FUJI EDS8-47N

HAND-HELD COMMUNICATOR < HHC >
DATA SHEET
FXW
This instrument is a handy type communicator with builtin battery, being designed to perform facilitated communication with operater through use of "smart" type FCX
series transmitter.
FEATURES
1. Simple operation
Adoption of large LCD display (16 digits × 4 lines) as
well as menu assisted software design provides easy-touse communication interface.
2.Application to every type of device
The communicator can be used with any "smart" type of
FCX transmitter, FCX-A/C transmitter, FCX-AX transmitter and FCX-AII/CII, AIII transmitter.
3. On-line operation
The communicator can be operated without interrupting
4 to 20mA DC signal.
4. Full variety of protective functions
The communicator incorporates transmitter diagnostic
function, data-write protection key, battery voltage drop
alarm function, automatic power standby function, etc.
5. Optional printer
Set data can be printed on an optional printer.
SPECIFICATIONS
Standard specifications
Applicable device:"Smart" type FCX series transmitter
FCX transmitter
FCX-A/C transmitter
FCX-AX transmitter
FCX-AII/CII transmitter
FCX-AIII transmitter
Transmission line requirement:
Line length; max 2km (0.75 to 1.25mm2
cable. For 1km and above, twist paircable is recommended.)
Load resistance;
250 to 578Ω in case of FCX-1 transmitter
250 to 600Ω in case of FCX-A/C,
FCX-AX, FCX-AII/CII transmitter
(including cable resistance at 24V DC
In case of FCX-AIII transmitter;
Refer to “Load limitations“.
Load capacitance; 0.22µF max.
Load inductance; 3.3mH max.
Separation from power line; 15cm or more
(avoid parallel wiring.)
Display unit:
LCD, 16 digits × 4 lines
Operating unit: Flat keys (32 keys), power switch, set
value protection key switch
Power source: Built-in nickel-cadmium battery
Battery life:
24 hours (without option under standard
conditions after full charge)
Charger power source:
100, 115, 230V ±10% AC, 50/60Hz (as
specified)
Charging time: 5 hours
Printer (option): Printing of 24 digits of each remote item
Ambient temperature:
-10 to +50°C
Storage temperature:
-20 to +60°C
Ambient humidity:
90% RH or less
Hazardous locations:
Designed to meet international intrinsic
safety standards. Applications have
been submitted for the following. (In
case of without printer only)
Authorities
ATEX
EEx ia IIC T3
EMC Comformity:
EN61326 Functional specifications
Remote function:See the next page.
Power alarm function:
Battery voltage drop is detected and
indicated by lamp flickering on display
unit (Batt ALM).
Set value protective function:
Set value can be changed by using key
switch
Automatic power standby function:
HHC automatically enters into standby
mode when key is not accessed for
more than 10 minutes (data measurement only).
EDS8-47n
Date
Apr. 1, 2011
FXW
Physical specifications
Material: Polycarbonate
Color:
Gray
Dimensions (H x W x D):
55 x 98 x 223mm (without printer)
Mass: Approx. 500g (without printer)
Remote functions
Items
Display
Set
Tag No.
v
v
Model No.
v
v
Serial No. & Software Version
v
—
Engineering unit
v
v
Range limit
v
—
Measuring range
v
v
Damping
v
v
Output mode
v
—
Burnout direction
v
v
Calibration
v
v
Output adjust
—
v
Data
v
—
Self diagnoses
v
—
—
Printer (In case of FXW with printer option)
v
External switch lock
v
v
Transmitter display
v
v
Linearize
v
v
Rerange
v
v
Saturate current
v
v
Write protect
v
v
History
– Calibration history
– Ambient temperature history
v
v
v
—
Note:HHC’s version must be higher than 7.1 1− 4), for FCX–AIII.
(or FXW
Load limitations
R [Ω]
Load resistance
2000
1500
1000
When Imax is 22.5mA
1474Ω
E-10.5
R=
(Imax+0.9)x10-3
577Ω
Communicable range
with Hand-Held
Communicator
Operating
area
500
250
0
10
16.35
10.5V
50
24V
E [V]
45V
Power supplay voltage E (DC)
Note:Imax is the bigger one, either upper saturation
current [mA] or upper burnout current [mA].
When Imax is from 20mA to 21.6mA, calculate
load resistance using Imax of 21.6mA.
And when Imax is from 21.7mA to 22.5mA,
calculate load resistance using the formula in the
figure.
2
CODE SYMBOLS
1 2 3 4 5 6 7 8
F XW
9 10
1 - A4
Description
Printer
Without
With (explosion-proof structure is not
applicable)
1
2
Charger
Without
100V AC 50/60Hz
115V AC 50/60Hz
230V AC 50/60Hz
0
1
2
3
Explosion-proof structure for hazardous
locations
Without
Intrinsic safety explosion-proof (ATEX)
A
K
Carrying case
Without
With
Y
A
Application
General
A
4
Use
FCX, FCX-A/C, FCX-AX, FCX-AII/CII,
FCX-AIII transmitter
(HHC software version 7.1 or upper)
Remarks
The FCX-AII/CII, AIII series cannot be operated with the
HHC whose software is older than version 6.0. The version of the HHC software can be upgraded by exchanging the built-in ROM. Contact the nearest Fuji Electric representative when it
needs to be upgraded.
(The software version can be checked on the screen display which appears when turning on HHC power supply.)
OUTLINE DIAGRAM (Unit:mm)
(55)
(53)
98
Printer (option)
2
127
66
Battery charger
connector
(350)
ø8
Transmission
signal
connector
Key switch
215
power
supply
42
8
8
89
CONNECTION (For example FCX-AIII transmitter)
To junction
terminal or
instrument
room
Field device
HHC
(Connect to transmitter "+" and "–" terminals)
Instrument room
Junctoin
terminal
Terminal blok
DC power source
For the power supply voltage,
Load resistor refer to the specification
250Ω or more "Operation area between power
supply voltage and load resistance"
of each field equipments.
HHC
HHC
HHC
3
FXW
The product conforms to the requirements of the
Electromagnetic compatibility Directive 2004/108/EC. The
applicable standards used to demonstrate compliance are :EMI (Emission)
EN61326-1 : 2006
Group 1 Class 1
Frequency range
MHz
Limits
30 to 230
40dB (V/m) quasi peak,
measured at 10m distance
230 to 1000
47dB (V/m) quasi peak,
measured at 10m distance
EMS (Immunity)
EN55011
HHC, special cable (with clips), keys (2)
OPTION
Charger, carrying case, printer (based on Code symbols)
EN61326-1: 2006
Table 2 (for Industrial Location)
Phenomenon
Electrostatic
discharge
Reference
standard
SCOPE OF DELIVERY
Test value
4kV (Contact)
8kV (Air)
Basic
standard
Performance
criteria
EN61000-4-2
B
80 to 1000MHz : 10V/m
Electromagnetic 1.4 to 2.0GHz : 3V/m
EN61000-4-3
2.0 to 2.7GHz : 1V/m
field
80%AM (1kHz)
A
Rated power
frequency
magnetic field
A
30A/m
50Hz
EN61000-4-8
Note) Definition of performance criteria
A: During testing, normal performance within the
specification limits.
B: During testing, temporary degradation, or loss of
function or performance which is self-recovering.
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.