ALLEN-BRADLEY MSR121RT

Safety Relays
Monitoring Safety Relays
Minotaur MSR121RT
Specifications
Standards
EN 954-1, ISO 13849-1, IEC/
EN60204-1, IEC 60947-4-1, IEC
60947-5-1, ANSI B11.19, AS4024.1
Category
Cat. 4 per EN954-1 (ISO 13849-1)
Approvals
C-Tick, CE marked for all
applicable directives, cULus & BG
Power Supply
24V AC/DC, 115/230V AC
0.8–1.1 x rated voltage, 50/60Hz
Power Consumption
4W
Safety Inputs
1 N.C., 2 N.C., Light Curtain or
Safety Mat
Input Simultaneity
Infinite
Description
Max. Allowable Input Resistance
45 ohms
The Allen-Bradley Guardmaster Minotaur MSR121RT is a safety
monitoring relay that provides three normally open safety contacts, a
normally open auxiliary contact and a solid state auxiliary output for
use with interfacing to PLCs.
Reset
Auto./Man. or Monitored Man.
Outputs
3 N.O. Safety, 1 N.C. Aux, 1 S.S.
PNP Aux.
Output Utilization per
IEC 60947-4-1 (Resistive)
AC-1: 8A/250V AC
DC -1L 8A/24V DC
➊ Output Utilization per
IEC 60947-5-1 (Inductive)
A300 AC-15; 6A/250V AC, 6A/
125V AC
N300 DC-13; 3A/24V DC; 6A/24V
DC @ 6 ops/min
Output, Solid State
20mA @ 24V DC
Thermal Current (non switching)
See limit curve
Max 10A in one current path
The MSR121RT has a versatile input arrangement. It can be
connected to a single or dual channel safety gate or e-stop, a safety
mat input or a light curtain that provides cross fault detection.
Reset and output monitoring is determined by the wiring
configuration. Automatic/manual reset can use a jumper or can be
used to check operation of external contactors. Monitored manual
requires the use of a manually operated normally open momentary
switch.
The MSR121RT has 3 normally open safety rated outputs. The
safety outputs have independent and redundant internal contacts to
help ensure the safety function. It has one normally closed auxiliary
output as well as a solid state PNP auxiliary output to indicate the
status of the MSR121RT to a indicator lamp or a PLC.
Features
•
•
•
•
•
•
•
•
•
Category 4 per EN 954-1
Stop category 0
3 Safety contacts N.O.
1 Auxiliary contact N.C.
1 Solid state PNP auxiliary contact
Single/dual channel operation
Cross fault monitoring
Monitored or automatic reset
E-stop, safety gate, safety mat or light curtain applications
current2 x number of contact paths, (A2)
Contact Current Limit Curve
100,000 operations
500,000 operations
300,000 operations
100,000 operations
1,000,000 operations
2,000,000 operations
Fuses, output external
6A slow blow or 10A quick blow
Min. Switched Current/Voltage
10mA/10V
Contact Material
AgSnO2 + 0.5µAu
Power On Delay
1s
Response Time 24V DC
24/115/230V AC
15ms
20ms
Recovery Time
100ms
Indication LEDs
Green = Power on; Green = K1
Closed; Green = K2 Closed
Impulse Withstand Voltage
2500V
Operating Temperature
-5°C to +55°C (+23° to +131°F)
200
Humidity
90% RH
180
Enclosure Protection
IP40 (NEMA 1), DIN 0470
160
Terminal Protection
IP20, DIN 0470
140
Electronic Short Circuit Prot.
Inputs & solid state output
120
Pollution Degree
2
100
Conductor Size
0.2 - 4mm2 (24 - 12AWG)
80
Mounting
35mm DIN rail
60
Weight 24V DC
110 and 230V AC
290g (0.64lbs)
370g (0.82lbs)
Mechanical Life
2,000,000 operations
Current over 3 contacts
40
Current over 2 contacts
20
0
0
10
20
30
40
50
Ambient Temperature (°C)
4-30
Electrical Life (w/Surge Supp.)
250V AC/6A/1500VA cosϕ=1
250V AC/2.5A/625VA cosϕ=1
250V AC/1.5A/375VA cosϕ=0.35
250V AC/5A/1250VA cosϕ=0.6
24V DC/2A/48W
10V DC/0.01A/0.1W
60
Vibration
10-55Hz, 0.35mm
Shock
10g, 16ms, 100 shocks
➊ See Output Ratings on page 1-29 for details. Consult factory for ratings not
shown.
Safety Relays
Monitoring Safety Relays
Minotaur MSR121RT
Product Selection
Inputs
Safety Outputs
Auxiliary Outputs
1 N.C., 2 N.C.,
Safety Mat or
Light Curtain
3 N.O.
1 N.C.
1 S.S. PNP
Power Supply
Catalogue Number
24V AC/DC
440R-J23102
115V AC
440R-J23100
230V AC
440R-J23099
Dimensions—mm (inches) Block Diagram
A1
(+)
87 (3.42)
109.5 (4.31)
S11
S52
S12
Y31
Y32
33
41
13
23
33
41
14
24
34
42
K2
S21
(PE)
75 (2.95)
23
K1
MSR121RT
45
(1.77)
13
S22
X5
S33
S34
14
24
34
A2
(–)
42
4.5 (0.17)
Typical Wiring Diagrams
+24V DC
L1
+
24VDC
-
Light curtain
Out 1 Out 2
L1 L2 L3
L1 L2 L3
A1 S11 S12 S52 X5 Y31 13 23 33 41
A1 S11 S52 S12 X5 Y31 13 23 33 41
Safety
Mat
K1
K1
MSR121RT
PE
A2 S21 S22 S34 S33 Y32 14 24
Reset
MSR121RT
K2
PE
A2 S21 S22 S34 S33 Y32 14 24
34 42
K2
34 42
M
K1 K2
Ground
Reset
M
K1 K2
N
24V DC Light Curtain, 115/230V AC Safety Relay,
Monitored Manual Reset, Monitored Output
Safety Mat
Monitored Manual Reset, Monitored Output
+24V DC
E-Stop
L1 L2 L3
A1 S11 S52 S12 X5 Y31 13 23 33 41
Safety Gate
+24V DC
L1 L2 L3
Closed
A1 S11 S12 S52 X5 Y31 13 23 33 41
K1
K1
MSR121RT
MSR121RT
PE
A2 S21 S22 S34 S33 Y32 14 24
Ground
Reset
K2
K2
PE
A2 S21 S22 S34 S33 Y32 14 24
34 42
K1 K2
Dual Channel E-Stop,
Monitored Manual Reset, Monitored Output
M
Ground
34 42
K1 K2
M
Single Channel Safety Gate,
Automatic Reset, No Output Monitoring
4-31