MAGNETROL 804-Y25D-330

Kotron® Sentinel
Model 804
RF Level Transmitter
D E S C R I P T I O N
The Sentinel is a unique, powerful level transmitter. The
leading-edge microprocessor-based circuitry has nonvolatile memory. The display and keypad simplify
calibration and setup of the instrument. Powerful diagnostics check all functions of the system, simplifying
troubleshooting. MagneCal™ offers the user the greatest
improvement in RF Capacitance—one small level change
is needed to calibrate.
F E A T U R E S
• Two or four SPDT relays with gold flash contacts for
alarm and control operation.
• Optional intrinsically safe probe circuitry (with
on-board barriers).
• 16-button keypad and 2 × 16 LCD display.
• Isolated 4–20 mA output includes an active/passive
mode.
• Relays can be configured for sequential or lead/lag
pump control.
• One small level change (2% of span) needed for initial
probe calibration.
A P P L I C A T I O N S
• Continuous level measurement
• Interface measurement
• 4–20 mA and up to eight control points can be programmed with no level change.
• Powerful self-diagnostics check the system, including
probe.
• Relay #1 can be dedicated as a diagnostics relay.
• Hydrocarbons and solvents
• Slurries
• Acids
• High temperature/pressure liquids
T E C H N O L O G Y
The amount of capacitance developed in any vessel is
determined by: the size (surface area) of the probe; the
As the media rises and falls in the tank, the amount of
capacitance developed between the probe and the
distance from the probe to its ground reference; and the
dielectric constant of the medium being measured.
ground reference also changes. The capacitance signal is
converted to a frequency proportional to the change in
Considering that the probe’s mounting position is fixed
level. The amplifier then converts this digital signal into
an isolated 4–20 mA analog output signal.
and the dielectric of the medium is constant, then the
amount of capacitance developed in any vessel becomes
dependent upon the amount of the probe which is covered with media.
S P E C I F I C A T I O N S
Supply voltage
Power consumption
Ambient temperature range
Humidity
Accuracy
Repeatability
Linearity
Temperature effect
Operator interface:
Data entry
Display
Continuous Output:
Active signal
Passive signal
Range
Damping
Discrete output (SPDT) with gold flash contacts:
Set point range
Adjustable differential range
Time delay
Relay output:
AC
DC
Maximum remote cable length:
Standard
Intrinsically safe
2
120 VAC, 50/60 Hz (+10 – 15%)
240 VAC, 50/60 Hz (+10 – 15%)
24 VDC (±10%)
15 VA nominal
-40° to +160° F (-40° to +70° C)
99% non-condensing (electronics)
Better than ±1.0%
±0.1%
±0.5%
±0.01%/° F (±0.018/° C)
16-button keypad
2 line × 16 character LCD display
4-20 mA (isolated), reversible, 1000 ohms max. loop resistance
4-20 mA (isolated), reversible, loop resistance
dependent on power supply
5 pF minimum; 50,000 pF maximum
0-90 seconds
0-50,000 pF
0.5 pF minimum; 50,000 pF maximum
0-90 seconds level rising, level falling, both
10 amp @ 120/240 VAC resistive
10 amp @ 30 VDC resistive
0.5 amp @ 125 VDC resistive
2500 feet (760 meters)
800 feet (240 meters)
A G E N C Y
A P P R O V A L S
Agency
Approved Model
Protection Method
Area Classification
FM
804-XXXX-23X
804-XXXX-33X
Insulated rigid probes only
Explosion proof
Class I Div. 1, Groups B, C & D
Class II, Div. 1, Groups E, F, & G
Class III
NEMA 4X, IP65
804-XXXX-53X
804-XXXX-63X
Explosion proof
with intrinsically safe
probe circuit
Integral units
Class I Div. 1, Groups B, C & D
Class II, Div. 1, Groups E, F, & G
Class III
NEMA 4X, IP65
Electronics
Class I Div. 1, Groups B, C & D
Class II, Div. 1, Groups E, F, & G
Class III
NEMA 4X, IP65
Remote probe
Class I Div. 1, Groups A, B, C & D
Class II, Div. 1, Groups E, F, & G
Class III, NEMA 4X, IP65
CSA
804-XXXX-23X
804-XXXX-33X
Insulated rigid probes only
804-XXXX-53X
804-XXXX-63X
Explosion proof
Explosion proof with intrinsically safe
probe circuit
Class I Div. 1, Groups C & D
Class II, Div. 1, Groups E, F, & G
Class III
TYPE 4X
Integral units with IS probe circuit
Class I Div. 1, Groups B, C & D
Class II, Div. 1, Groups E, F, & G Class III
TYPE 4X
Electronics
Class I Div. 1, Groups B, C & D
Class II, Div. 1, Groups E, F, & G Class III
TYPE 4X
Remote probe
Class I Div. 1, Groups A, B, C & D
Class II, Div. 1, Groups E, F, & G Class III
TYPE 4X
For Class II, Groups E & F insulated probes must be used
These units have been tested to EN 50081-2
and EN 50082-2 and are in compliance with
the EMC Directive 89/336/EEC.
3
D I M E N S I O N A L
I N C H E S
S P E C I F I C A T I O N S
( m m )
B
1 Rotation
clearance
A
B
1 Rotation
clearance
C
A
G
G
C
G
plugged
D
G
plugged
D
2
Optional
mounting
flange
Optional
mounting
flange
.1875 (5)
.2500 (6)
2
2.95
(75)
Integral Mount with Flexible Probe
.50 (13)
.625 (16)
Integral Mount with Standard Rigid Probe
4.63
(118) Dia.
3.00
(76)
2.75
(70)
3.23
(82)
3/4"
Optional
mounting
flange
NPT
2
.50 (13)
.625 (16)
Rigid Probe
4
D I M E N S I O N A L
I N C H E S
S P E C I F I C A T I O N S
( c o n t . )
( m m )
B
1 Rotation
clearance
A
E
G
G
2.37
(60)
2 Holes
.38 (10) Dia.
plugged
F
3.00
(76)
2.00
(51)
3.50
(89)
1/2"
NPT
or 3/4" NPT
3
Remote Mount
4.63
(118) Dia.
3.00
(76)
2.75
(70)
4.67
(119)
3/4"
Optional
mounting
flange
NPT
2
.1875 (5)
.2500 (6)
2.95
(75)
Flexible Probe
Outline Dimensions
Housing
NEMA 4X/7/9
Aluminum
A
B
3.87
(98)
5.93
(151)
Conduit
Connections
NEMA 4X/7/9
(remote probe housing)
Single conduit
NEMA 4X/7/9
Dual conduit
G
⁄4" NPT
3
1" NPT
C
10.89
(276)
Standard Rigid Probe
D
E
2.44
(61)
13.44
(341)
F
C
4.11
(104)
12.33
(313)
Flexible Probe
D
E
4.71
(119)
13.44
(341)
F
4.11
(104)
NOTES:
Allow 8.00 (200) overhead clearance for cover removal.
Standard process connection is 3⁄4" NPT. Consult probe bulletin (50-125) for
flange and other probe connections.
Probe/amplifier connecting cable to be shielded, twisted pair, 22-gauge stranded
conductors, Magnetrol part number 009-7146-001; 2500 feet (760 m) maximum;
800 feet (240 m) maximum for intrinsically safe models.
5
M O D E L
N U M B E R
Models available for quick shipment, usually within one week after factory
receipt of a purchase order, through the Expedite Ship Plan (ESP).
BASIC MODEL
804
Sentinel RF Level Transmitter
ELECTRONIC HOUSING
R
Y
NEMA 4X/7/9 aluminum, 1" NPT
NEMA 4X/7/9 aluminum, 1" NPT with 316 SS, remote housing
INPUT POWER
0
1
2
120 VAC
240 VAC
24 VDC
ANALOG OUTPUT/COMMUNICATIONS
1
5
4-20 mA
4-20 mA with RS-485 (Modbus)
ALARM/CONTROL OUTPUT
0
C
D
No relays
(2) 10 amp SPDT relays with gold flash contacts
(4) 10 amp SPDT relays with gold flash contacts
MOUNTING
2
Integral explosion proof
3
Remote explosion proof
5
6
Integral explosion proof w/IS safe probe circuit
Remote explosion proof w/IS safe probe circuit Not available with Electronic housing code Y
8
0
4
3
0
P R O B E S
R E M O T E
A full range of rigid and flexible probes, for conductive and non-conductive process media, is available
in various lengths and materials of construction. For
further information on probe assemblies, refer to
bulletin 50-125.
Remote cable should be shielded, twisted pair, 22-gauge
stranded conductors and may be ordered using
Magnetrol part number 009-7146-001. Cable length in
feet must be specified at time of order; 2500 feet (760m)
maximum; 800 feet (240 m) maximum for intrinsically
safe models.
6
C A B L E
N O T E S
7
Q U A L I T Y
The quality assurance system in place at
Magnetrol guarantees the highest level of
quality throughout the company. Magnetrol is
committed to providing full customer
satisfaction both in quality products and
quality service.
Magnetrol’s quality assurance system is registered to ISO 9001 affirming its commitment
to known international quality standards
providing the strongest assurance of product
and service quality available.
Several Kotron Model 804 RF transmitters are
available for quick shipment, usually within
one week after factory receipt of a purchase
order, through the Expedite Ship Plan (ESP).
ESP service may not apply to orders of ten
units or more. Contact your local representative for lead times on larger volume orders,
as well as other products and options.
E S P
Expedite
Ship
Plan
To take advantage of ESP, simply match the
color coded model number codes (standard
dimensions apply).
W A R R A N T Y
All Magnetrol electronic level and flow
controls are warranted free of defects in
materials or workmanship for one full year
from the date of original factory shipment.
If returned within the warranty period; and,
upon factory inspection of the control, the
cause of the claim is determined to be covered under the warranty; then, Magnetrol
will repair or replace the control at no cost
to the purchaser (or owner) other than
transportation.
Magnetrol shall not be liable for misapplication, labor claims, direct or consequential
damage or expense arising from the installation or use of equipment. There are no other
warranties expressed or implied, except special written warranties covering some
Magnetrol products.
For additional information, see Instruction Manual 50-604.
5300 Belmont Road • Downers Grove, Illinois 60515-4499 • 630-969-4000 • Fax 630-969-9489 • www.magnetrol.com
145 Jardin Drive, Units 1 & 2 • Concord, Ontario Canada L4K 1X7 • 905-738-9600 • Fax 905-738-1306
Heikensstraat 6 • B 9240 Zele, Belgium • 052 45.11.11 • Fax 052 45.09.93
Regent Business Ctr., Jubilee Rd. • Burgess Hill, Sussex RH15 9TL U.K. • 01444-871313 • Fax 01444-871317
Copyright © 2010 Magnetrol International, Incorporated. All rights reserved. Printed in the USA.
Performance specifications are effective with date of issue and are subject to change without notice.
BULLETIN: 50-118.3
EFFECTIVE: February 2001
SUPERSEDES: September 2000