FUJI EDS9-47C

FFI SYSTEM
OPTICAL-PNEUMATIC CONVERTER
DATA SHEET
ZLD
The optical-pneumatic converter is used to convert optical signal from master station, etc. to pneumatic signal (0.2
to 1.0kg/cm 2 etc.). It is installed in site when operating
pneumatic final control element such as pneumatic positioner
or diaphragm valve.
Signals are processed in digital mode with built-in microcomputer, providing high accuracy and intelligent performance, adoption of piezo-electric element (flapper) has
realized low-power operation.
This instrument is φ6 mm optical fiber cable connection type.
SPECIFICATIONS
Functional specifications
Input signal:
FFI system optical digital signal
Output signal and air supply pressure:
Output signal
Air supply pressure
19.6 to 98.1kPa {0.2 to 1.0kgf/cm2}
39.2 to 196.1kPa {0.4 to 2.0kgf/cm2)
3 to 15psi
3 to 27psi
6 to 30psi
140kPa {1.43kgf/cm2}
240kPa {2.45kgf/cm2}
20± 1psi
32± 1psi
Power supply:
Self-diagnosis:
35± 1psi
Built-in lithium battery (expected life;
about 2 years/cell)
Indication on display unit (option) and
transmission to host master station
Item
HHC, MS
(*1)
Indication
Battery voltage
Converter temperature
Abnormal output (*2)
Battery voltage drop
Notes: *( 1) HHC: Hand-held communication
MS: Master station
( 2) Output overflow or large offset
Emergency operation:
In case of emergency (abnormal input),
output operation can be select from
remote setting unit (HHC, MS), as
specified.
• Output; Less than –10%
• Output; more than +110%
Explosion proofing:
Intrinisically safety (JIS i3nG5, safety
barriers not required)
Ambient temperature:
–20 to +60°C
Storage temperature:
–30 to +70°C
Ambient humidity:
0 to 95% RH
Transmission: Half-duplex bidirectional optical transmission with one-line optical fiber
Transmission distance; 1.2 km max.
(free from effect of noise and surge)
Performance specifications
± 0.5% of full scale
(output ripple; about ± 0.1%)
Response speed:1.5 to 2.5 sec (90% response time at load
capacity 0.5r)
Input/output characteristic:
Linear
Standard air consumption:
12Nr/min.(at air supply pressure 140kPa
{1.43kgf/cm 2})
20Nr/min.(at air supply pressure 240kPa
{2.45kgf/cm 2})
Maximum air flow:
60Nr/min.(at air supply pressure 140kPa
{1.43kgf/cm 2})
80Nr/min.(at air supply pressure 240kPa
{2.45kgf/cm 2})
Accuracy:
EDS9-47c
Date
Jul. 31, 1994
ZLD
CODE SYMBOLS
Structure and material
Enclosure:
JIS C0920, splash-proof type
(equivalent to IEC IP54)
Finish color:
Epoxy/polyurethane double coating, silver
(Case cover ...... blue)
External dimension (HxWxD):
257 x 165 x 220 mm
Mass (weight}
Approx. 5 kg
Mounting method:
Mounted on 50A (2B) pipe with U-bolt
Optical cable and connection:
Fuji’s specified optical cable (supplied as
separate item)
Connection; Optical connector is used.
Air piping connection:
Rc 1/4 (PT 1/4)
1/4-18NPT as specified
1 2 3 4 5 6 7 8
Z LD
9 11 12 13
Description
1 -
Output signal and supply pressure
19.6 to 98.1 kPa {0.2 to 1 .0kgf/cm2}
(140kPa {1.43kgf/cm2})
39.2 to 196.1kPa {0.4 to 2.0kgf/cm2}
(240kPa {2.45kgf/cm2})
3 to 15psi (20psi)
6 to 30psi (35psi)
3 to 27psi (32psi)
1
2
3
4
5
Air piping connection
Rc 1/4 (PT 1/4)
1/4-18 NPT
A
B
6 optical cable protection adapter
With
Without
Notes: 9 mm optical cable connection
type: manufacture non-standard
B
C
Additional specifications
Indicator ....LCD, 4 digits (–10°C to +60°C)
Setting unit .... Pushbutton switch
(4 switches)
Output pressure gauge:
JIS Class-3
Scale; 0 to 2kgf/cm2 or 0 to 3 kgf/cm2
(depends on output range)
Lithium battery (2 batteries, built-in):
Changed over by internal select switch.
[Two batteries can be built into the housing
(standard specification)]
Acid/alkali-proofing:
Mounting U-bolts, nuts and washers;
Stainless steel (304 stainless steel)
Display unit and output pressure
gauge
Output pressure
Display unit
gauge
–
–
–
(output
% scale)
–
(output
% scale)
–
(output
% scale)
(output
% scale)
Display unit:
A
B
C
D
E
F
Explosion-proof specification
Standard (non-explosion-proof)
Intrinsic safety explosion-proof
(JIS i3nG5)
0
1
Emergency operation
(at abnormal input)
Scale out to less than -10%
output
Scale out to more than 110%
output
B
C
Treatment
Standard (non acid/alkali-proof)
Acid/alkali-proof treatment
Y
B
1
2
Number of built-in lithium
batteries
One
Two
SYSTEM CONFIGURATION DIAGRAMS
Pneumatic operation
final element
Optical-pneumatic
converter
ZLD
P/P
Optical star coupler
FXQ
O/P
SUP
8 pcs.
SUP
Master station
OUTLINE DIAGRAM
(Unit:mm)
108
Mounting pipe
(JIS 2B)
70
50
U-bolt (M8)
76
Approx. 245
ø122
112
70
Display unit
(option)
OUT
SUP
Approx. 196
45
62
Optical connector
connection
M42 screw thread
4.8 depth
165
121
76
56
With optical
protection adapter
Adapter 1/2-14NPT
(option)
SCOPE OF DELIVERY
Converter (excluding the optical items), U-bolt.
RELATED DEVICES
•
•
•
•
Optical star couple (Data sheet No. EDS 8–48)
HHC (Data sheet No. EDS 8-44)
Master station (Data sheet No. EDS 11–86)
Option connector, cable
ORDERING INFORMATION
1. Product name
2. Code symbols
3. Other necessary items
Air piping connection
(Rc 1/4)
ZLD
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan
http://www.fesys.co.jp/eng
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http: //www.fic-net.jp/eng
Information in this catalog is subject to change without notice.