MEANWELL TN

TN-3000
3000W True Sine Wave DC-AC Inverter with Solar Charger
series
Features :
True sine wave output (THD<3%)
High surge power up to 6000W
U.P.S. mode and energy saving mode (selectable)
High efficiency up to 92%
Power ON-OFF switch
Standby saving mode can be selectable
Front panel indicator for operation status
Thermostatically controlled cooling fan
Protections: Bat. low alarm / Bat. low shutdown / Over voltage / Over temp.
/ Output short / Input polarity reverse / Overload / AC circuit breaker
Application : Home appliance, power tools, office and portable
equipment, vehicle and yacht ...etc.
Built-in solar / AC charger
Optional monitoring software and connection cable
(MW order No.: DS-TN-1500)
3 years warranty
E13
SPECIFICATION
MODEL
TN-3000-112
TN-3000-124
TN-3000-148
TN-3000-212
TN-3000-224
TN-3000-248
3000W
RATED POWER (Typ.)
MAXIMUM OUTPUT POWER (Typ.) 3450W for 180 sec. / 4500W for 10 sec. / surge power 6000W for 30 cycles
Factory setting set at 110VAC
AC VOLTAGE
OUTPUT
200 / 220 / 230 / 240VAC selectable by setting button S.W
FREQUENCY
60 0.1Hz
50 0.1Hz
WAVEFORM
True sine wave (THD<3%) at rated input voltage
50/60Hz selectable by setting button S.W
TRANSFER TIME (Typ.)
10ms inverter
SAVING MODE (Typ.)
Load
by pass
5W will be changed to standby mode
FRONT PANEL INDICATOR
Battery voltage level, output load level, saving mode, fault and operation status
BAT. VOLTAGE
12V
VOLTAGE RANGE (Typ.) Note.3,6 10.5 ~ 15VDC
DC CURRENT (Typ.)
Note.4 300A
24V
48V
12V
24V
48V
21 ~ 30VDC
150A
42 ~ 60VDC
75A
10.5 ~ 15VDC
21 ~ 30VDC
42 ~ 60VDC
300A
150A
75A
91%
89%
91%
92%
20A*6
45V
40A*12
11.3V
40A*6
22.5V
20A*6
45V
42V
10.5V
21V
42V
NO LOAD DISSIPATION (Typ.)
10W @ standby saving mode
OFF MODE CURRENT DRAW (Typ.)
1mA
EFFICIENCY (Typ.)
Note.1 88%
90%
Open & sealed lead acid battery
BATTERY TYPES
FUSE
40A*12
40A*6
BATTERY BAT. LOW ALARM
22.5V
Note.6 11.3V
INPUT
21V
PROTECTION BAT. LOW SHUTDOWN Note.6 10.5V
By internal fuse open
REVERSE POLARITY
90
OVER TEMPERATURE
SAFETY &
EMC
WORKING HUMIDITY
85
5
85
5
75
5
75
5
Protection type : Shut down o/p voltage, re-power on to recover
AC output: 20A, AC receptacle: 15A
AC output: 40A, AC receptacle:15A
Optional (Only type F)
Note.2 0 ~ +40 @ 100% load ; 60 @ 50% load
20% ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY
VIBRATION
-30 ~ +70
None
o
/ -22 ~ +158 F, 10 ~ 95% RH
SAFETY STANDARDS
10 ~ 500Hz, 3G 10min./1cycle, 60min. each along X, Y, Z axes
UL458 (only for "GFCI" receptacle-Type F ) None
LVD
WITHSTAND VOLTAGE
None
Bat I/P - AC I/P:3.0KVAC
ISOLATION RESISTANCE
Bat I/P - AC O/P, Bat I/P - FG, AC O/P - FG: 100M ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 class A, 72/ 245/ CEE, 95/ 54/ CE, E-Mark
25A
AC
CHARGER
CHARGE CURRENT (Typ.)
SOLAR
PANEL
MAX OPEN CIRCUIT VOLTAGE 25V
NOTE
80
Protection type : Shut down o/p voltage, re-power on to recover
Bat I/P - AC O/P:3.0KVAC
EMI CONDUCTION&RADIATION Compliance to FCC class A
None
EMS IMMUNITY
OTHERS
5
105 ~ 115% load for 180 sec., 115% ~ 150% load for 10 sec.
CIRCUIT BREAKER
GFCI PROCTECTION
WORKING TEMP.
5
Protection type : Shut down o/p voltage, re-power on to recover
OUTPUT SHORT
OUTPUT
PROTECTION OVER LOAD (Typ.)
ENVIRONMENT
50/60Hz selectable by setting button S.W
3%
AC REGULATION (Typ.)
INPUT
Factory setting set at 230VAC
100 / 110 / 115 / 120VAC selectable by setting button S.W
CHARGE VOLTAGE
Note.6 14.3V
EN60950-1
AC O/P - FG:1.5KVAC
Compliance to EN61000-4-2,3,4,5,6,8,11 ENV50204
12A
6A
25A
12A
6A
28.5V
57V
14.3V
28.5V
57V
45V
75V
25V
45V
75V
SHORT CIRCUIT CURRENT (max.) 30A
RJ11 -RS232 (Option)
CONTROL WIRING
DIMENSION
PACKING
466.8*283.5*100mm (L*W*H)
12.9Kg; 1pcs/14Kg/1.98CUFT
1.Efficiency is tested by 2100W, linear load at 13V, 26V, 52V input voltage.
2.Output derating capacity referenced by curve 1.
3.Output derating capacity referenced by curve 2.
4.DC current is tested by 3000W, linear load at 12V, 24V, 48V input voltage.
5.All parameters not specified above are measured at rated load, 25 of ambient temperature.
6.The tolerance of each voltage value by models is:112/212
0.5V;124/224
1V;148/248
2V
File Name:TN-3000-SPEC 2011-02-09
3000W True Sine Wave DC-AC Inverter with Solar Charger
TN-3000
series
Instructions for TN-3000 monitoring software
1. Installation of TN-3000 unit and PC
9
8
7
6
1
6
5
4
3
2
1
Phone Jack
RJ11
DB9 FEMALE
RJ11
PIN NO.
DB9
PIN NO.
2
3
4
3
5
2
Figure 1
2. Explanation of Monitoring Manu
2.1 Main Page
Inverter TN V1.38
Setting
Statistics
R.C. Power off
Pause
2
3
4
1
Exit
Solar Charge
INVERTER
100
AC Charge
100
0
Battery
5
0
Loading
O/P Voltage 230 V
O/P Frequency 50.0 Hz
Battery Voltage 13.5 V
Internal Temperature 10.0
AC In
By pass
Utility Voltage 0.0 V
TN-3000-212
6
Start Date 2010/01/01 03:13:33 PM
Reset Date 2010/01/01 01:40:56 PM
Power on
Remote off
Battery low
Battery used up
Stand by saving mode
Abnormal Shutdown
Figure 2
1. Setting: Adjustment for output voltage, charging related voltage, frequency, and operation mode. Please refer to Figure 3 for details.
2. Statistics: Calculate for the percentage of operating period for each operation mode. Please refer to Figure 4 for details.
3. R.C. Power off: Power can be turned ON or OFF at the remote location.
4. Pause: Stop refreshing the page of monitoring software.
5. Status of unit: Indicating current operating status of TN-3000.
6. Signals that display current condition of the unit.
File Name:TN-3000-SPEC 2011-02-09
3000W True Sine Wave DC-AC Inverter with Solar Charger
TN-3000
series
2.2 Setting Page
Inverter Setting
File Name D:\TN_110RR\20100101\REV\TN_110RR\TNF\TN_3K0_512.TNF
Model name TN-3000-212
Manufacture MeanWell
Series Number
LOC-1234567890
Revision REV:1.38
Date Of Manu.
01/01/2010
I/O Type
212
Voltage
230
V
Equalization Volt.
14.3
V
13.6 ~ 15.0V
Floating Volt.
13.3
V
13.0 ~ 13.5V
Alarm Volt.
11.3
V
11.1 ~ 11.5V
Shutdown Volt.
10.5
V
10.0 ~ 11.0V
1
Frequency
Stand-by saving mode
UPS mode
Energy saving mode
50
Hz
Off
On
On
On
Comm Ports
Bauds Rate 9600
1
Read
Write
Lead
2
3
4
Exit
Read OK!!
Figure 3
1. User can adjust the settings based on the characteristics of batteries been used: Equalization Voltage, Floating Voltage, Alarm Voltage,
and Shut-down Voltage. UPS Mode / Energy Saving Mode selection and AC output voltage and frequency can also be set in this page.
2. Read: Read current settings of the unit.
3. Write: Write the revised setting into the unit.
4. Load: Load in factory default settings.
2.3 Statistic Page
Inverter Setting
Start Date 2010/01/01 03:13:33 PM
Inverter time rate
91.2 %
Bypass time rate
0.0 %
Shut Down rate
8.8 %
Solar time rate
0.0 %
Loading average
24.7 %
Start Date 2010/01/01 01:40:56 PM
Inverter time rate
31.9 %
Bypass time rate
0.0 %
Shut Down rate
68.1 %
Solar time rate
0.0 %
Loading average
63.7 %
RESET
Exit
Figure 4
1. Start Date: Date that installing the monitoring software.
2. Reset Date: Date that resetting the statistics. The Start Date will not be influenced by resetting the statistics or turning off the unit.
3 .Inverter time rate: Operating period of "Inverter Mode" represents how many percent of the whole operating period.
4. Bypass time rate: Operating period of "Bypass Mode" (energy provides directly by the utility) represents how many percent of the whole
operating period.
5. Shut down rate: Percentage of time period that the unit is under the condition of shut down.
* Inverter time rate + Bypass time rate + Shut down rate = 100%
6. Solar time rate: Percentage of time period that the solar charger is functioning after turning on the TN-3000 unit.
7. Loading average: Average loading after turning on the TN-3000 unit.
File Name:TN-3000-SPEC 2011-02-09
TN-3000
3000W True Sine Wave DC-AC Inverter with Solar Charger
TN
3000
112 A
True sine wave inverter
+AC charger and solar charger
A :TYPE A OUTLET
B :TYPE B OUTLET
C :TYPE C OUTLET
D :TYPE D OUTLET
E :TYPE E OUTLET
F :TYPE F OUTLET
12:12VDC
Bat. Voltage: 24:24VDC
48:48VDC
Output:
O/P Wattage:3000W
series
1:110VAC
2:230VAC
AC Output Receptacle (optional)
Receptacle type
TYPE-A
TYPE-B
TYPE-C
TYPE-D
TYPE-E
TYPE-F
USA
EUROPE
AUSTRALIA
U.K
JAPAN
GFCI
Country
E13
Certificate
E13
E13
(Expect for 48V input)
Derating Curve
Mechanical Specification
Unit:mm
161.84
122.44
100
LOAD (%)
POS
100
31.6
80
NEG
Reverse Polarity
Will Damage The
Unit.
29
60
40
20
129.63
-
46
Air flow
direction
0
+
+
+
10
20
30
40
50
60
70
AMBIENT TEMPERATURE ( )
CURVE 1
Air flow
direction
100
LOAD (%)
90.3
80
7
7.5
60
40
20
10.5VDC
11.5VDC
15VDC
(HORIZONTAL)
AC Receptacle
466.8
286.2
BATTERY INPUT VOLTAGE (V)
CURVE 2
SOLAR CHARGE
ON
AC CHARGE
OFF
100
r
R
Ci
s
t o
R
e
Bat Low
AC IN
BY PASS
Saving
(For Receptacle)
(For AC Output)
Chassis
Ground
Setting
0
t
e
100
On
0
se
r
Ci
t
se
t o
e
e
s
er
Pr
Pr
er
s
s
LOAD
BATTERY
INVERTER
i t Br e
ak
cu
i t Br e
ak
cu
Cat.No.(1GG1HS-212)
Wire Range(10-4 AWG Str
Cu Soldered Wires)
Torque (17.7-26.5 in lb)
13
Remote
port
AC INTPUT
AC OUTPUT
31.29
Type-A
AC INPUT
L
N
AC OUTPUT
L
Note: When the load current is >15A, must
use output terminal connection which
can be found inside the AC output panel
of the inverter.
FG
N
AC Receptacle
SOLAR CHARGE
ON
AC CHARGE
OFF
100
r
Ci
t
se
e
LOAD
100
Setting
On
0
t
0
Bat Low
se
r
Ci
12
34
R
s
e
e
283.5
t o
er
Pr
s
s
t o
R
e
AC IN
BY PASS
Saving
(For Receptacle)
(For AC Output)
Chassis
Ground
Cat.No.(1GG1HS-212)
Wire Range(10-4 AWG Str
Cu Soldered Wires)
Torque (17.7-26.5 in lb)
Remote
port
13
273
Pr
er
s
BATTERY
INVERTER
i t Br e
ak
cu
i t Br e
ak
cu
AC INTPUT
AC OUTPUT
31.29
Type-B
File Name:TN-3000-SPEC 2011-02-09