ETC RA1225H06PCS

Solid State Relays
System Monitoring Relays (Sense Relay)
Type RA.... .....S
• System (line and load) monitoring relay
• Zero switching
• Rated operational current: 25, 50 and 90 AACrms
• Rated operational voltage: 120, 230 and 400 VACrms
• High surge current capability
• Alarm output signal
• LED indication for alarm and supply
Product Description
The system monitoring solid
state relay (sense relay) provides an alarm output in the
event of a circuit failure. Internal circuits monitor:
- line voltage/line current
- correct functioning of the SSR
- SSR input status
Ordering Key
The relay is designed for applications where immediate fault
detection is required.
A red LED indicates an alarm,
a green LED indicates DC control supply OK (half LED light
intensity) resp. relay switched
ON (full LED light intensity).
RA 23 25 H 06 NO S
Solid State Relay
Switching mode
Rated operational voltage
Rated operational current
Control input
Non-rep. peak voltage
Alarm output type
Sense SSR
Type Selection
Switching mode
Rated operational
voltage
Rated operational
current
Control
input
Non-rep. peak
voltage
Alarm output
type
A: Zero switching
12: 120 VACrms
23: 230 VACrms
40: 400 VACrms
25: 25 AACrms
50: 50 AACrms
90: 90 AACrms
H: Active high
L: Active low
06: 650 Vp
10: 1000 Vp
NO: NPN, NO
NC: NPN, NC
PO: PNP, NO
PC: PNP, NC
Selection Guide
Rated operational voltage
Control
input
Alarm output
type
Rated operational current
25 AACrms
50 AACrms
90 AACrms
120 VACrms
Active high
NPN, NO
NPN, NC
PNP, NO
PNP, NC
NPN, NO
NPN, NC
PNP, NO
PNP, NC
NPN, NO
NPN, NC
PNP, NO
PNP, NC
NPN, NO
NPN, NC
PNP, NO
PNP, NC
NPN, NO
NPN, NC
PNP, NO
PNP, NC
NPN, NO
NPN, NC
PNP, NO
PNP, NC
RA 1225 H06NOS
RA 1225 H06NCS
RA 1225 H06POS
RA 1225 H06PCS
RA 1225 L06NOS
RA 1225 L06NCS
RA 1225 L06POS
RA 1225 L06PCS
RA 2325 H06NOS
RA 2325 H06NCS
RA 2325 H06POS
RA 2325 H06PCS
RA 2325 L06NOS
RA 2325 L06NCS
RA 2325 L06POS
RA 2325 L06PCS
RA 4025 H10NOS
RA 4025 H10NCS
RA 4025 H10POS
RA 4025 H10PCS
RA 4025 L10NOS
RA 4025 L10NCS
RA 4025 L10POS
RA 4025 L10PCS
RA 1290 H06NOS
RA 1290 H06NCS
RA 1290 H06POS
RA 1290 H06PCS
RA 1290 L06NOS
RA 1290 L06NCS
RA 1290 L06POS
RA 1290 L06PCS
RA 2390 H06NOS
RA 2390 H06NCS
RA 2390 H06POS
RA 2390 H06PCS
RA 2390 L06NOS
RA 2390 L06NCS
RA 2390 L06POS
RA 2390 L06PCS
RA 4090 H10NOS
RA 4090 H10NCS
RA 4090 H10POS
RA 4090 H10PCS
RA 4090 L10NOS
RA 4090 L10NCS
RA 4090 L10POS
RA 4090 L10PCS
Active low
230 VACrms
Active high
Active low
400 VACrms
Active high
Active low
Specifications are subject to change without notice (30.06.1999)
RA 1250 H06NOS
RA 1250 H06NCS
RA 1250 H06POS
RA 1250 H06PCS
RA 1250 L06NOS
RA 1250 L06NCS
RA 1250 L06POS
RA 1250 L06PCS
RA 2350 H06NOS
RA 2350 H06NCS
RA 2350 H06POS
RA 2350 H06PCS
RA 2350 L06NOS
RA 2350 L06NCS
RA 2350 L06POS
RA 2350 L06PCS
RA 4050 H10NOS
RA 4050 H10NCS
RA 4050 H10POS
RA 4050 H10PCS
RA 4050 L10NOS
RA 4050 L10NCS
RA 4050 L10POS
RA 4050 L10PCS
1
RA.... .....S
General Specifications
Operational voltage range
Non-rep. peak voltage
Zero voltage turn-on
Operational frequency range
Power factor cos ϕ
CE-marking
RA12...06..S
RA23...06..S
RA40...10..S
40 to 140 VACrms
600 Vp
≤ 15 V
45 to 65 Hz
≥ 0.5 @ 120 VACrms
Yes
85 to 265 VACrms
600 Vp
≤ 15 V
45 to 65 Hz
≥ 0.5 @ 230 VACrms
Yes
150 to 440 VACrms
1000 Vp
≤ 15 V
45 to 65 Hz
≥ 0.5 @ 400 VACrms
Yes
Control Specifications
Supply voltage range
Supply current @ 24 VDC
Response time pick-up @ 50 Hz
Response time drop-out @ 50 Hz
Active high control input
Pick-up voltage
Drop-out voltage
Input current (Vc = 32 V)
Active low control input
Pick-up voltage
Drop-out voltage
Input current (Vcc = 32 V)
20 to 32 VDC
≤ 40 mA DC
≤ 10 ms
≤ 10 ms
Typ. 7 VDC
Typ. 6.8 VDC
≤ 4 mA
PNP Alarm output
Alarm output voltage open
Alarm output voltage @ 100 mA
Alarm output current
NPN Alarm output
Alarm output voltage open
Alarm output voltage @ 100 mA
Alarm output current
0 VDC
Vcc - 2 VDC
≤ 100 mA
≤ 32 VDC
2 VDC
≤ 100 mA
Typ. Vcc - 10 VDC
Typ. Vcc - 10 VDC
≤ 4 mA
Output Specifications
Rated operational current AC 1
Min. operational load current
Non-rep. surge current t=10 ms
Off-state leakage current
@ rated voltage and frequency
I2t for fusing t=1-10 ms
Critical dv/dt
RA..25.06..S
RA..50.06..S
RA..90.10..S
≤ 25 Arms
≤ 200 mA
≤ 250 Ap
≤ 50 Arms
≤ 200 mA
≤ 600 Ap
≤ 90 Arms
≤ 200 mA
≤ 1000 Ap
≤ 6 mA
≤ 310 A2s
≥ 500 V/µs
≤ 6 mA
≤ 1800 A2s
≥ 500 V/µs
≤ 6 mA
≤ 5000 A2s
≥ 500 V/µs
RA12...06..S
RA23...06..S
RA40...10..S
≥ 50 mA
≤ 20 mA
≥ 50 mA
≤ 20 mA
≥ 50 mA
≤ 20 mA
≥ 60 Vrms
≤ 30 Vrms
≥ 120 Vrms
≤ 50 Vrms
≥ 150 Vrms
≤ 80 Vrms
≤ 100 ms
Will be sensed
≤ 100 ms
Will be sensed
≤ 100 ms
Will be sensed
Sense Specifications
Current
Sensed load current
Non-sensed leakage current
Voltage
Sensed line voltage
Non-sensed line voltage
Timing
Response time from fault to
alarm output
Short-circuit of semiconductor
2
Specifications are subject to change without notice (30.06.1999)
RA.... .....S
Thermal Specifications
Operating temperature
Storage temperature
Junction temperature
Rth junction to case
Rth junction to ambient
RA..25.....S
RA..50.....S
RA..90.....S
-20° to +70°C (-4° to +158ºF)
-40° to +100°C (-40° to +212ºF)
≤ 115°C (239ºF)
≤ 1.25 K/W
≤ 12 K/W
-20° to +70°C (-4° to +158ºF)
-40° to +100°C (-40° to +212ºF)
≤ 115°C (239ºF)
≤ 0.65 K/W
≤ 12 K/W
-20° to +70°C (-4° to +158ºF)
-40° to +100°C (-40° to +212ºF)
≤ 115°C (239ºF)
≤ 0.35 K/W
≤ 12 K/W
Insulation
Wiring Diagrams
Rated insulation voltage
Input to output
Rated insulation voltage
Output to case
RAxxxxxxNxS
≥ 4000 VACrms
+3
6
Alarm output 7
4
≥ 4000 VACrms
2
Control input
IC
Line/load
1
Functional Diagram
VCC
Mains input/load output
RAxxxxxxPxS
Control
input
Alarm
output
+3
6
Alarm output 7
4
2
Control input
C/V
C/V
IC
Line/load
1
Com.
3+
45 Not con.
6 Control
7 Alarm
Load output/mains input
Operation Diagram
Normal
Relay
OFF
Operation
Relay
ON
Line
Voltage
Loss
Line
Voltage
Loss
Load
Open
Circuit
DC
Supply
Loss
DC
Supply
Loss
Relay
Remains
OFF
Shorted
Relay
Shorted
Relay
Line Voltage
Load Current
Control
Green LED
DC Supply
Red LED
Alarm output (normally open type)
= Half LED light intensity
Specifications are subject to change without notice (30.06.1999)
3
RA.... .....S
Heatsink Dimensions
(load current versus ambient temperature)
RA ..25 .....S
RA ..50 .....S
25
Power dissipation [W]
Thermal resistance
[K/W]
Load
current [A]
Load
current [A]
Power dissipation [W]
Thermal resistance
[K/W]
2
1.7
1.4
1
0.71
0.40
32
50
0.92
0.76
0.60
0.45
0.29
-
63
22.5
2.5
2.1
1.8
1.4
1
0.66
27
45
1.2
0.99
0.80
0.62
0.44
0.26
55
20
3.1
2.7
2.3
1.9
1.4
1
23
40
1.5
1.3
1.1
0.85
0.63
0.42
47
17.5
4
3.5
3
2.5
2
1.4
20
35
1.9
1.6
1.4
1.1
0.89
0.63
40
15
4.9
4.3
3.7
3.1
2.5
1.9
16
30
2.4
2.1
1.8
1.5
1.2
0.91
33
12.5
6.2
5.4
4.6
3.9
3.1
2.3
13
25
3
2.7
2.3
1.9
1.5
1.1
26
10
8.1
7.1
6.1
5.1
4
3
10
20
3.9
3.5
3
2.5
2
1.5
20
7.5
11.3
9.9
8.5
7.1
5.6
4.2
7
15
5.5
4.8
4.1
3.4
2.7
2.1
15
-
15.6
13.3
11.1
8.9
6.7
5
10
8.6
7.5
6.4
5.4
4.3
3.2
9
2
5
17.9
15.6
13.4
11.2
8,9
6.7
4
20
30
40
50
60
70
5
2.5
-
-
-
-
18.7
14
20
30
40
50
60
70
TA
Ambient temp. [°C]
TA
Ambient temp. [°C]
RA ..90 .....S
Load
current [A]
Power dissipation [W]
Thermal resistance
[K/W]
90
0.63
0.53
0.42
0.32
-
-
97
80
0.81
0.69
0.57
0.45
0.33
-
84
70
1
0.89
0.75
0.61
0.47
0.33
71
60
1.3
1.2
1
0.83
0.66
0.49
59
50
1.7
1.5
1.3
1.1
0.85
0.64
47
40
2.2
1.9
1.7
1.4
1.1
0.83
36
30
3.1
2.7
2.3
1.9
1.5
1.2
26
20
4.8
4.2
3.6
3
2.4
1.8
17
10
10
8.8
7.5
6.3
5
3.8
8
20
30
40
50
60
70
TA
Ambient temp. [°C]
4
Specifications are subject to change without notice (30.06.1999)
RA.... .....S
Heatsink Selection
Housing Specifications
Compare the value found in the load current versus temperature chart with the standard heatsink values and select the
heatsink with the next lower value.
Weight
Housing material
Base plate
Potting compound
Relay
Mounting screws
Mounting torque
Power terminal
Mounting screws
Mounting torque
Control connector
Dimensions
Accessories
Carlo Gavazzi Heatsink
(See “General Accessories”)
No heatsink required
RHS 100 Assy
RHS 301 Assy
RHS 301 F Assy
Consult your distributor
Thermal resistance
Rth s-a >12.5
3.0
0.8
0.25
< 0.25
Heatsinks
DIN rail adapter
Varistors
Fuses
Connector for ribbon cable:
Header for PCB mounting:
Ribbon cable:
58.2
29
24.5
45.5
K/W
K/W
K/W
K/W
K/W
5.3
17.8
5.1
47.5
APPLY
HEATSINK
COMPOUND
14.5
4xM
M = 2.54
SUPPLY LED
5.2
M5
≤ 1.5 Nm
M5 x 6
≤ 2.4 Nm
5 pole,
centre distance 2.54 mm
Methode 1300-105-424
Methode 1100-8-105-01
5 x 0.5 mm2,
centre distance 2.54 mm
Ribbon Cable Ordering No.
2 x M5
ALARM LED
Approx. 110 g
Noryl GFN 1, black
Aluminium, nickel-plated
Polyurethane
13
RCS 5-200-0*
R-System
Cable sense
5-wire
Cable length in cm
*
All dimensions in mm
Specifications are subject to change without notice (30.06.1999)
0: No connector mounted (Method 1300-105-424)
1: 1 connector mounted
2: 2 connectors mounted
5