MEANWELL MDR

60W Single Output Industrial DIN Rail Power Supply
MDR-60
series
Features :
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
NEC class 2 / LPS compliant (24V,48V only)
LED indicator for power on
DC OK relay contact
No load power consumption<0.75W
100% full load burn-in test
3 years warranty
SPECIFICATION
MODEL
MDR-60-5
MDR-60-12
MDR-60-24
MDR-60-48
DC VOLTAGE
5V
12V
24V
48V
RATED CURRENT
10A
5A
2.5A
1.25A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
0 ~ 2.5A
0 ~ 1.25A
RATED POWER
50W
RIPPLE & NOISE (max.) Note.2 80mVp-p
OUTPUT
12 ~ 15V
24 ~ 30V
2.0%
1.0%
1.0%
1.0%
LINE REGULATION
1.0%
1.0%
1.0%
1.0%
LOAD REGULATION
1.5%
1.0%
1.0%
1.0%
Note.5 500ms, 30ms/230VAC
HOLD UP TIME (Typ.)
50ms/230VAC
VOLTAGE RANGE
85 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
500ms, 30ms/115VAC at full load
20ms/115VAC at full load
120 ~ 370VDC
EFFICIENCY (Typ.)
78%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
1.8A/115VAC
1A/230VAC
COLD START 30A/115VAC
60A/230VAC
<1mA / 240VAC
OVERLOAD
PROTECTION
OVER VOLTAGE
FUNCTION DC OK SIGNAL
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
SAFETY &
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
EMC
ISOLATION RESISTANCE
(Note 4)
EMC EMISSION
EMC IMMUNITY
MTBF
DIMENSION
PACKING
NOTE
60W
200mVp-p
48 ~ 56V
5 ~ 6V
VOLTAGE ADJ. RANGE
LEAKAGE CURRENT
OTHERS
60W
150mVp-p
VOLTAGE TOLERANCE Note.3
SETUP, RISE TIME
INPUT
60W
120mVp-p
86%
88%
87%
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
6.25 ~ 7.25V
15.6 ~ 18V
31.2 ~ 36V
57.6 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
Relay contact rating(max.): 30V/1A resistive
-20 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6
UL508, UL60950-1, TUV EN60950-1 approved, NEC class 2 / LPS compliant (24V,48V only)
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
299.2K hrs min. MIL-HDBK-217F (25
40*90*100mm (W*H*D)
0.33Kg; 42pcs/14.8Kg/0.82CUFT
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
File Name:MDR-60-SPEC 2011-05-24
MDR-60
60W Single Output Industrial DIN Rail Power Supply
Mechanical Specification
Case No.962A
35
40
series
Unit:mm
100
5 5 5 5 5
+V +V -V -V
DC OK
DC OK
+
90
+V ADJ
N
L
7.5 7.5
Install DIN rail TS35/7.5 or TS35/15
Block Diagram
fosc : 60KHz
DC OK
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
O.C.P.
DETECTION
CIRCUIT
FG
CONTROL
O.L.P.
O.V.P.
DC OK Relay Contact
Contact Close
PSU turns on / DC OK.
Contact Open
PSU turns off / DC Fail.
Contact Ratings (max.) 30V/1A resistive load.
Derating Curve
Output Derating VS Input Voltage
Ta=25
100
100
12V,24V,48V
90
80
80
70
50
5V
LOAD (%)
LOAD (%)
60
40
20
-20
0
10
20
30
45
55
AMBIENT TEMPERATURE ( )
60
70 (VERTICAL)
60
50
40
85
95
100
115
120
140
160
180
200
220
240
264
INPUT VOLTAGE (VAC) 60Hz
File Name:MDR-60-SPEC 2011-05-24