FFI SYSTEM OPTICAL-PNEUMATIC CONVERTER DATA SHEET ZLD The optical-pneumatic converter is used to convert optical signal from master station, etc. to pneumatic signal (0.2 to 1.0kg/cm 2 etc.). It is installed in site when operating pneumatic final control element such as pneumatic positioner or diaphragm valve. Signals are processed in digital mode with built-in microcomputer, providing high accuracy and intelligent performance, adoption of piezo-electric element (flapper) has realized low-power operation. This instrument is φ6 mm optical fiber cable connection type. SPECIFICATIONS Functional specifications Input signal: FFI system optical digital signal Output signal and air supply pressure: Output signal Air supply pressure 19.6 to 98.1kPa {0.2 to 1.0kgf/cm2} 39.2 to 196.1kPa {0.4 to 2.0kgf/cm2) 3 to 15psi 3 to 27psi 6 to 30psi 140kPa {1.43kgf/cm2} 240kPa {2.45kgf/cm2} 20± 1psi 32± 1psi Power supply: Self-diagnosis: 35± 1psi Built-in lithium battery (expected life; about 2 years/cell) Indication on display unit (option) and transmission to host master station Item HHC, MS (*1) Indication Battery voltage Converter temperature Abnormal output (*2) Battery voltage drop Notes: *( 1) HHC: Hand-held communication MS: Master station ( 2) Output overflow or large offset Emergency operation: In case of emergency (abnormal input), output operation can be select from remote setting unit (HHC, MS), as specified. • Output; Less than –10% • Output; more than +110% Explosion proofing: Intrinisically safety (JIS i3nG5, safety barriers not required) Ambient temperature: –20 to +60°C Storage temperature: –30 to +70°C Ambient humidity: 0 to 95% RH Transmission: Half-duplex bidirectional optical transmission with one-line optical fiber Transmission distance; 1.2 km max. (free from effect of noise and surge) Performance specifications ± 0.5% of full scale (output ripple; about ± 0.1%) Response speed:1.5 to 2.5 sec (90% response time at load capacity 0.5r) Input/output characteristic: Linear Standard air consumption: 12Nr/min.(at air supply pressure 140kPa {1.43kgf/cm 2}) 20Nr/min.(at air supply pressure 240kPa {2.45kgf/cm 2}) Maximum air flow: 60Nr/min.(at air supply pressure 140kPa {1.43kgf/cm 2}) 80Nr/min.(at air supply pressure 240kPa {2.45kgf/cm 2}) Accuracy: EDS9-47c Date Jul. 31, 1994 ZLD CODE SYMBOLS Structure and material Enclosure: JIS C0920, splash-proof type (equivalent to IEC IP54) Finish color: Epoxy/polyurethane double coating, silver (Case cover ...... blue) External dimension (HxWxD): 257 x 165 x 220 mm Mass (weight} Approx. 5 kg Mounting method: Mounted on 50A (2B) pipe with U-bolt Optical cable and connection: Fuji’s specified optical cable (supplied as separate item) Connection; Optical connector is used. Air piping connection: Rc 1/4 (PT 1/4) 1/4-18NPT as specified 1 2 3 4 5 6 7 8 Z LD 9 11 12 13 Description 1 - Output signal and supply pressure 19.6 to 98.1 kPa {0.2 to 1 .0kgf/cm2} (140kPa {1.43kgf/cm2}) 39.2 to 196.1kPa {0.4 to 2.0kgf/cm2} (240kPa {2.45kgf/cm2}) 3 to 15psi (20psi) 6 to 30psi (35psi) 3 to 27psi (32psi) 1 2 3 4 5 Air piping connection Rc 1/4 (PT 1/4) 1/4-18 NPT A B 6 optical cable protection adapter With Without Notes: 9 mm optical cable connection type: manufacture non-standard B C Additional specifications Indicator ....LCD, 4 digits (–10°C to +60°C) Setting unit .... Pushbutton switch (4 switches) Output pressure gauge: JIS Class-3 Scale; 0 to 2kgf/cm2 or 0 to 3 kgf/cm2 (depends on output range) Lithium battery (2 batteries, built-in): Changed over by internal select switch. [Two batteries can be built into the housing (standard specification)] Acid/alkali-proofing: Mounting U-bolts, nuts and washers; Stainless steel (304 stainless steel) Display unit and output pressure gauge Output pressure Display unit gauge – – – (output % scale) – (output % scale) – (output % scale) (output % scale) Display unit: A B C D E F Explosion-proof specification Standard (non-explosion-proof) Intrinsic safety explosion-proof (JIS i3nG5) 0 1 Emergency operation (at abnormal input) Scale out to less than -10% output Scale out to more than 110% output B C Treatment Standard (non acid/alkali-proof) Acid/alkali-proof treatment Y B 1 2 Number of built-in lithium batteries One Two SYSTEM CONFIGURATION DIAGRAMS Pneumatic operation final element Optical-pneumatic converter ZLD P/P Optical star coupler FXQ O/P SUP 8 pcs. SUP Master station OUTLINE DIAGRAM (Unit:mm) 108 Mounting pipe (JIS 2B) 70 50 U-bolt (M8) 76 Approx. 245 ø122 112 70 Display unit (option) OUT SUP Approx. 196 45 62 Optical connector connection M42 screw thread 4.8 depth 165 121 76 56 With optical protection adapter Adapter 1/2-14NPT (option) SCOPE OF DELIVERY Converter (excluding the optical items), U-bolt. RELATED DEVICES • • • • Optical star couple (Data sheet No. EDS 8–48) HHC (Data sheet No. EDS 8-44) Master station (Data sheet No. EDS 11–86) Option connector, cable ORDERING INFORMATION 1. Product name 2. Code symbols 3. Other necessary items Air piping connection (Rc 1/4) ZLD Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office 6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng Sales Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http: //www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan