ALLEN-BRADLEY 100S

Contactors & Control Relays
Safety Contactors
100S-D
Specifications
Conformity to Standards
IEC 60947-4
IEC 60947-4 Annex F
IEC 60947 Type “2” Coordination
CSA 22.2 No. 14
UL 508
Approvals
Description
Bulletin 100S-D safety contactors are designed to provide safe
isolation of hazardous motion loads, utilizing “mirror contact”
performance. Mirror contacts provide reliable indication about the
open/closed status of the main power poles.
Features
CE marked for all applicable directives
CSA Certified
UL Listed
SUVA Certified
•
•
•
•
45…220 kW @500V
60…600 Hp @460V
75…700 Hp @575V
Electronic and Conventional Coils
AC & DC
Integrated PLC Interface
Low Power Pick-Up & Hold-In
Wide Voltage Ranges
• Complete Range of Accessories
• Environmentally-Friendly
• Compact Dimensions
9-9
Contactors & Control Relays
Safety Contactors
100S-D
Product Selection
3-pole AC Contactors
• Conventional and Electronic AC Coils
• 3 Main Contacts
• Non-Reversing
Ie [A]
60°C
Switching of 3-Phase Motors—AC-2, AC-3
40°C
kW (50 Hz)
AC-3 AC-1 230V 400V 415V
⊗
Auxiliary Contacts
Hp (60 Hz)
500V
690V
N.C. ➊
N.O.
1000V 200V 230V 460V 575V
Catalogue Number
95
160
25
50
50
55
80
45
25
30
60
75
2
2
100S-D95⊗22C
110
160
32
55
55
63
100
55
40
40
75
100
2
2
100S-D110⊗22C
140
250
45
75
75
80/90➌ 110/132➌
75
40
50
100
125
2
2
100S-D140⊗22C
180
250
55
90
100
90/110➌ 132/160➌
90
50
60
150
150
2
2
100S-D180⊗22C
210
350
63
110
110
150
200
110
60
75
150
200
2
2
100S-D210⊗22C
250
350
80
132
150
160
250
133
75
100
200
250
2
2
100S-D250⊗22C
300
450
90
160
160
200
300
163
100
125
250
300
2
2
100S-D300⊗22C
420
500
132
220
250
300
425
225
150
175
350
400
2
2
100S-D420⊗22C
630
800
200
355
355
450
500
425
200
250
500
600
2
2
100S-D630⊗22C
860
1000
250
500
500
560
600
425
250
300
600
700
2
2
100S-D860⊗22C
AC Coil Voltage Code
The Catalogue Number as listed is incomplete. Select a coil voltage code from the table below to complete the Catalogue Number. Example: 120V 60 Hz:
Catalogue Number 104S-C09⊗210C becomes Catalogue Number 104S-C09D210C.
Conventional Coil
V
24
48
100
110
120
200
208
220…
230
230
240
277
380…
400
415
440
480
500
550
600
100S-D95…
100S-D180
50 Hz
K
Y
—
D
—
—
—
A
—
T
—
N
B
G
—
M
C
—
60 Hz
J
X
—
—
D
—
H
—
—
A
T
—
—
N
B
—
—
C
50/60 Hz
KJ
—
KP
KN
—
KG
—
—
KF
KA
—
—
—
—
—
—
—
—
V
24
42…
64
100
110…
130
200
208…
277
380…
415
440…
480
500
600
100S-D95…
100S-D250
50/60 Hz
EJ
EY
EP
ED
EG
EA
EN
EN
EN
—
100S-D300…
100S-D420
50/60 Hz
—
EY
EP
ED
EG
EA
EN
EN
EN
—
100S-D630…
100S-D860
50/60 Hz
—
—
EP
ED
EG
EA
EN
EB
EM
EC
100S-D95…
100S-D110
Electronic Coil
w/PLC Interface ➋
➊ The N.C. contacts meet IEC 60947-4 Annex F requirements to mirror contact performance. The N.C. mirror contacts are wired in series or parallel and must
be used as monitoring contacts with feedback to the safety circuit.
➋ Signal voltage of the Cat. No. 100S-D… electronic interface:Ue: 24V DC/Ie: 15 mA
Pick-Up Voltage: 13.0V DC…30.2V DC
Drop-Out Voltage: -3.0V DC…+5.0V DC
➌ Higher kW rating only applies to contactors with electronic coil.
9-10
Contactors & Control Relays
Safety Contactors
100S-D
Product Selection
3-Pole DC Contactors
• Conventional and Electronic DC Coils
• 3 Main Contacts
• Non-Reversing
Ie [A]
60°C
Switching of 3-Phase Motors—AC-2, AC-3
40°C
kW (50 Hz)
Auxiliary Contacts
Hp (60 Hz)
N.O.
N.C. ➊
3
2/1L
AC-3 AC-1 230V 400V 415V 500V 690V 1000V 200V 230V 460V 575V
95
110
140
⊗
160
25
160
32
250
45
50
50
55
55
75
75
55
80
63
100
80
110
90 ➍ 132 ➍
90
132
45
55
25
30
40
40
60
75
75
100
Catalogue Number
100S-D95⊗33LC ➋
2
2
100S-D95⊗22C
3
2/1L
100S-D110⊗33LC ➋
2
2
100S-D110⊗22C
3
2/1L
100S-D140⊗33LC ➋
2
2
100S-D140⊗22C
75
40
50
100
125
90
50
60
150
150
2
2
100S-D180⊗22C
180
250
55
90
100
210
350
63
110
110
150
200
110
60
75
150
200
2
2
100S-D210⊗22C
250
350
80
132
150
160
250
133
75
100
200
250
2
2
100S-D250⊗22C
300
450
90
160
160
200
300
163
100
125
250
300
2
2
100S-D300⊗22C
420
500
132
220
250
300
425
225
150
175
350
400
2
2
100S-D420⊗22C
630
800
200
355
355
450
500
425
200
250
500
600
2
2
100S-D630⊗22C
860
1000
250
500
500
560
600
425
250
300
600
700
2
2
100S-D860⊗22C
110 ➍ 160 ➍
AC Coil Voltage Code
The Catalogue Number as listed is incomplete. Select a coil voltage code from the table below to complete the Catalogue Number. Example: 120V 60 Hz:
Catalogue Number 104S-C09⊗210C becomes Catalogue Number 104S-C09D210C.
Conventional Coil
V
24
48
110
125
220
250
100S-D95…100S-D140 ➋
DC
ZJ
ZY
ZD
ZS
ZA
ZT
Electronic Coil
w/EI Interface ➌
V
24
48…72
110…130
200…255
100S-D95…100S-D300
DC
EZJ
EZY
EZD
EZA
100S-D420
DC
—
EZY
EZD
EZA
100S-D630…860
DC
—
—
ED
EA
➊ The N.C. contacts meet IEC 60947-4 Annex F requirements to mirror contact performance. The N.C. mirror contacts are wired in series or parallel and must
be used as monitoring contacts with feedback to the safety circuit.
➋ For conventional DC coil only. The pickup winding must be interconnected with the N.C. late-breaking auxiliary contacts.
➌ Signal voltage of the Cat. No. 100S-D… electronic interface:Ue: 24V DC/Ie: 15 mA
Pick-Up Voltage: 13.0V DC…30.2V DC
Drop-Out Voltage: -3.0V DC…+5.0V DC
➍ Higher kW rating only applies to contactors with electronic coil.
9-11
Contactors & Control Relays
Safety Contactors
100S-C
General Ratings
Catalogue Number 100S-C09...100S-C85
Rated Isolation Voltage Ui
IEC, AS, BS, SEV, VDE 0660; UL; CSA
690V
600V
Rated Impulse Voltage Uimp
8 kV
Rated Voltage Ue Main Contacts
AC 50/60Hz
115, 200, 208, 230, 240, 380, 400, 415, 460, 500, 575, 690V
DC
24, 48, 110, 115, 220, 230, 300, 440V
Operating Frequency for AC Loads
50…60 Hz
Switching Motor Loads
Catalogue
Number
100SC09
100SC12
100SC16
100SC23
100SC30
100SC37
100SC43
100SC60
100SC72
100SC85
Standard Ratings
AC-2, AC-3, AC-4-50Hz
DOL & Reversing
IEC
AC-2, AC-3, AC-4-60Hz
DOL & Reversing
UL/CSA/IEC
9-12
230V
[A]
12
15
20
26.5
25
38
44
62
72
85
240V
[A]
12
15
20
26.5
35
38
44
62
72
85
400V
[A]
9
12
16
23
30
37
43
60
72
85
415V
[A]
9
12
16
23
30
37
43
60
72
85
500V
[A]
7
10
14
20
25
30
38
55
67
80
690V
[A]
5
7
9
12
18
21
25
34
42
49
230V
[kW]
3
4
5.5
7.5
10
11
13
18.5
22
25
240V
[kW]
3
4
5.5
7.5
10
11
13
18.5
22
25
400V
[kW]
4
5.5
7.5
11
15
18.5
22
32
40
45
415V
[kW]
4
5.5
7.5
11
15
20
22
32
40
45
500V
[kW]
4
5.5
7.5
13
15
20
25
37
45
55
690V
[kW]
4
5.5
7.5
10
15
18.5
22
32
40
45
1-Ph 115V
[A]
9.8
9.8
16
24
24
34
34
56
56
80
230V
[A]
10
12
17
17
28
28
40
50
68
68
115 V
[HP]
1/2
1/2
1
2
2
3
3
5
5
7-1/2
230 V
[HP]
1 1/2
2
3
3
5
5
7-1/2
10
15
15
3-Ph 200V
[A]
7.8
11
17.5
17.5
25.3
32.2
32.2
48.3
62.1
78.2
230 V
[A]
6.8
9.6
15.2
22
28
28
42
54
68
80
460 V
[A]
7.6
11
14
21
27
34
40
52
65
77
575 V
[A]
9
11
17
17
27
32
32
52
62
62
200 V
[HP]
2
3
5
5
7-1/2
10
10
15
20
25
230 V
[HP]
2
3
5
7-1/2
10
10
15
20
25
30
460 V
[HP]
5
7-1/2
10
15
20
25
30
40
50
60
575 V
[HP]
7-1/2
10
15
15
25
30
30
50
60
60
Contactors & Control Relays
Safety Contactors
100S-D
General Ratings
Catalogue Number 100S-D95...100S-D860
Rated Isolation Voltage Ui
IEC, AS, BS, SEV, VDE 0660; UL; CSA
690V
600V
Rated Impulse Voltage Uimp
12kV
Rated Voltage Ue Main Contacts
AC 50/60Hz
115, 200, 208, 230, 240, 380, 400, 415, 460, 500, 575, 690, 1000V
DC
24, 48, 110, 115, 220, 230, 300, 440V
Operating Frequency for AC Loads
50…60 Hz
Switching Motor Loads
Catalogue
Number
100SD95
100SD110
100SD140
100SD140
100SD180
100SD180
100SD210
100SD250
100SD300
100SD420
100SD630
100SD860
Conventional
X
Electronic-EI
X
X
X
X
—
—
X
—
—
—
—
—
—
—
X
—
X
X
X
X
X
X
230V
[A]
95
110
X
140
140
180
180
210
250
300
420
630
860
240V
400V
[A]
95
[A]
95
110
140
140
180
180
210
250
300
420
630
860
110
140
140
180
180
210
250
300
420
630
415V
[A]
860
95
110
140
140
180
180
210
250
300
420
630
500V
860
[A]
95
110
115
140
140
180
210
250
300
420
630
690V
753
[A]
95
110
115
140
140
180
210
250
300
420
1000V
[A]
33
40
55
55
65
65
80
95
115
160
230V
[kW]
25
32
45
45
57
57
67
80
97
135
200
250
240V
[kW]
25
32
45
45
60
60
70
83
101
141
200
250
400V
[kW]
45
55
75
75
101
101
118
140
170
238
355
500
415V
[kW]
45
55
80
80
105
105
122
145
174
250
355
500
500V
[kW]
55
63
80
90
98
126
150
177
213
300
450
560
690V
[kW]
80
100
110
132
135
176
205
250
300
425
—
Coil Type
Standard Ratings
AC-2, AC-3, AC-4-50Hz
DOL & Reversing
IEC
AC-2, AC-3, AC-4-60Hz
DOL & Reversing
UL/CSA/IEC
1000V
[kW]
45
55
75
75
90
90
110
132
160
225
1-Ph 115V
[A]
80
100
135
135
—
—
—
—
—
—
—
230V
[A]
68
110
136
136
176
176
216
—
—
—
—
—
115 V
[HP]
7.5
10
15
15
—
—
—
—
—
—
—
—
230 V
[HP]
15
25
30
30
40
40
50
—
—
—
—
—
3-Ph 200V
[A]
78.2
120
120
120
150
150
177
221
285
414
552
692
230 V
[A]
80
104
130
130
154
154
192
248
312
420
602
720
460 V
[A]
77
96
124
124
180
180
180
240
302
414
590
702
575 V
[A]
77
99
125
125
144
144
192
242
289
382
562
651
200 V
[HP]
25
40
40
40
50
50
60
75
100
150
200
250
230 V
[HP]
30
40
50
50
60
60
75
100
125
175
250
300
460 V
[HP]
60
75
100
100
150
150
150
200
250
350
500
600
575 V
[HP]
75
100
125
125
150
150
200
250
300
400
600
700
9-13
Contactors & Control Relays
Safety Contactors
100S-C
Coil Data
Catalogue
Number
100S-C09
100SC12
100SC16
100SC23
100SC30
Voltage Range
100SC37
100SC43
100SC60
100SC72
100SC85
0.85…1.1
Pick-up
[x Us]
Dropout
[x Us]
Pick-up
[x Us]
Dropout
[x Us]
Pick-up
[VA/W]
70/50
70/50
70/50
70/50
80/60
80/60
130/90
200/110
200/110
200/110
Hold-in
[VA/W]
8/2.6
8/2.6
8/2.6
9/3
9/3
9/3
10/3.2
16/4.5
16/4.5
16/4.5
Pick-up
[W]
6.5
6.5
6.5
9.2
9.2
9.2
10.1
200
200
200
Hold-in
[W]
6.5
6.5
6.5
9.2
9.2
9.2
10.1
4.5
4.5
4.5
Operating Time
AC: 50 Hz, 60 Hz,
50/60 Hz
Pick-up
[ms]
15…30
15…30
15…30
15…30
15…30
15…30
15…30
20…40
20…40
20…40
Dropout
[ms]
10…60
10…60
10…60
10…60
10…60
10…60
10…60
10…60
10…60
10…60
with RC Suppressor
Dropout
[ms]
10…60
10…60
10…60
10…60
10…60
10…60
10…60
10…60
10…60
10…60
Pick-up
[ms]
40…70
40…70
40…70
40…70
50…80
50…80
50…80
20…40
20…40
20…40
Dropout
[ms]
7…15
7…15
7…15
7…15
7…15
7…15
7…15
—
—
—
with Integ. Suppres.
Dropout
[ms]
14…20
14…20
14…20
17…23
17…23
17…23
17…23
20…35
20…35
20…35
with Diode Suppres.
Dropout
[ms]
70…95
70…95
70…95
80…125
80...125
80...125
80...125
80...125
80...125
80...125
AC: 50 Hz, 60 Hz,
50/60 Hz
DC
0.3…0.6
0.8…1.1
0.1…0.6
Coil Consumption
AC: 50 Hz, 60 Hz,
50/60 Hz
DC
DC
9-14
Contactors & Control Relays
Safety Contactors
100S-D
Coil Data
Catalogue
Number
100SD95
100SD110
100SD140
100SD140
100SD180
100SD180
100SD210
100SD250
100SD300
100SD420
100S-D630
100S-D860
Conventional
X
X
X
—
X
—
—
—
—
—
—
—
X
X
X
Coil Type
Electronic-EI
X
X
—
X
—
Voltage Range
AC: 50 Hz, 60 Hz,
50/60 Hz
Pick-up
[x Us]
Dropout
[x Us]
Pick-up
[x Us]
Dropout
[x Us]
Pick-up
[VA/W]
Hold-in
[VA/W]
DC
DC
Pick-up
[W]
Hold-in
[W]
X
X
X
0.85…1.1
0.85…1.1
0.3…0.5
0.3…0.8
0.85…1.1
0.80…1.1
0.3…0.5
0.3…0.8
370/243 ➊
Coil Consumption
AC: 50 Hz, 60 Hz,
50/60 Hz
X
590/355➊
1915/1720 ➊
12/6
15/7
33/30
190 ➊
375 ➊
1980 ➊
6
7
30
75…90
75…90
60…100
30…60
30…60
70…145
Operating Time
AC: 50 Hz, 60 Hz,
50/60 Hz
Pick-up
[ms]
Dropout
[ms]
with RC Suppressor
Dropout
[ms]
—
—
—
Pick-up
[ms]
75…90
75…90
60…100
30…60
30…60
70…145
—
—
—
—
—
—
DC
Dropout
[ms]
with Integ. Suppres.
Dropout
[ms]
with Diode Suppres.
Dropout
[ms]
➊ Electronic coil drives are designed to minimize coil consumption. However, this design may cause a large inrush (<1ms) when energizing. This must be taken into account
when sizing power supplies, all-or-nothing relays and the cross-sections of the coil wires.
9-15
Contactors & Control Relays
Safety Contactors
Connections
3-Pole Safety Contactors
51 61 71 81
51 61 71 81
11 21 31 41
52 62 72 82
52 62 72 82
12 22 32 42
1
3
5
21
1
3
5
13
1
3
5
2
4
6
22
2
4
6
14
2
4
6
100S-C09⊗05C...C23⊗05C
100S-C09⊗14C...C23⊗14C
100S-C30⊗04C...C85⊗04C
4-Pole Safety Contactors
11 21 31 41
11 21 31 41
12 22 32 42
12 22 32 42
1
3
5
7
1
3
5
R7
2
4
6
8
2
4
6
R8
100S-C09⊗404C...C23⊗404C
100S-C09⊗304C...C23⊗304C
Reversing Safety Contactors
51 61 71 81
21
51 61 71 81
11 21 31 41
21
11 21 31 41
52 62 72 82
22
52 62 72 82
12 22 32 42
22
12 22 32 42
1
3
5
13
21
1
3
5
13
1
3
5
21
1
3
5
2
4
6
14
22
2
4
6
14
2
4
6
22
2
4
6
104S-C09⊗210C...C23⊗210C
9-16
104S-C30⊗010C...C85⊗010C