ALLEN-BRADLEY 700

Bulletin 700-SK
Solid-State Relays
Overview/Product Selection
Bulletin 700-SK
Table Of Contents
•
•
Product Selection . . . . . . . . 58
Accessories . . . . . . . . . . . . 58
Specifications . . . . . . . . . . . 60
Approximate
Dimensions . . . . . . . . . . . . . 62
•
•
•
High Response Speed Models
Input Sensor Module to Allow High Voltage 100…240V AC or 12…24V DC Sensor
Interface to Low Voltage (Logic) Device Such as a PC
Output Module For Typical SSR Applications
LED Indicator
Input Modules and Output Modules Can Be Used With the 700-HN121 Socket
Product Selection
Input/Sensor Module
Input-to-Output
Isolation Method
LED Indicator
Photocoupler
Yes
Response
Speed
Logic Level
Supply
Voltage
Supply
Current
4…32V DC
0.1…100 mA
10 Hz
High-speed
(1 kHz)
Rated Input Sensor
Voltage
Cat. No.
Factory-stocked
item
(Single Pack)
100…240V AC
700-SKICA18
✔
12…24V DC
700-SKICZ24
✔
Output/SSR Module
Input-to-Output
Isolation Method
Phototriac
Photocoupler
58
Zero
Cross Function
LED
Indicator
Yes
No
N/A
Rated
Output (Load) Max.
Current and Voltage
Range
Rated
Input Control Voltage
2 A at 100…240V AC
Yes
2 A at 5…48V DC
1.5 A at 48…200V DC
5…24V DC
Cat. No.
Factory-stocked
item
(Single Pack)
700-SKOZ2Z25
✔
700-SKON2Z25
✔
700-SKOC2Z25
✔
700-SKOC1Z25
✔
Bulletin 700-SK
Solid-State Relays
Accessories
Description
Pcs./Pkg.
Cat. No.
Factory-stocked
Item
Screw Terminal Socket — Panel
or DIN Rail Mounting
Order must be in multiples of ten
10
700-HN121
✔
DIN Rail Mounting Pack
Standard 35 x 7.5 mm DIN Rail, 1
meter long, 10 rails per package.
Order must be for 10 rails or
multiples of 10.
10
199-DR1
✔
10
700-N40
10
700-N41
Cat No. 700-HN121
Cat No. 199-DR1
Pre-printed identification tags —
contains 10 sheets of pre-printed
and blank tags. Each sheet
contains 13 sets of the markings
CR…9CR, TR…9TR, M…9M, F, R,
1S, and 117 blank tags. Tags are
peel-off with sticky backing for easy
placement on relays.
Blank identification tags —
contains 10 sheets of blank
identification tags for customer
specialized printing. Each sheet
contains 546 blank tags. Tags are
peel-off with sticky backing for easy
placement on relays.
59
Bulletin 700-SK
Solid-State Relays
Specifications
Input Sensor Module
Input Sensor Ratings
Rated Input
Voltage
Cat, No.
Operating
Voltage Range
Input
Current
Pick-up Voltage
Drop-out Voltage
700-SKICZ24
12…24V DC
6.6…32V DC
8 mA max.
6.6V DC max.
3.6V DC min.
700-SKICA18
100…240V AC
60…264V AC
15 mA max.
60V AC max.
20V AC min.
Output Logic Ratings
Cat. No.
700-SKICZ24
700-SKICA18
Logic Level
Supply Voltage
Logic Level
Supply Current Draw
4…32V DC
0.1…100 mA
Characteristics
700-SKICA18
700-SKICZ24
Pick-up time
Cat. No.
20 ms max.
0.1 ms max.
Drop-out time
20 ms max.
0.1 ms max.
Response frequency
10 Hz
1 kHz
Output ON voltage drop
1.6 V max.
5 µA max.
Leakage current
VDRM VCEO (V)
80 (ref. value)
80 (ref. value)
Output di/dt (A/uS)
—
—
Output dv/dt (V/uS)
—
—
Output I2t (A2S)
—
—
Output Tj (°C) Max.
150
150
Insulation resistance
100 MΩ min. between input and output
Dielectric strength
4,000V AC, 50/60 Hz for 1 min. between input and output
Vibration resistance (max.)
Shock resistance
10…55 Hz, 1.5 mm double amplitude (10 G)
1,000 m/s2
(max.)
Ambient temperature
Operating
Storage
(100 G)
–30…80°C (–22…176°F) with no icing or condensation
–30…100°C (–22…212°F) with no icing or condensation
UL 508
CSA C22.2
CE, TÜV
Standards
Ambient humidity
Operating
45…85% (No condensation)
Weight
Approx. 18 g
Output SSR Module
Control/Input Ratings
Cat. No.
Rated Control Voltage
Operating Control Voltage Range
Impedance➊
4…32V DC
15 mA max.
at 25°C
(77°F)
700-SKOZ2Z25
700-SKON2Z25
5…24V DC
700-SKOC2Z25
Pick-up
Voltage
Drop-out
Voltage
4V DC
max.
1V DC min.
8 mA max.
700-SKOC1Z25
Load/Output Ratings
Continuous Load Current
(Resistive)
Max. Inrush Current➋
Cat. No.
Rated Load Voltage
Load Voltage Range
—
—
—
Min.
Max.➌
—
100…240V AC
75…264V AC
0.05 A
2A
30 A (@50/60 Hz, 1
cycle)
700-SKOZ2Z25
700-SKON2Z25
700-SKOC2Z25
5…48V DC
4…60V DC
0.01 A
2A
8 A (10 ms)
700-SKOC1Z25
48…200V DC
40…200V DC
0.01 A
1.5 A
8 A (10 ms)
➊ With a constant current input system. SSR impedance varies with a change in input voltage.
➋ If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to the “Inrush Current Resistivity” graphs on page 61 for more details.
➌ Refer to "Load Current Versus Ambient Temperature Characteristics" graphs on page 61 for additional details.
60
Bulletin 700-SK
Solid-State Relays
Specifications, Continued
Output Module, Continued
Characteristics
700-SKOZ2Z25
Cat. No.
Load Switching Method/Device
700-SKON2Z25
700-SKOC2Z25
700-SKOC1Z25
Triac
Transistor
Pick-up time
1/2 of load power source cycle + 1 ms max.
1 ms max.
Drop-out time
1/2 of load power source cycle + 1 ms max.
2 ms max.
20 Hz
100 kHz
Response frequency
Output ON voltage drop
1.6 V max.
Leakage current
2.5V max.
1.5 mA max.
VDRM VCEO (V)
1 mA max.
600 (ref.value)
600 (ref.value)
80 (ref.value)
Output di/dt (A/uS)
30
30
—
—
Output dv/dt (V/uS)
300
300
—
—
Output I2t (A2S)
10.4
10.4
—
—
Output Tj (°C) Max.
125
125
150
150
Insulation resistance
400 (ref.value)
100 MΩ min. between input and output
Dielectric strength
4,000V AC, 50/60 Hz for 1 min. between input and output
Vibration resistance (max.)
10…55 Hz, 1.5 mm double amplitude (10 G)
1,000 m/s2 (100 G)
Shock resistance (max.)
Operating
Storage
Ambient temperature
–30…80°C (–22…176°F) with no icing or condensation
–30…100°C (–22…212°F) with no icing or condensation
UL 508
CSA C22.2, CE
TÜV
Standards
Ambient humidity
Operating
45…85% (no condensation)
Weight
Approx. 18 g
Load Current vs. Ambient Temperature Characteristics
Maximum Load Current (A)
Maximum Load Current (A)
For 2 A Versions
2
1.5
1
0.5
2
1.5
1
0.5
˚c
˚c
Inrush Current
Resistivity➊
700-SKOZ
/ SKON
700-SE05
700-SKOC2
700-SKOZ /SKOC1
2000
➊ Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability
once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.
61
Bulletin 700-SK
Solid-State Relays
Approximate Dimensions
All units are in millimeters unless otherwise indicated. Dimensions are not to be used for manufacturing purposes.
Note: The input module (700-SKI) and output module (700-SKO) are compatible with the 700-HN121 socket.
1
5.2
Terminal Arrangement/
Internal Connections
(Bottom View)
3
0.5
29 max.
17.4
4.75
1
13 max.
28 max.
5
(+)
4
9.6
(–)
4.7
Input
0.5 4.75
4
10
4
Load
5
7.5
3
1
5
(–)
(+)
2
20
Bulletin 700-SK
Application Considerations of Bulletin 700-SK
Connection
For DC load switching, Bulletin 700-SK SSR will operate properly if the load is connected to either the positive or negative SSR load terminal. The load can
be connected to either positive or negative output terminals of the SSR.
Protective Element (to extend SSR life)
Since the SSR does not incorporate a surge absorption component, be sure to connect a surge absorption component when using the SSR to control an
inductive load.
For additional details applying solid-state relays, refer to pub. number 700-AT001A-EN-E, "Solid-State Relay Application Guide." Document available at
www.theautomationbookstore.com.
62