DESCRIPTION
The Kotron Model 82 RF Capacitance transmitter is one
of the most cost effective level transmitters available
today. Compact in size, it employs state-of-the-art surface mount technology in an encapsulated (potted)
module for a stable, accurate measurement in a wide
range of materials.
FEATURES
• 4–20 mA isolated output signal
(reversed 20–4 mA output optional)
• Utilizes a 24 VDC current loop for power source and
signal transmission
• 120/240 VAC option available for four-wire applications
• Minimum span 50 pF
• Maximum span 4000 pF
• Integral metering points to allow the local
measurement of 4–20 mA loop current without
breaking the two-wire circuit loop
• Power indicator LED varies in brightness with level
changes
APPLICATIONS
• Continuous level monitoring
• ±0.25% repeatability
• Liquid-liquid interface level measurement
• FM, CSA, and ATEX listed intrinsically safe when used
in conjunction with an approved barrier
• CSA explosion proof designs
• Available with a full range of rigid and flexible sensing
probes to 5000 psig (345 bar) and +1000° F (+538° C)
• Input voltage of 14 to 40 VDC at transmitter terminals
• Two-wire, integrally mounted units meet CE requirements for RFI/EMI noise immunity
• Clean or dirty liquids
• Viscous liquids
• Light slurries
• High temperature liquids
• Hydrocarbons & solvents
• Acids & corrosive liquids
• Food & beverage
TECHNOLOGY
The amount of capacitance developed in any vessel is
determined by the size (surface area) of the probe, the
distance from the probe to its ground reference (e.g. tank
wall), and the dielectric of the medium being measured.
If the probe’s mounting position is fixed and the dielectric
value of the medium is constant, then the amount of
ELECTRICAL
capacitance developed becomes dependent on the media
in contact with the probe.
As media rises and falls in the tank, the amount of capacitance developed between the sensing probe and the
ground also rises and falls. This change in capacitance is
converted into a proportional 4–20 mA output signal.
SPECIFICATIONS
Supply Voltage
Current
Line Variation
Ambient Temperature
Zero Range
Span Range
Output Linearity
Response Time
Repeatability
Temperature Coefficient of Output
-40° to +160° F (-40° to +70° C)
24 VDC, (14–40 VDC)
120/240 VAC, 50–60 Hz, (+10/-15%)
38 mA maximum
Less than ±.10%/volt, for voltages between 14–40 VDC
-40° to +160° F (-40 to +70° C) ➀
1000 pF (max.), 0 pF (min.)
4000 pF (max.), 50 pF (min.)
50–500 pF ±1% of span
501–1500 pF ±2% of span
1501–4000 pF ±1% of span
Less than 0.1 second
±0.25%
4000 pF span: Less than 0.035%/° F (0.063%/° C)
1000 pF span: Less than 0.025%/° F (0.045%/° C)
50 pF span: Less than 0.075%/° F (0.135%/° C)
➀ Consult factory for higher temperatures on remote mounted transmitter
2
MODEL
STANDARD
NUMBER
PRESSURE
Models available for quick shipment, usually within one week after factory
receipt of a purchase order, through the Expedite Ship Plan (ESP)
BASIC
082
82 CE transmitter
HOUSING
8
FM/CSA/CENELEC EEx ia, aluminum 3⁄4" NPT dual conduit
FUNCTION/INPUT POWER
0
1
3
4
Four-wire, 120 VAC ➀
Four-wire, 240 VAC ➀
Two-wire, 24 VDC Nominal (14 to 40 VDC), FM, CSA
Two-wire, 24 VDC Nominal (14 to 40 VDC), ATEX Intrinsically Safe
METER
0
1
None
Analog meter (Not FM/CSA approved)
OUTPUT SIGNAL
3
4
Standard 4–20 mA
Reversed 20–4 mA ➁ ➂ (Not CSA approved)
MOUNTING CONFIGURATION
00
04
10
14
Integral, NEMA 4X/7/9 aluminum housing
Integral, NEMA 4X/7/9 316 stainless steel housing ➂ ➅
Remote, NEMA 4X/7/9 aluminum housing ➃ ➄
Remote, NEMA 4X/7/9 316 stainless steel housing ➂ ➃ ➄ ➅
PROBE ASSEMBLIES ➆
A full range of rigid and flexible probes for conductive and
non-conductive process media is available. For further information on probe assemblies, please refer to bulletin 50-125.
➀ Not available with mounting codes 04 and 14.
➁ Consult factory on reversed output model.
➂ Not available with function/input power codes 0 and 1.
➃ Remote units supplied with separate probe and
transmitter housing, 20 feet (6 meters) of cable
and transmitter housing bracket.
➄ Remote units up to 40 feet (12 meters) with special cable,
order cable part number 009-8222-001.
➅ Not available with Meter option code 1.
➆ Delivery is ESP only if Model 082 and probe
selected are both ESP.
0
8
2
4
3
DIMENSIONAL
INCHES
SPECIFICATIONS
(mm)
4.63 (118)
Dia.
3.00
4.63 (118)
Dia.
3.00
(76)
2.75 (70)
3/4" NPT
Optional
mounting
flange
12.65 (321)
(76)
1"
NPT
Optional
mounting
flange
3.5"
3.5"
3/4" NPT
3/4" NPT
I.L.
I.L.
.50 (13)
.625 (16)
.50 (13)
.625 (16)
Integral Mount with Rigid Probe
(24 VDC Two-Wire)
4.63 (118)
Dia.
3.00
Integral Mount with Rigid Probe and Meter
(24 VDC Two-Wire)
(76)
4.54 (115)
2
Optional anchor
assembly
P/N 032-8814-001
I.L.
Optional
mounting
flange
2.37 (60)
3.5"
4.38 (111)
3/4" NPT
4.87 (124)
2.75
(70)
4.76
(121)
3/4"
NPT
Optional
mounting
flange
4.63 (118)
Dia.
3.00 (76)
6.68 (170)
4.63 (118)
Dia.
2 Holes
.38 Dia.
(10)
3.00 (76)
2.00
(51)
Probe
2 diameter
.1875 (5)
.2500 (6)
3.75
(95)
3.50
(89)
3.00
(76)
3/4"
NPT
3/4" NPT
I.L.
Side View
Bracket Front View
.50 (13)
.625 (16)
2.95 (75)
5.50 (141)
Remote Mount with Rigid Probe
(24 VDC Two-Wire)
.75 (19)
Optional weight
P/N 032-8814-001
1.25 (32)
Integral Mount with Flexible Probe
(120 VAC or 240 VAC Four-Wire)
4.63 (118)
Dia.
14.08 (358)
4.63 (118) Dia.
3.00 (76)
2 Holes
.38 Dia.
(10)
3.00
2.75
(70)
4.76
(121)
(76)
Optional
mounting
flange
2.37 (60)
3.75
(95)
10.33 (262)
Side View
3/4" NPT
3.50
(89)
1" NPT
3.5"
3.00
(76)
2.00
(51)
3/4" NPT
I.L.
Bracket Front View
.50 (13)
.625 (16)
Remote Mount with Rigid Probe and Meter
(24 VDC Two-Wire)
4
AGENCY
APPROVALS
AGENCY
APPROVED MODEL
PROTECTION METHOD
AREA CLASSIFICATION
FM
082-8303-400
082-8303-410
082-8304-400
082-8304-410
Intrinsically Safe
Class I, Div 1, Groups A, B, C & D;
Class II, Div 1, Groups E, F & G;
Class III, NEMA 4X
Non-Incendive
Class I, Div 2, Groups A, B, C & D
Suitable for:
Class II, Div 2, Groups F & G;
Class III
Intrinsically Safe ➀
Class I, Div 1, Groups A, B, C & D;
Class II, Div 1, Groups E, F & G;
Class III, TYPE 4X
Suitable for:
Class I, Div 2, Groups A, B, C & D;
Class II, Div 2, Groups F & G;
Class III
Explosion Proof ➁
Class I, Div 1, Groups C & D;
Class II, Div 1, Groups E, F & G
Class III, TYPE 4X
CSA
082-8303-400
082-8303-410
082-8303-400
082-8303-410
ATEX
082-84XX-4XX
II 1G EEx ia IIC T6
➀ Not I.S. (CSA) for Groups E & F when used with a bare probe.
➁ Approval is valid only with the use of insulated rigid probes.
These units have been tested to EN 50081-2
and EN 50082-2 and are in compliance with
the EMC Directive 89/336/EEC.
Loop Resistance vs. Power Supply Voltage
1300
1300 ohms
@ 40V
MAXIMUM LOOP RESISTANCE (Ohms)
(Including Barrier Resistance)
1200
1100
1000
900
800
700
600
500
500 ohms at 24V
400
300
200
100
0
12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
Power Supply Voltage (Volts)
Electrical data
5
QUALITY
The quality assurance system in place at
Magnetrol guarantees the highest level of quality throughout the company. Magnetrol is committed to providing full customer satisfaction
both in quality products and quality service.
Magnetrol’s quality assurance system is registered to ISO 9001 affirming its commitment to
known international quality standards providing the strongest assurance of product/service
quality available.
Several Model 82 CE transmitter models are
available for quick shipment, usually within
one week after factory receipt of a purchase
order, through the Expedite Ship Plan (ESP).
ESP service may not apply to orders of ten units
or more. Contact your local representative for
lead times on larger volume orders, as well as
other products and options.
ESP
Expedite
Ship
Plan
To take advantage of ESP, match the color
coded model number codes in the selection
charts (standard dimensions apply).
WARRANTY
All Magnetrol electronic level and flow controls
are warranted free of defects in materials or
workmanship for one full year from the date of
original factory shipment.
If returned within the warranty period; and,
upon factory inspection of the control, the
cause of the claim is determined to be covered
under the warranty; then, Magnetrol will repair
or replace the control at no cost to the purchaser
(or owner) other than transportation.
Magnetrol shall not be liable for misapplication,
labor claims, direct or consequential damage or
expense arising from the installation or use of
equipment. There are no other warranties
expressed or implied, except special written
warranties covering some Magnetrol products.
5300 Belmont Road • Downers Grove, Illinois 60515-4499 • 630-969-4000 • Fax 630-969-9489 • www.magnetrol.com
145 Jardin Drive, Units 1 & 2 • Concord, Ontario Canada L4K 1X7 • 905-738-9600 • Fax 905-738-1306
Heikenstraat 6 • B 9240 Zele, Belgium • 052 45.11.11 • Telex 25944 • Fax 052 45.09.93
Regent Business Ctr., Jubilee Rd. • Burgess Hill, Sussex RH15 9TL U.K. • 01444-871313 • Fax 01444-871317
Copyright © 2004 Magnetrol International, Incorporated. All rights reserved. Printed in the USA.
Magnetrol and Magnetrol logotype are registered trademarks of Magnetrol International.
Performance specifications are effective with date of issue and are subject to change without notice.
The brand and product names contained within this document are trademarks or registered trademarks of their respective holders.
BULLETIN: 50-123.18
EFFECTIVE: January 2004
SUPERSEDES : December 2001