TQ
1
øG
øH
øJ
øK
t
P
N-øh
FLANGE
FFH * 0 * * 1
FFH * 1 * * 1
FFH * 2 * * 1
FFH * 3 * * 1
FFH * 4 * * 1
FFH * 5 * * 1
FFH * 6 * * 1
FFH * 7 * * 1
185
210
210
240
191
229
210
254
150
175
170
195
152.5
190.5
168
200
126
151
126
151
126
151
126
151
100
103
100
103
100
103
100
103
73
96
73
96
73
96
73
96
38
38
48
52
44
44
49
52
116
141
116
141
116
141
116
141
8-19
8-19
8-23
8-25
4-20
8-20
8-23
8-23
JIS-10k-80A
JIS-10k-100A
JIS-30k-80A
JIS-30k-100A
ANSI / JPI 150lb 3B
ANSI / JPI 150lb 4B
ANSI / JPI 300lb 3B
ANSI / JPI 300lb 4B
54
29 27
47
P
øF
ø102
288
Type
Type
20
E
FFHS
G1/2
FFHT
1/2-14NPT
2-M6 Depth9
(Tr-18)
FLANGE
Type
øH
øJ
øK
FFH * P * * 1
126
100
73
116 For JIS-80A, ANSI/JPI 3B
FFH * Q * * 1
151
103
96
141 For JIS-100A, ANSI/JPI 4B
P
FFX-P series transmitter
Optical fieldbus equipment
OUTLINE DIAGRAM (Unit: mm)
6) Level transmitter
1
2
t
L
20
A
Low pressure
connection
øF
øH
øJ
øK
ø102
øG
Q
54
N- øh
Hole
Inner diameter of gasket seat
Vent/drain plug
46.4
27
41.3
ø7
2.5
15
3
8
ø15
D
E
ø18.5
Details of area B
241
126
70
8
Details of area A
Type
FPLS
15
B
Indicator (option)
Optical cable connection
View from arrow Q
D
E
Rc1/4
G1/2
1/4-18NPT 1/2-14NPT
FPLT
øJ
øK
t
N-øh
FPL * 0 * * 1 185 150 126 100
73
38
8-19
JIS-10k-80A
FPL * 1 * * 1 210 175 151 103
96
38
8-19
JIS-10k-100A
FPL * 2 * * 1 210 170 126 100
73
48
8-23
JIS-30k-80A
FPL * 3 * * 1 240 195 151 103
96
52
8-25
JIS-30k-100A
FPL * 4 * * 1 191 152.5 126 100
73
44
4-20
ANSI / JPI 150lb 3B
FPL * 5 * * 1 229 190.5 151 103
96
44
8-20
ANSI / JPI 150lb 4B
FPL * 6 * * 1 210 168 126 100
73
49
8-23
ANSI / JPI 300lb 3B
FPL * 7 * * 1 254 200 151 103
96
52
8-23
ANSI / JPI 300lb 4B
Type
øF
øG
øH
FLANGE
(Tr-19)
L
1
2
Type
FPL * * * * 1- * * Y 0 365 150
FPL * * * V1- * * A
FPL * * * H1- * * E 50
FPL * * * V1- * * B
FPL * * * H1- * * F 100 359 144
FPL * * * V1- * * C
FPL * * * H1- * * G 150
FPL * * * V1- * * D
FPL * * * H1- * * H 200
Mass (kg)
10.5 to 14
11 to 18
11.5 to 18.5
12 to 19
12.5 to 19.5
21
Optical fieldbus equipment
FFX-T Series Temperature Transmitter
DATA SHEET
This temperature transmitter is equipped with a thermocouple and a platinum resistance bulb for measuring temperatures of various kinds of fluids.
The electronic unit has a built-in micro-processor for processing signals in digital mode to provide highly accurate and intelligent measurements.
The signal transmission line uses optical fiber cables to realize an optical fieldbus system with optical star coupler and
host system.
Composition of models
1) Temperature transmitter (integrated type); Type FUP
2) Temperature transmitter (separated type); Type FUT
Specifications
Functional specifications
• Measured fluid: Liquid, gas, vapor
• Measuring range
Integrated type (FUP) Separated type (FUT)
J Thermocouple
-200 to +400˚C
-200 to +750˚C
E Thermocouple
-200 to +400˚C
-200 to +800˚C
K Thermocouple
-200 to +400˚C
-200 to +1200˚C
R Thermocouple
0 to +1600˚C
T Thermocouple
-200 to +350˚C
Resistance bulb Pt100
Note)
-200 to +400˚C
-200 to +600˚C
When the operating temperature range is not specified at the time of ordering, the transmitter will be
adjusted within the maximum measuring range prior
to delivery.
• Operating pressure:
Flange type...Flange rated pressure
Screw type... 4MPa or less
• Output:
Optical digital signal, specifications of
Fieldbus Foundation
• Burnout:
Previous output is retained at burnout of
sensor. With BAD status
• Explosion-proof:
Intrinsic safety explosion-proof, JIS ib II C
T3 (under application), CENELEC ib II C T4
(under application)
• Zero point deviation:
80% between minimum and maximum
temperatures within measuring range
• Power supply: Built-in lithium battery
Life: About 2 years ... under the following conditions.
 Macro-cycle: 1sec

 Status read cycle; 4sec 


 Token go-round; 0.25sec
 Voltage read cycle; 1hr 
22
• Self-diagnosis: Display on indicator and transmission to
host
Item
Host
Indicator
Measuring range error
Sensor error
Amplifier fault
Battery voltage
—
Battery voltage-drop alarm
• Remote setting: Read-out from hose devices and setting
items
Item
Read-out
Setting
Tag No.
Serial No.
—
Maximum range
—
Measuring range
Damping constant
Unit of process variable
Process variable
—
• Ambient temperature:
-30 to +70˚C
Intrinsic safety explosion-proof; -10 to
+60˚C
• Storage temperature:
-40 to +80˚C
• Ambient humidity:
95%RH or less
• Regulation:
Fieldbus Foundation specifications (basic
device, device type 411, AI function block)
Performance specifications
1. Sensor (for integrated type)
• Accuracy rating:
Thermocouple; JIS C 1604 Class 2
Resistance bulb; JIS C 1604 Class B
• Response time (time constant):
Protective tube, ø4.8mm... About 8sec
Protective tube, ø12mm... About 70sec
FFX-T Series Temperature Transmitter
Optical fieldbus equipment
Relation between measured fluid flow
velocity and insertion length
2. Electronic unit (integrated/separated type)
• Accuracy rating:
FUP
A (integrated type)
FUT
A (separated type)
FUT
B (separated type)
FUP
C (integrated type)
FUT
C (separated type)
FUT
D (separated type)
FUP
E (integrated type)
Sensor
J Thermocouple
J Thermocouple
E Thermocouple
E Thermocouple
K Thermocouple
Temperature
range
Accuracy
rating
-140 to +400˚C
± 0.6˚C
Under. -140˚C *
± 1˚C
-100 to +750˚C
± 1.1˚C
Under. -100˚C *
± 1.9˚C
-200 to +400˚C
± 0.6˚C
-80 to +800˚C
± 1.2˚C
Under. -80˚C *
± 2˚C
-150 to +400˚C
± 0.6˚C
FUT
E (separated type)
Under. -150˚C *
± 1˚C
FUT
F (separated type)
K Thermocouple
0 to +1200˚C
± 1.8˚C
Under. 0˚C *
± 3˚C
FUT
G (separated type)
R Thermocouple
0 to +1600˚C
± 4˚C
FUT
G (separated type)
T Thermocouple
-200 to +350˚C
± 0.8˚C
FUP
J (integrated type)
Pt100
-200 to +400˚C
± 0.6˚C
FUT
L (separated type)
FUT
K (separated type)
-200 to +600˚C
± 0.9˚C
Study the insertion length of the temperature sensor to be
used referring to the relation between the flow velocity and
insertion length shown in Fig. 1.
When inserting the sheath type into flow, a protective tube
should be provided separately.
1300
1000
Insertion length L (mm)
Type
When inserting the protective tube into the fluid piping, the
temperature sensor receives the stress of the flow of fluid,
so the strength of the protective tube to be inserted should
be taken into account.
Water
100
Air
M (separated type)
FUT
N (separated type)
JPt100
-200 to +400˚C
± 0.6˚C
FUT
P (separated type)
JPt100
-200 to +500˚C
± 0.7˚C
Note
1. Accuracy with segmented line compensation
2. Reference junction compensation error not included.
• Reference junction compensation accuracy:
± 1˚C (for thermocouple)
• Ambient temperature effect:
(Variation at -30 to +70˚C)
± 0.5% of Max. measured temperature;
± 1% of the above temperature range
marked "*"
• Wiring resistance:
(For separated type)
Thermocouple: Less than 100Ω, resistance bulb; less than 10Ω
10
0.1
1
10
Flow velocity (m/ S)
100
Fig. 1 Relation between flow velocity and insertion length
(Protective tube, ø12mm)
Option specifications
• Indicator:
5-digit LCD display, % or scale display
Operating temperature range; -20 to +70
˚C
Scope of delivery
Instrument main unit, pipe mounting brackets (for
separated type)
Structure and material
• Casing:
Immersion-proof type, JIS C 0920
(IEC IP67, NEMA4X or equivalent)
• Optical cable connections:
G1/2 or 1/2-14NPT
• Mounting method:
(1) Integrated type (FUP); screw or flange
mounting ... according to code symbols
(2) Separated type (FUT); 50A (2B) pipe
mounting with U-bolt or wall mounting
• Coating:
Epoxy/urethane, double coating
Color; silver (blue for case cover)
• Mass:
(1) Integrated type (FUP); 3 to 5kg,
depending on the length of sensor
(2) Separated type (FUT); about 2.4kg
• Insertion length:
(Length of integrated type sensor)
100 to 2000 mm ... Refer to the code symbols.
• Minimum bending radius:
(Allowable bend of integrated type sensor)
14.4mm ... Sheath type (ø4.8mm) only
• Dimensions:
See outline diagram.
• Material:
(Material of integrated type sensor
protective tube)
SUS304 or SUS316... according to code
symbols
23
FFX-T Series Temperature Transmitter
Optical fieldbus equipment
CODE SYMBOLS
Temperature transmitter (integrated type)
1 2 3 4 5 6 7 8
FUP
9 10 11 12 13
1 -
14
-
Description
Opt. cable connection (4th digit)
G1/2
1/2-14NPT
S
T
Measuring range (5th digit)
J Thermocouple
E Thermocouple
K Thermocouple
3-wire system Pt 100 (1989)
3-wire system Pt 100 (1997)
A
C
E
J
L
Explosion-proof (6th digit)
For general-use (non-explosion-proof)
JIS Intrinsic safety (under application)
CENELEC Intrinsic safety (under application)
A
G
K
Indicator (7th digit)
None
Digital, % display
Digital, actual scale display
A
L
P
Optical connector (9th digit)
FC type
ST type
F
S
Type of protective tube (10th digit)
ø12
ø4.8(sheath type)
A
B
Protective tube material (11th digit)
SUS304 (10th digit B not applicable)
SUS316
S
W
Temperature transmitter (separated type)
1 2 3 4 5 6 7 8
FUT
9
1 -
Description
Opt. cable connection(4th digit)
G1/2
1/2-14NPT
S
T
Input signal, measuring range (5th digit)
J Thermocouple
-200 to 400˚C
J Thermocouple
-200 to 750˚C
E Thermocouple
-200 to 400˚C
E Thermocouple
-200 to 800˚C
K Thermocouple
-200 to 400˚C
K Thermocouple
-200 to 1200˚C
R Thermocouple
0 to 1600˚C
T Thermocouple
-200 to 350˚C
3-wire system Pt 100 (1989)
-200 to 400˚C
3-wire system Pt 100 (1989)
-200 to 600˚C
3-wire system Pt 100 (1997)
-200 to 400˚C
3-wire system Pt 100 (1997)
-200 to 600˚C
3-wire system JPt 100
-200 to 400˚C
3-wire system JPt 100
-200 to 500˚C
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Explosion-proof (6th digit)
For general-use (non-explosion-proof)
JIS Intrinsic safety (under application)
CENELEC Intrinsic safety (under application)
A
G
K
Indicator (7th digit)
None
Digital, % display
Digital, actual scale display
A
L
P
F
S
24
Optical connector (9th digit)
FC type
ST type
-200 to 400˚C
-200 to 400˚C
-200 to 400˚C
-200 to 400˚C
-200 to 400˚C
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
2
Insertion length (mm) (12th, 13th digit)
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700 10th digit A not applicable
1800
1900
2000
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
0
1
2
3
4
5
6
7
8
9
Mounting method (14th digit)
Flange JIS 10K-25A RF
Flange JIS 20K-25A RF
Flange JIS 30K-25A RF
Flange JIS 63K-25A RF
Screw-in G 3/4B
Screw-in R 3/4
Screw-in 3/4-14NPT
Flange ANSI 150LB, 1B
Flange ANSI 300LB, 1B
Flange ANSI 600LB, 1B
FFX-T Series Temperature Transmitter
Optical fieldbus equipment
Outline diagram
1) Temperature transmitter (integrated type)
T
øD1
øD
P
49
ø70
1–
L
222
ø102
FUP
0
17
28
39
A
B
øD2
4- ød
241
1
54
8
80
122
70
T
Flange
Type
D1
D2
d
FUP * * * * 1 - * * * * * 0
JIS 10K-25A RF
14
125
90
19
FUP * * * * 1 - * * * * * 1
JIS 20K-25A RF
16
125
90
19
FUP * * * * 1 - * * * * * 2
JIS 30K-25A RF
20
130
95
19
FUP * * * * 1 - * * * * * 3
JIS 63K-25A RF
27
140
100
23
FUP * * * * 1 - * * * * * 7
ANSI 150lb,1B
14.5
108
79.4
16
FUP * * * * 1 - * * * * * 8
ANSI 300lb,1B
17.5
124
88.9
20
FUP * * * * 1 - * * * * * 9
ANSI 600lb,1B
17.5
124
88.9
20
t
1.0
15
Indicator (option)
B
Optical cable connection
"P" view
1.6
15
3
ø15
A
FUP
1–
"B" detail
A
B
4
5
6
L
223
20
Type
FUPS * * * 1 - * A* * *
A
G1/2
FUPT * * * 1 - * A* * * 1/2-14NPT
D
ø12
L
100 to 1300
(to be specified)
ø4.8 100 to 2000
(sheath (to be specified)
FUPT * * * 1 - * B* * * 1/2-14NPT type)
FUPS * * * 1 - * B* * *
øD
ø102
38
M
54
G1/2
Type
FUP * * * * 1 - * * * * * 4
M
G3/4
FUP * * * * 1 - * * * * * 5
Rc 3/4
FUP * * * * 1 - * * * * * 6
3/4-14NPT
FUP * * * * 1 - * * * * * 4
G3/4
FUP * * * * 1 - * * * * * 5
Rc 3/4
FUP * * * * 1 - * * * * * 6
3/4-14NPT
25
FFX-T Series Temperature Transmitter
Optical fieldbus equipment
Outline diagram
2) Temperature transmitter (separated type)
241
Mounting pipe
JIS 50A (2B)
80
108
70
U-bolt
(M8)
Terminal block
(for sensor connection)
70
ø102
8
225
266
54
15
B
Optical cable connection
Indicator (option)
27
47
3
ø15
15
Type
FUTS
FUTT
G1/2
1/2-14NPT
D
D
"B" detail
6.5
M3 screw
A
+
B
–
B
E
E
Resistance
bulb
Thermocouple
Connection diagram
26
Optical fieldbus equipment
FFX-T Series Multi-point Temperature Converter
DATA SHEET
This multi-point temperature converter is used to receive input signals from a maximum of 8 points of thermocouple or
resistance bulb temperature sensors and convert these
signals into optical digital output signals.
The signal transmitter using optical fiber cables configures an
optical fieldbus system together with an optical star coupler
and a host system.
Specifications
• Burnout:
Functional specifications
• Input:
Thermocouple (J, E, K, R, T type)
Resistance bulb (Pt100, JPt100, 3-wire
system)
• Input points:
8 points, max.
Temperature sensors should be of the
same type and the same range.
• Output:
Optical digital signal, Fieldbus Foundation
specifications
• Power supply: 24V DC (20 to 30V) or 85 to 264V AC 50/
60 Hz, according to code symbols
• Power consumption:
About 1W ... 24V DC
About 5VA ... 85-264V AC
• Explosion-proof: Intrinsic safety explosion-proof,
JIS ib II C T3 (under application)
CENELEC ib II C T4 (under application),
24V DC only
Used in combination with safety barrier
(PWXCA001)
• Zero point deviation:
80% of minimum-maximum temperatures within measuring range
• Remote setting: Read-out from host system and setting
items
Item
Read-out
Setting
Tag No.
Sensor
Temperature range
Accuracy rating
FRM1A
J Thermocouple
-200 to +400˚C
± 1.2˚C
-200 to +75˚C
± 2.2˚C
-200 to +400˚C
± 1.2˚C
-200 to +800˚C
± 2.4˚C
-200 to +600˚C
± 1.8˚C
-200 to +1200˚C
± 3.6˚C
FRM1B
FRM1C
E Thermocouple
FRM1D
FRM1E
K Thermocouple
FRM1F
FRM1G
R Thermocouple
0 to +1600˚C
± 4.8˚C
FRM1H
T Thermocouple
-200 to +350˚C
± 1˚C
FRM1 J
Resistance bulb
-200 to +300˚C
± 0.9˚C
-200 to +600˚C
± 1.8˚C
Pt100
Maximum range
—
FRM1 K
Resistance bulb
FRM1 M
Pt100
Process variable
• Measuring range:
Sensor
J Thermocouple
FRM1B
Temperature range
-200 to +400˚C
-200 to +750˚C
E Thermocouple
FRM1D
FRM1E
Type
FRM1 L
Unit of process variable
FRM1C
• Accuracy rating:
—
Damping constant
FRM1A
Performance specifications
Serial No.
Measuring range
Type
Previous output value is retained at
burnout of sensor. With BAD status
• Self-diagnosis: Detection of faults and transmission to
host system; measurement error, sensor
burnout, amplifier fault
• Ambient temperature:
-30 to +60˚C
Intrinsic safety explosion-proof; -10 to
+60˚C
• Storage temperature:
-40 to +70˚C
• Ambient humidity: 95%RH or less
• Regulation:
Fieldbus Foundation specifications
(Basic device, device type 411, AI function
block)
-200 to +400˚C
-200 to +800˚C
K Thermocouple
FRM1F
-200 to +600˚C
-200 to +1200˚C
FRM1G
R Thermocouple
0 to +1600˚C
FRM1H
T Thermocouple
-200 to +350˚C
FRM1J
Resistance bulb
-200 to +300˚C
FRM1L
Pt100
FRM1K
Resistance bulb
FRM1M
Pt100
-200 to +600˚C
FRM1N
Resistance bulb
-200 to +300˚C
FRM1P
JPt100
-200 to +500˚C
—
FRM1N
Resistance bulb
-200 to +300˚C
± 0.9˚C
FRM1P
JPt100
-200 to +500˚C
± 1.5 ˚C
Note)
Accuracy: With linearize, reference junction compensation error not included
• Reference junction compensation accuracy:
± 1˚C (for thermocouple)
• Measuring cycle:2sec (at any input point)
• Ambient temperature effect:
(Variations at -30 to +60˚C)
± 0.5% of maximum measuring temperature
• Allowable wiring resistance:
Thermocouple; less than 100Ω
Resistance bulb; less than 10Ω
• Insulation:
Fully insulated between input and output
and between output and power supply by
optical interface
Power supply
24V DC
85 to 264V AC
Withstand-voltage
500V AC, 1min
2000V AC, 1min
Insulation resistance
More than 100MΩ at 500V DC
More than 100MΩ at 500V DC
27
FFX-T Series Multi-point Temperature Converter
Structure and materials
• Casing:
Splash-proof type (IEC IP65 or equivalent)
• Optical/power cable connection port:
G1/2 or 1/2-14NPT ... according to code
symbols
• Sensor cable connection port:
G11/4 or 11/4-11NPT ... according to code
symbols
• Mounting method:
Mounting on 50A (2B) pipe with U-bolt or
wall mounting .... according to code symbols
• Mass:
Approx. 9kg
• Coating:
Epoxy/urethane double coating
• Dimensions:
See outline diagram.
Scope of delivery
Instrument main unit, U-bolt (for pipe mounting)
CODE SYMBOLS
1 2 3 4 5 6 7 8
F RM
9 10
1 -
Description
Input points (4th digit)
8 points
1
Measuring range (5th digit)
J Thermocouple
-200 to +400˚C
J Thermocouple
-200 to +750˚C
E Thermocouple
-200 to +400˚C
E Thermocouple
-200 to +800˚C
K Thermocouple
-200 to +600˚C
K Thermocouple
-200 to +1200˚C
R Thermocouple
0 to +1600˚C
T Thermocouple
-200 to +350˚C
Resistance bulb
-200 to +300˚C
3-wire system Pt 100 (1989)
Resistance bulb
-200 to +600˚C
3-wire system Pt 100 (1989)
Resistance bulb
-200 to +300˚C
3-wire system Pt 100 (1997)
Resistance bulb
-200 to +600˚C
3-wire system Pt 100 (1997)
Resistance bulb
-200 to +300˚C
3-wire system JPt 100
Resistance bulb
-200 to +500˚C
3-wire system JPt 100
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Explosion-proof (6th digit)
For general-use (non-explosion-proof)
JIS Intrinsic safety (under application)
*1
CENELEC Intrinsic safety (under application)
A
G
K
Power supply (7th digit)
DC24V
AC85 to 264V 50/60Hz
1
2
Optical connector (9th digit)
FC type
ST type
F
S
A
B
C
D
Cable connection and mounting (10th digit)
Cable connection
Mounting
G1/2, 11/4
Pipe mounting
Wall mounting
G1/2, 11/4
Pipe mounting
NPT1/2, 11/4
Wall mounting
NPT1/2, 11/4
*1: Not applicable for the 7th digit code 2
28
Optical fieldbus equipment
FFX-T Series Multi-point Temperature Converter
Optical fieldbus equipment
Outline diagram
348.5
200
176
70
47.5
414
350
291
440
210
128
series
Multi-point
Temperature Converter
U-bolt
(M8)
4- ø9 (for mounting)
Mounting pipe
JIS 50A (2B)
Blind plug
E
40
50
A
Sensor cable connection
"B" detail
38.5
16.5
16.5
B
Optical cable connection
B
Power cable connection
D
"A" detail
59.5
120.5
120.5
Type
D
E
FRM1 * * *1– * A
B
G11/4
G1/2
C 11/4–11NPT 1/2–14NPT
FRM1 * * *1– * D
29
Optical fieldbus equipment
FFX-Z Series Optical-Pneumatic Converter
DATA SHEET
This instrument is used to convert optical digital signals into
pneumatic signals proportional to the set value given from
the host system for operating pneumatic actuatres such as
pneumatic positioners, diaphragm valves, etc. The adoption
of optical fiber cables to the signal transmission line configures an optical fieldbus system together with an optical star
coupler and a host system.
Specifications
Functional specifications
• Input:
Optical digital signal, Fieldbus Foundation
specifications
• Output:
Pneumatic output; 20 to 100kPa
• Supply air pressure:
140kPa
• Power supply: Built-in lithium battery
Life: About 1.5 years ... under the following conditions
 Macro-cycle; 1sec

 Status read cycle; 4sec 


 Token go-round; 0.25sec 
 Voltage read cycle; 1hr 
• Explosion-proof: Intrinsic safety explosion-proof, JIS ib II C
T3 (under application)
CENELEC ib II C T4 (under application)
• Self-diagnosis: Display on indicator and transmission to
host
Item
Host
Indicator
Detector error
Amplifier fault
Battery voltage
—
Battery voltage-drop alarm
• Remote setting: Read-out from host device and setting
items
Read-out
Setting
Tag No.
Serial No.
—
Output value
—
Unit of output value
Direction of emergency
operation
• Emergency operation:
Direction of output pneumatic operation at
input OFF is selected from the following
3 operations ... according to code symbols.
Previous value hold / Scale-out below 0%
(less than 5kPa) / Scale-out above 100%
(more than 120kPa)
• Ambient temperature:
-20 to +60˚C
Intrinsic safety explosion-proof; -10 to +60˚C
• Storage temperature:
-30 to +70˚C
• Ambient humidity: 95%RH or less
• Regulation:
Fieldbus Foundation specifications
(basic device, device type 411 AO function block)
30
Structure and materials
• Casing:
Measuring range error
Item
Performance specifications
• Accuracy rating:± 0.5%, full scale (output ripple; about
± 0.2%)
• Response speed:
3sec or less (90% response time at load
capacity 0.5R)
• Input/output characteristic:
Linear
• Air consumption:
Steady time (at steady output); 8NR/min
Maximum (at sudden change of output);
60NR/min
Splash-proof type, JIS C 0920 (IEC IP54
or equivalent)
• Air piping connection port:
Rc 1/4 or 1/4 -18NPT (according to code
symbols)
• Optical cable connection:
G1/2 or 1/2-14NPT (according to code symbols)
• Mounting method:
Mounting on 50A (2B) pipe with U-bolt or
wall mounting
• Coating:
Epoxy/urethane double coating, color;
silver (blue for case cover)
• Mass:
Approx. 5.3kg
• Dimensions:
See outline diagram.
Option specifications
• Indicator:
5-digit LCD display, % or actual scale
display
Scope of delivery
Instrument main unit, pipe mounting brackets
FFX-Z Series Optical-Pneumatic Converter
Optical fieldbus equipment
CODE SYMBOLS
1 2 3 4 5 6 7 8
ZLK1
9 10 11
1 -
Description
Output air pressure/ supply pressure (4th digit)
20 to 100kPa / 140kPa
1
Air piping connection/ opt.cable connection (5th digit)
Rc1/4 / G1/2
1/4-18NPT / 1/2-14NPT
S
T
Optical connector (6th digit)
FC connector
ST connector
F
S
Indicator (7th digit)
None
Digital, % display
Digital, actual scale display
A
L
P
Explosion-proof (9th digit)
For general-use (non-explosion-proof)
JIS Intrinsic safety (under application)
CENELEC Intrinsic safety (under application)
A
G
K
Emergency operation (at input OFF) (10th digit)
Previous value hold
Scale-out below 0%
Scale-out above 100%
A
B
C
Y
A
Air set (11th digit)
None
With air regulater
31
FFX-Z Series Optical-Pneumatic Converter
Optical fieldbus equipment
Outline diagram
225
Mounting pipe
JIS 50A (2B)
64.5
108
70
91
U-bolt
(M8)
191
130
214
SUP
OUT
25
Indicator (option)
27
64
Pressure gauge (output)
B
Optical cable connection
39
47
2-air connection port
ø15
Type
ZLK1T
Air connection port
Rc 1/4
1/4-18NPT
Optical cable connection D
G 1/2
1/2-14NPT
15
3
ZLK1S
D
"B" detail
32
Optical fieldbus equipment
Optical Star Coupler
DATA SHEET
This optical star coupler is used to branch optical signals; signals from the host system are branched for transmission to
each field device, while signals from field devices are transmitted to the host system.
It is a reflection type star coupler capable of communications
between field devices, and configures an optical fieldbus system together with field devices and host system.
Specifications
Function/performance
• Number of branches:
16 branches
• Applicable optical fiber:
Silica fiber ... core/cladding dia.
100/140 µm
PCF fiber ... core/cladding dia. 200/230 µm
... according to code symbols
• Applicable optical connector:
FC connector or ST connector ... according to code symbols
• Insertion loss: Silica; Max. 17.5dB
PCF; Max. 18.5dB
• Ambient temperature:
Silica; -30 to +70˚C
PCF; -20 to +60˚C
• Storage temperature:
Silica; -40 to +80˚C
PCF; -30 to +70˚C
• Ambient humidity:
95%RF or less
 Fieldbus Foundation specifications
• Regulation:


 Silica fiber (A1d) device type 421 
PCF fiber (A3C) device type 422
CODE SYMBOLS
1 2 3 4 5 6 7 8
FXB
001
1
2
1
2
Description
Applicable optical fiber
Silica; (100/140 µm)
PCF; (200/230 µm)
Applicable optical connector
FC connector
ST connector
Scope of delivery
Instrument main unit
Structure and materials
• Casing:
Dust-proof type JIS C 0920 ... indoor-use
(IEC IP50 or equivalent)
• Coating:
Melamine coating, color; Munsell
7.5BG6/1.5
• Mounting method:
Wall mounting
• Dimensions:
See outline diagram.
• Mass:
Approx. 1.8kg
• Material:
Case, steel plate
33
Optical star coupler
Optical fieldbus equipment
Outline diagram
FXB
1
2
70
100
165
330
310
290
1.6
30
77
20
13
4– ø9 (for mounting)
34
34
34
34
34
34
34
Receptacle (for FC connector)
FXB
2
9
70
100
165
330
310
290
1.6
30
77
20
13
4– ø9 (for mounting)
34
34
34
34
34
34
34
Receptacle (for ST connector)
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fesys.co.jp/eng
Instrumentation Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http://www.fic-net.jp/eng
Information in this catalog is subject to change without notice.