PAPERLESS RECORDER DATA SHEET PHL This is a paperless recorder that displays measured data on the LCD in real time and stores data in CompactFlash. The type of input such as thermocouple, resistance bulb, D.C. voltage (current), etc. can be arbitrarily set to 18 channels at the maximum. The data stored in CompactFlash can be regenerated on the screen, and the use of supplied support software allows the data to be regenerated on a PC screen. The data recorded in ASCII format can be directly read in a spreadsheet such as Excel, which facilitates the processing on a PC. (The data recorded in binary format cannot be read in.) FEATURES 1.Large capacity storage by CompactFlash Measured data is periodically stored in CompactFlash. Large storage capacity of up to 512MB allows display files for approximately one and a half years to be recorded continuously at the display refresh cycle of 30 seconds (in the case of ASCII data format, 9 channels). 2.Quick search and display of past data Data stored in CompactFlash can be displayed in succession by scrolling the screen. 3.Various display capability Depending on the object of measurement, the most suitable display format can be selected from a variety of formats including bar graph display, trend display, digital display, etc. 4.PC support software supplied as standard Loader software that enables easy display and change of set data and data viewer software that regenerates the data stored in CompactFlash are supplied as standard. 5.Compact size 160 (W) × 144 (H) × 185 (D) mm (Panel mounting), 1.5kg compact size 6.18-point recording (Option) 12 types of thermocouples, 5 types of resistance bulbs and DC voltage/current input can be recorded up to 18 points. 7.Communication function (Option) With RS485 (MODBUS protocol) interface 8.Screen saver fanction Period of non-operation exceeds the setting value of parameter, “LCD lights-out time”, recorder turns off the backlight. Setting range of this parameter is 0 to 60 minutes. Set to 0, this function doesn’t work, so the backlight keeps turning on during power on. Screen saver function makes the life of backlight expand and power consumption reduce. 9.Ethernet function (Option) FTP, Web server, e-mail and MODBUS-TCP are available using 10Base-T. SPECIFICATIONS Input system Number of input points: 9 points or 18 points (Can be selected at the time of purchase) Input circuit: Input mutual isolation Resistance bulb measured current: about. 1 mA Measuring cycles: 9 or 18 points….100ms cycles Recording cycle: 1 sec to 12 hours Input types: Thermocouple, resistance bulb, dc voltage, and dc current (Shunt resistors are fitted in input terminals). Note) Provide a shunt resistor (type: PHZP0101) separately. Measuring range Input types Reference range 400.0 to 1760.0°C Thermocouple B 0.0 to 1760.0°C R 0.0 to 1760.0°C S −200.0 to 1370.0°C K −200.0 to 800.0°C E −200.0 to 1100.0°C J −200.0 to 400.0°C T 0.0 to 1300.0°C N 0.0 to 1760.0°C W −200.0 to 900.0°C L −200.0 to 400.0°C U 0.0 to 1300.0°C PN −200.0 to 600.0°C Resistance bulb JPt100 −200.0 to 600.0°C Pt100 −60.0 to 180.0°C Ni100 −200.0 to 600.0°C Pt50 −50.0 to 200.0°C Cu50 0.00 to 50.00mV DC voltage 50mV 0.0 to 500.0mV 500mV 1.000 to 5.000V 1-5V 0.000 to 5.000V 0-5V Note) B, R, S, K, E, J, T : JIS C 1602, DIN IEC 584-1 N : NICOSIL-NISIL (IEC 584) W : 5%Re-26%Re · W (Hoskins Mfg. Co. USA) L : Fe-Cu · Ni (DIN 43710) U : Cu-Cu · Ni (DIN 43710) PN: Platinum JPt100 : JIS C 1604-1989 (Old JIS Pt 100) Pt100, Pt50 : JIS C 1604, DIN IEC 751 EDS10-75j Date Dec. 5, 2011 PHL Selection of input types: By key operation on the front panel. Note that the same input type (thermocouple, resistance bulb, voltage) should be set every 2 channels. Refer to “Setting method of input types” for details. Burn-out function: Equipped in thermocouple and resistance bulb inputs as standard, and overswings the recording to 100% side. Thermocouple burn-out current: approx. 0.2 µA Input filter function: Settable for each channel (primary delay filter) Time constants are settable in the range from 0 to 900 sec. Scaling function:Possible by dc voltage (current) input Scaling range: -32767 to 32767 Decimal position: settable at any point Unit symbol: settable up to 7 digits and 125+12 types Subtraction function: Subtraction between each channel is allowed. Totalizing function: The measured value of each channel can be totalized. The base time can be selected from Day, Hour, Minute, and Second. F value calculation function: F value (extinction value of bacteria by sterilization by heating) can be calculated from the measured temperature by each channel. Square rooter function: Square rooter can be performed against the input value per each channel. Logarithmic calculation function: The measured value of each channel can be displayed in exponent form. Mathematics function: The math function as shown below is available. 1) Formula It can be set 1 main formula and 3 temporary one. Addition, Subtraction, Multiplication, Division Absolute value, X to the power of Y, Logarithm, Natural logarithm, Exponential function, Humidity, Average, Maximum, Minimum. 2) Input signal DI (DI1 to DI10), Totalize (ch1 to ch30), Analog input (ch1 to ch30), Constant (No.1 to No.20), Communication input (No.1 to No.12) Indication system 5.7” TFT color LCD (320 × 240 dots) with backlight, no contrast adjustment Note)The LCD may have some pixels that do not stay on or off. Due to the characteristics of liquid crystal, the brightness may not be uniform, which is not a failure. Color of indication: 14 colors Indicator: 2 Applicable language: English, French, German, Italian (switchable) Life of backlight: 50,000 hours (20°C) (the complete indicator unit should be replaced when replacing backlight). Trend display: Direction: vertical and horizontal Number of channels: 10 channels or 4 channels for the group on one screen (Input: 18 points at the maximum). Display refreshment cycles: select from 1 second to 12 hours No numerical value display. Scale display/ no-display can be selected. Bar graph display: Direction: vertical Number. of channels: 10 channels or 4 channels for the group on one screen (Input:18 points at the maximum). Display refreshment cycles: 1 second. Analog meter display: Display for up to 4 inputs per group (input from 1 to 4). Display in bar graphs or in analog meters can be selected. Display refresh cycle: 1 second Digital display: Number of channels: 10 channels or 4 channels for the group on one screen (Input:18 points at the maximum). Display refreshment cycles: 1 second. Totalizing data display: Number of channels: 10 channels or 4 channels for the group on one screen (Input: 18 points at the maximum) Display refresh cycle: 1 second. Event summary display: Alarm summary and message summary can be displayed. The message occurrence information and message display can be switched. Ethernet log display: E-mail sending, FTP server log in/off and MODBUS TCP/IP communication start/ stop can be displayed. Parameter display/set: Already-set Data Display and Set Change Display screen TAG indication: Number. of characters to be displayed: Up to 8 characters (note 1) at 10 channels on one screen or up to 16 (= 8 × 2) characters at 4 channels on one screen. Note 1: On some screen, it can be displayed only 7 characters. Characters to be displayed: Alphanumerical characters Tag, unit and channel number display: It depends on the screen. See below table. Screen Number of channel on one screen Items unit ch number 4 or less + + more than 5 x x Bar graph 4 or less + + + more than 5 x x Analog 4 or less all items are displayed meter more than 5 No1 to 4 v v v x x x others Digital 4 or less all items are displayed more than 5 v v v x: only 1 item can be displayed. +: only 2 items can be displayed. v: 3 items can be displayed. Only TAG2 can’t be displayed. Trend TAG1 + x + x TAG2 + Historical trend display: The past data can be displayed from the Compact Flash or internal memory. The past data file can be read and displayed with scroll display function or jump the cursor to the position which you entered date and time. Scale display/no-display can be selected. Number of screen groups: Four groups (Up to 10 channels per 1 group can be registered.) Keyboard No. of Keys: Function: 8 Use to select various screens and set various parameters. Recording function External memory media: Compact Flash card (Format as FAT32, FAT16 or FAT, or recorder can’t read and write.) Recording capacity: 2 GB maximum (compact flash). Limiting the recording file to 64 MB is recommended (for 112 hours if display refresh cycle is 1 second. See Table 1 (p. 7).) (When the size of the recording file comes to be 256 MB or more, a new file is created automatically and recording is maintained.) * Please change the compact flash every six month to prevent the data losing. Recording method: Turning ON the REC key allows measured data to be written at fixed cycles. Recorded as a new file whenever the recording starts Data save cycles: Linked to the display refreshment cycles on the “Trend display” screen. However, they are automatically set to about 1 minute if the refreshment cycles are set to less than 1 minute. Trend data: Average, instance or min. and max. measured values out of measured data that are sampled at the measuring cycles are saved. Event data: Saves alarm data, message data and power ON data when the power turns off and on during recording. Totalizing value data: Totalizing value data at designated timing is recorded per channel. Totalized value data at designated totalized value recording cycle or the sum total is recorded in the totalizing file. You can choose which type you want to record. For each cahnnel. it can be select as totalizing action from Analog input totalization, Digital input count or period of Digital input ON, and it can be select as totalizing period type from Dairy, Weekly, Monthly, Annual, Periodic, Dairy (time set) or External input signal. Even if a power failure occues during totalization and then the power is restored,the totalization restarts from the value before power failure. Storage capacity : Approximately 3 years when the display refresh cycle is 30 seconds (in the case of 9-channel recording in ASCII data format, and 512 MB Compact Flash is used). Refer to Table 1. Residual capacity of memory: Indicates the memory which has already used on the screen. When all the memory is used up, you can stop recording or delete the oldest recording file to save the newest data. Compact flash card form: PHZP2801 (CF card) (If a card other than the above is used, no operation assurance is ensured. Meanwhile, as for other CF cards for which operation check will have been completed, the results will be posted on our company's homepage sequentially. Please refer to this website.) Data format: Either of ASCII or binary format can be selected. (Switching cannot be made while the recording is in progress. In the case of ASCII format, the data can be directly read on Excel, etc.) Note: The data recorded in binary format cannot be read directly. Approximately 166 bytes per 1 sampling (for 9-channel input in ASCII format) or approximately 40 bytes (for 9-channel input in binary format) Alarm function No. of settings: Up to 4 alarms for each channel are settable. Type of alarm: High/Low limits Indication: Status (alarm types) is displayed on digital display unit when an alarm occurs. History display on alarm summary (Alarm start/cancel time and alarm types) Hysteresis: Set within the recording range of 0 to 100% (it is effective only in case of high/ low limit alarm) Relay output: Number of points; 10 (option: Cannot be selected if the number of input points is 18.) Transistor output (Open collector): Number of points; 18 (option) Alarm latch function: Keeps alarm indication and alarm output turning on after alarm reset. ON/OFF operation is performed according to key setting. Power supply Rated power voltage: 100 to 240V AC Range of operating voltage: 90 to 264V AC 3 PHL Supply frequency: 50/60Hz (both employable) Power consumption: 100V AC About 36VA 240V AC About 47VA Structure Mounting method: Panel-mounted (vertical panel) Thickness of panel: 2 to 26 mm Materials: PC-ABS for case and bezel Color: Black External dimensions: Panel-mounted: 160 (W) × 144 (H) × 185 (D) mm Mass: About 1.5 kg (no option) External terminal board: Screw terminals (M3 thread) RJ45: Ethernet terminal (option) Normal operating condition Power voltage: 90 to 264V AC Supply frequency: 50/60 Hz ±2% (both employable) Ambient temperature: Panel-mounted 0 to 50°C (without Ethernet option*1) 0 to 40°C (with Ethernet option*2) Ambient humidity: 20 to 80%RH Vibration: 10 to 60Hz 0.2m/s2 or less Shock: None Magnetic field: 400 A/m or less Signal source resistance: Thermocouple input …. 1kW or less Resistance bulb input … 10W/wire or less (resistance of each wire of 3-wire system should be balanced). Voltage input … 0.1% or less of input resistance Mounting posture: Forward tilt 0°, backward tilt within 30°, horizontal 0° Warm-up time: One hour or more after power ON Environmental protection: IEC IP50 (Front)/20 (Terminal) Installation category: II Pollution degree: 2 Operating altitude: 2000m max. *1: In case of the 12th digit of ordering code is ”Y” or ”R”. *2: In case of the 12th digit of ordering code is ”E” or ”W”. Safety and EMC standard Safety standard: Based on IEC61010-1 EMC standard: Based on EN61326 Transportation/storage conditions Temperature: Humidity: Vibration: 4 −10 to +60°C 5 to 90%RH, no condensation 10 to 60Hz, 2.45m/s2 or lower Shock: 294m/s2 or lower (packed state) Reference standard Accuracy/resolution: Measuring conditions (23±2°C, 65±10% RH, power voltage, frequency fluctuation within ±1%, no external noise, warm-up time of 1 hour or more, vertical mounting, standard values of signal source resistance and wiring resistance... within 1% ) Input types Thermocouple B R S K E J T N W L U PN Digital indication accuracy Note 1 Digital indication resolution ±(0.15%+1 digit) ±(0.3%+1 digit) for the range shown below Thermocouple B : 400 to 600°C Thermocouples R and S : 0 to 300°C Thermocouples K, E, J, T, L and U : −200 to −100°C 0.1°C Resistance bulb JPt100 Pt100 ±(0.15%+1 digit) Pt50 0.1°C Ni100 Cu50 ±(0.5%+1 digit) DC voltage 50mV 10µV 500mV 100µV ±(0.15%+1 digit) 1-5V 1mV 0-5V 1mV Note 1) Digital indication accuracy is a percentage (%) of the value in the measuring range on page 1. Note 2) No error of reference contact compensation of thermocouple is included. Error of reference contact compensation: K, E, J, T, N, L, U, PN: ±0.5°C R, S, B, W: ±1.0°C (when measured at 0°C or more) Max. input voltage: Thermocouple, resistance bulb, dc voltage: ±10V DC (continuous) Input resistance: Thermocouple, DC voltage: About 1MΩ Others With calendar function (Christian era) Accuracy: ±100ppm or less (monthly error: about 4 minutes) However, time error at ambient temperature 23±2°C and power ON/OFF is not included. Memory backup:Parameters are saved to the internal nonvolatile flash memory. The clock and totalized data are backed up with built-in lithium battery. Insulation resistance: 100MW or more (when measured between each terminal and ground by using a 500V DC megger) Withstand voltage: Power terminal – ground: 2000V AC, 1 min Input terminal – ground: 500V AC, 1 min Alarm terminal – ground: 2000V AC, 1 min Alarm terminal – alarm terminal: 750V AC, 1 min Communication terminal – ground: 500V AC, 1 min Alarm terminal (open-collector) – ground: 500V AC, 1 min Clock: Effect on operation Effect of power supply fluctuation conditions: For the fluctuation in the range from 90 to 264V AC (frequency: 50/60Hz) Reading change (100V AC base): ±(0.2%+1 digit) or lower. For the fluctuation in the range from 47 to 63Hz (power voltage: 100V AC) Reading change (50Hz base): ±(0.2%+1 digit) or lower. Effect of input signal resistance: Thermocouple input: (0.5µV/Ω)+1 digit or less DC voltage: Fluctuation for resistance value equivalent to 0.1% of the input resistance: ±(0.2%+1 digit) or lower. Resistance bulb (for wiring resistance of 10Ω for 1 line (the same for 3 lines)) Reading change: ±(0.2%+1 digit) or lower. Effect of ambient temperature: Reading change: ±(0.3%+1 digit)/10°C or lower. Effect of Mounting position: For the backward 30° slant Reading change: ±(0.2%+1 digit) or lower. Effect of vibration: When sine wave of 10 to 60Hz with the acceleration of 0.2m/s2 is applied in each direction for 2 hours. Reading change: ±(0.2%+1 digit) or lower. Effect of external noise: Normal mode noise (50, 60Hz±0.1Hz) …20dB or more Common mode noise (50, 60Hz±0.1Hz) …120dB or more (Thermocouple input: minus terminalground) (Resistance bulb input: b Line-ground) Additional function (option) ■Alarm relay output/DI (11th digit of code symbols: “1”) A card with 10-point relay output and 5-point DI input can be mounted. Cannot be mounted if the number of input points is 18. Terminal structure: M3 screw terminal Alarm relay output: Contact output (SPST:10 points), Individual channel or common output (OR output) allowed. DO1: Contact capacity; 150V/3A AC, 30V/3A DC (resistive load) DO2-10: Contact capacity; 240V/3A AC, 30V/3A DC (resistive load) DI input: No-voltage contact input (5 points) The following control is allowed by contact input. (1) Recording start/stop (2) Message set (3) F value calculation reset (4) Totalizing start/stop (5) Totalizing reset (6) LCD turns on (7) E-mail sending On pulse width: 200msec or longer Off pulse width: 200msec or longer ■Communication, Alarm output with open-collector and DI (12th digit of code symbols: “R”) A card with communication with RS485. MODBUS protocol, 18-points open-collector output and 5-points DI input is available. Terminal structure: M3 screw terminal for communication, DO11 (alarm output with open-collector), DI6 and power supply for DIO. D-sublight type 25 pins connector with female terminal for DO12 to DO28 (alarm output with open-collector), and DI7 to DI10. Communication: Physical specifications: EIA RS485 Communication protocol: Modbus (RTU) Communication method: 2 wire method. Half duplex bit serial, start-stop sync type. Data type: 8 bits. Parity: odd/even/none. Stop bit: 1 bit. Communication rate: 9600, 19200bps Connection aspect: multi-drop/up to 32 recorders connectable including master station Communication distance: Total extension 500m or less RS232C/RS485 Signal converter (recommendation): Isolated type Manufacture: OMRON Corporation Model: K3SC-10 Alarm output: Open-collector transistor output (18 points) Electrical Rate: 30Vdc, 100mA (resistive load) DI input: No-voltage contact input (5 points) The following control is allowed by contact input. (1) Recording start/stop (2) Message set (3) F value calculation reset (4) Totalizing start/stop (5) Totalizing reset (6) LCD turns on (7) E-mail sending On pulse width: 200msec or longer Off pulse width: 200msec or longer 5 PHL Ethernet (Option) The following can be performed through the Ethernet function. ■HTTP server (Internet Explorer 6 is available) Note 1 Measurement display: Digitally displays the measurement of each channel of the recorder and alarm occurrence status. Event summary display: Displays event summary including alarm ON/OFF and issuance of messages. Main unit information display: Displays memory use conditions and information on the main unit such as the battery end warning. Integrated value display: Digitally displays the integrated value of each channel of the recorder. ■FTP server (Internet Explorer 6, is available.) Note 1 File download: Record files stored in compact flash (CF) can be downloaded from the browser. File delete: Record files stored in CF can be deleted from the browser. Access authentication: Authenticates access authority to FTP server. ■SMTP (e-mail client) Transmits e-mails to specified address under the following conditions. (1) When an alarm turns on or off (2) When DI is set to ON or OFF (3) When an error occurs to the main unit (such as low battery or no memory space) (4) At specified intervals ■MODBUS TC/IP Data read: Settings can be read through MODBUS TCP/IP communication. Data write: Settings can be written through MODBUS TCP/IP communication. Note1: Neither Netscape nor Mozilla Firefox are available. Support software The following software is provided as standard. •PC/AT-compatible machine •Operation on PC98-series machines by NEC is not guaranteed. •Operation on self-made or shop-brand PCs is not guaranteed. ■Loader software for PC Major function: Performs various parameter setting/ change of the main unit O/S: Windows 2000/XP Required memory: 64MB or larger Disk drive: Windows 2000/XP-capable CD-ROM drive Hard disk capacity: Free capacity of 30MB or larger required Printer: Windows 2000/XP-capable printer and printer driver Note) PC loader communication cable (type PHZP1801) is separately required. 6 ■Data viewer software Major function: Regenerates the past trend record on the PC from the data in the Compact Flash. Provided with historical trend display and event display functions. O/S: Windows 2000/XP Required memory: 64MB or larger Disk drive: Windows 2000/XP-capable CD-ROM drive Hard disk drive: Free capacity of 30MB or larger required Printer: Windows 2000/XP-capable printer and printer driver Standard functions Function Record range voluntary setting Description Recording range can be set by channel. Input type setting Input can be set by channel. (Key operation on the front face) Set the same input type for every 2 channels. See “SELECTING INPUT TYPE” on the last page. Skip function Trend display Skips arbitrary channel display/recording. Time display: Time is displayed at the top of the trend display screen. Alarm display: On occurrence of an alarm and the restoration, alarm is displayed in the alarm display field. The Compact Flash usage is displayed at the top of the bargraph. TAG name display Screen name display Unit creation By channel, Maximum of 8 characters. Displays the screen name (maximum of 16 characters). Industrial units can be arbitrarily created, Maximum of 7 digits, 12 types. Arbitrary scaling is allowed in the case of DC voltage input. Decimal point position can also be arbitrarily set in the range from -32767 to 32767. Scaling function PV shift Shift the zero point and slant of the reading. Input filter Prevents sudden fluctuation of input for each channel (primary delay filter). Time constant: 0 to 900 seconds. Burnout function Displays the break of thermocouple/resistance bulb input by scaling out to 100% side. Historical trend display Regenerates and displays the data stored in the compact flash by scrolling the screen or jump to time when you entered. Table 1. Recording capacity If the number of input points is 9, there are no events such as messages, and the data format is ASCII, the recordCompactFlash size for the period of time 64MB ing can be made listed in the tables shown below. (When the number of input points is 18, the Display refreshment 1 sec 10 sec 30 sec 1 min 10 min cycle is approximately one half of those listed in the table.) period Recordable capacity the period is approximately 4 times as long (In binary format, 112 hours 46 days 140 days 280 days 7.7 years (about) as those listed in the table.) CompactFlash size Display refreshment cycle Recordable capacity(about) 256MB 1 sec 10 sec 30 sec 1 min 18 days 187 days 1.5 years 3 years When Compact Flash is not used, up to 600K bytes of the recording data and the event data can be stored in the main unit. (In case of 9-channel in Max./Min. recording, approximately 15,300 data can be stored. For 4 hour at the display refresh cycle of 1 second. The number of the save data varies depending on the number of the event data. ORDERING CODE Digit Specifications 4 <Number of input points> 9 18 11 <Alarm (relay) output/DI input> Without With 12 <Communication> Without any communication With RS485, Alarm and DI input With Ethernet communication With Ethernet, RS485, Alarm and DI input PHL 4 5 6 7 8 9 10 11 12 13 1 B 1 2 - E 1 V Note 1 Note 2 2 0 1 Note 1 Y R E W Note 3 Note 3 Note 1 : Cannot be selected if 2 is selected for the forth digit (the number of input points is 18). Note 2 : Cannot be selected if 1 is selected for the 11th digit. Note 3 : Alarm outputs are open-collector transister output. STANDARD ACCESSORY Quantity Panel mounting Item Recorder (PHL) 1 Panel mounting bracket 2 CD-ROM PC support software instruction manual 1 Panel packing for the front face 1 Noise filter for the power supply 1 OPTIONAL ITEMS Item Code Specification Shunt resistor for DC current input PC loader communication cable CD-ROM with Instruction manual and 2 support software Terminating resister for communication PHZP0101 10Ω±0.1% PHZP1801 With USB-A and USB miniB * PHZP0601 PHZP0701 D-sublight type 25pins connector with male terminal for alarm output, which does not include cable PHZP0801 Transmission cable PHZP0901 100Ω PHZP1001 For PHL to PC For PHL to PHL PC card adapter PHZP0501 For Compact Flash Compact Flash PHZP2801-512 PHZP2801-01G 512MB 1GB * Shape of this cable is shown below USB (A) Plug – USB (Mini-B ) Plug 7 PHL OUTLINE DIAGRAMS (Unit : mm) Panel Mounting In the case of 9-point input Panel 2 T 26 T Mtg.bracket Ethernet terminal (Option) Digital input & alarm output (Option) Input terminal Source terminal L DIOSHLD A6 DO11 COM 24VDC IN DIO-CN TRX1 TRX2 R-MODULE Rcj Fuji Electric 144 136.5 161 N 100~240VAC ETHERNET 160 140 21.6 185 136.5 Communication, digital input and alarm output terminal. (Option) 24.6 when packing is mounted In the case of 9-point input (Note) When placing the main unit on another instrument or on the floor, allow a space of 100mm or more between the unit and instrument or the floor. In the case of 18-point input Input terminal (ch1 to ch9) Panel 2 T 26 T Mtg.bracket Ethernet terminal (Option) Input terminal (ch10 to ch18 : Option) Source terminal TRX1 TRX2 R-MODULE Rcj Fuji Electric R-MODULE Rcj Fuji Electric 136.5 161 144 DIO-ON DIOSHLD A6 DO11 COM 24VDC IN L N 100~240VAC ETHERNET 160 140 21.6 185 24.6 when packing is mounted (Note) When placing the main unit on another instrument or on the floor, allow a space of 100mm or more between the unit and instrument or the floor. 8 136.5 Communication, digital input and alarm output terminal. (Option) In the case of 18-point input Mounting one unit Mounting n unit 137 +1.5 0 (160 × n-22)+20 n : Number of units to be mounted 137 +1.5 0 137 +1.5 0 Panel cutout Do not use the water proof packing in case of mounting n unit 9 PHL EXTERNAL CONNECTION DIAGRAMS (M3 screw) In the case of 9-point input 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 Source terminal Input terminal Voltage DI1 DI2 DI3 DI4 DI5 DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10 Thermocouple Resistance Thermocouple Voltage bulb Resistance bulb 61 62 63 71 72 73 CH6 CH7 RCJ 81 82 83 91 92 93 CH8 CH9 11 12 13 21 22 23 31 32 33 41 42 43 51 52 53 AC100 240V 50/60Hz CH1 Digital input and alarm (open collector) output terminal. D-Sub terminal. CH2 CH3 CH4 CH5 (Note) For current input, connect an optional shunt resistance to a voltage input terminal PCD 1 14 13 25 6 7 8 9 10 11 12 15 16 17 18 19 20 21 22 23 24 2 3 4 5 VPD PCD DO12 DO13 DO14 DO15 DO16 DO17 DO18 DO19 DO20 DO21 DO22 DO23 DO24 DO25 DO26 DO27 DO28 DI7 DI8 DI9 DI10 Communication, digital input and alarm (open collector) output terminal. VPD VPD DIO(+24V) PCD PCD DIO(0V) DO11 DI6 SHLD (shield) TRX2 – TRX1 + (–) (+) 24Vdc MODBUS communication Alarm (relay) output / digital Input terminal PCD In the case of 18-point input CH15 CH16 RCJ CH17 CH18 Input terminal Resistance Thermocouple Voltage bulb 111 161 112 162 113 163 121 171 122 172 123 173 131 132 133 141 181 142 182 143 183 151 191 152 192 153 193 Thermo- Resistance Voltage couple bulb CH10 CH11 CH7 CH12 CH13 CH14 61 62 63 71 72 73 CH6 RCJ CH8 CH9 81 82 83 91 92 93 Source terminal Resistance Thermocouple Voltage bulb 11 12 13 21 22 23 31 32 33 41 42 43 51 52 53 AC100 240V 50/60Hz CH1 CH2 Digital input and alarm (open collector) output terminal. D-Sub terminal. CH3 CH4 CH5 (Note) For current input, connect an optional shunt resistance to a voltage input terminal PCD 10 1 14 13 25 6 7 8 9 10 11 12 15 16 17 18 19 20 21 22 23 24 2 3 4 5 VPD PCD DO12 DO13 DO14 DO15 DO16 DO17 DO18 DO19 DO20 DO21 DO22 DO23 DO24 DO25 DO26 DO27 DO28 DI7 DI8 DI9 DI10 Communication, digital input and alarm (open collector) output terminal. VPD VPD DIO(+24V) PCD PCD DIO(0V) DO11 DI6 SHLD TRX2 – TRX1 + PCD (shield) (–) (+) 24Vdc MODBUS communication Input terminal Thermo- Resistance Voltage couple bulb Selecting input type Basically, the input type can be every 2 channels. The input type of channel 2, 4, 6, 8, 11, 13, 15 and 17 can only be set in the same category of previous channel. The following input types are available. Input category Details Thermocouple, 50mV Resistance bulb 500mV 5V K, E, J, T, R, S, B, N, W, L, U, and PN thermocouples, 50mV Pt100, JPt100, Ni100, Pt50, Cu50 500mV 1 to 5V, 0 to 5V Note, however, that input type can be arbitrarily selected only for channels 9 and 18 irrespective of the type allocated to other channels. Example of channel input type selection Input type Channel 1 K thermocouple Channel 2 T thermocouple Channel 3 1-5V Input category Thermocouple, 50mV Description The type of thermocouple can be arbitrarily selected for each channel. 5V Channel 4 0-5V Channel 5 Pt100 Channel 6 JPt100 Channel 7 500mV Channel 8 500mV Channel 9 J thermocouple Thermocouple, 50mV Input type can be arbitrarily selected for channel 9. Channel 10 K thermocouple Channel 11 50mV Thermocouple, 50mV The input type of the thermocouple and 50mV is the same. Channel 12 Skip 5V Skip can arbitrarily selected irrespective of the input type. Channel 13 1-5V Channel 14 Pt100 Channel 15 Skip Channel 16 Skip Channel 17 500mV Channel 18 50mV Resistance bulb The type of resistance bulb can be arbitrarily selected for each channel. 500mV Resistance bulb 500mV Thermocouple, 50mV Input type can be arbitrarily selected for channel 18. 11 PHL Note 1) Windows 2000/XP, Excel and Internet Explorer are the registered trademarks of Microsoft Corporation in the U.S.A. Note 2) Compact Flash is the registered trademark of Sandisk Corporation. Note 3) Modbus® is the trade mark or registered trade mark of AEG Schneider Automation International. Note 4) PC98 series are the trade mark or registered trade mark of NEC Corp. Note 5) Netscape is the trade mark or registered trade mark of Netscape Communication Corp. Note 6) Mozilla Firefox is the registered trade mark of Mozilla Foundation. Caution on Safety *Before using this product, be sure to read its instruction manual in advance. International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice. Printed in Japan