ALLEN-BRADLEY MSR131RTP

Safety Relays
Monitoring Safety Relays
Minotaur MSR131RTP
Specifications
Description
The MSR131RTP is a versatile monitoring safety relay. It can be
connected in four different input wiring configurations: 1 N.C., 2
N.C., 2 PNP connections from a light curtain, or a four wire safety
mat. When connected in the 2 N.C. fashion, the MSR131RTP
checks for cross faults across the two inputs. When connected to
light curtains, the light curtain must perform the cross fault
detection.
The MSR131RTP has output monitoring that can accommodate
either automatic/manual reset or a monitored manual reset. When
configured with automatic/manual reset (jumpers on X1-X2 and
X3-X4), the MSR131RTP can have the reset terminals S33-S34
jumpered or can be converted to an unmonitored manual reset by
adding a normally open switch in the monitoring loop (S33-S34).
When configured to monitored manual reset, the MSR131RTP
checks the output monitoring circuit through the manual application
of the reset switch.
The outputs include 3 normally open safety rated outputs, 2
normally closed auxiliary outputs, and 2 solid state outputs. One
solid state output indicates that the inputs are closed. The second
solid state output indicates that the safety outputs are active.
The safety outputs have independent and redundant internal
contacts to help ensure the safety function. The auxiliary output is a
nonsafety output intended to provide an external signal about the
status of the safety outputs.
Features
•
•
•
•
•
•
•
•
•
Category 4 per EN 954-1
Stop category 0
Light curtain, safety mat, E-Stop inputs
3 safety contacts
2 auxiliary contact
2 solid state outputs
Cross fault monitoring
Monitored or automatic reset
Removable terminals
Standards
EN 954-1, ISO 13849-1, IEC/EN
60204-1, IEC 60947-4-1, IEC
60947-5-1, ANSI B11.19, AS4024.1
Category
Approvals
Cat. 4 per EN 954-1 (ISO 13849-1)
Power Supply
24V AC/DC, 115V or 230V AC
0.85 to 1.1 x rated volt., 50/60Hz
Power Consumption
Safety Inputs
4W
Input Simultaneity
Infinite
C-Tick, CE marked for all
applicable directives, cULus & BG
1 N.C., 2 N.C., light curtain or
safety mat
Max. Allowable Input Resistance
45 ohms
Reset
Outputs
Monitored manual or Auto./manual
Output Utilization per IEC
60947-4-1 (Resistive)
AC-1: 6A/250V AC
DC-1: 6A/24V DC
➊ Output Utilization per IEC
60947-5-1 (Inductive)
B300, AC-15
3A/250V AC, 6A/125VAC
P300, DC-13; 3A/24V DC
6A/24V DC @ 6 ops/min
3 N.O. safety; 2 N.C. auxiliary; 1
S.S. PNP inputs closed; 1 S.S. PNP
outputs active
Thermal Current (non switching)
1 x 6A, 3x5A
Output, Solid State
30mA short circuit protected
Fuses Output (external)
6A slow blow or 10A quick blow
Min. Switched Current/Voltage
10mA/10V DC
Contact Material
AgSnO2 + 2mAu
Power On Delay
1s
Response Time
15ms
Recovery Time
Indication LEDs
100ms
Green = Power; Green = Start
Green = CH1 Input Closed
Green = CH2 Input Closed
Green = CH1 Output Active
Green = CH2 Output Active
Impulse Withstand Voltage
2500V
Pollution Degree
2
Operating Temperature
-5°C to +55°C (+23°F to 131°F)
Humidity
90% RH
Enclosure Protection
IP40 (NEMA 1)
Terminal Protection
IP20
Conductor Size
0.2–4mm2 (24–12 AWG)
Torque Settings—term. screws
0.4–0.5Nm (3.54–4.43lb²in)
Case Material
Polyamide PA 6.6
Mounting
35mm DIN rail
Weight 24V DC
110V AC or 230V AC
320g (0.71lbs)
450g (0.99lbs)
Electrical Life (w/Surge Supp.)
250V AC/6A/1500VA cosϕ=1
250V AC/2.5A/625VA cosϕ=1
250V AC/1.5A/375VA cosϕ=0.35
250V AC/5A/1250VA cosϕ=0.6
24V DC/2A/48W
10V DC/0.01A/0.1W
100,000 operations
500,000 operations
300,000 operations
100,000 operations
1,000,000 operations
2,000,000 operations
Mechanical Life
2,000,000 cycles
Vibration
10-55Hz, 0.35mm
Shock
10g, 16ms, 100 shocks
➊ See Output Ratings on page 1-29 for details. Consult factory for ratings not
shown.
4-40
Safety Relays
Monitoring Safety Relays
Minotaur MSR131RTP
Product Selection
Inputs
Safety Outputs
Auxiliary Outputs
1 N.C. or 2 N.C. or
Safety Mat or
Light Curtain
3 N.O.
2 N.C.
2 PNP Solid State
Power Supply
Catalogue Number
24V AC/DC
440R-C23139
115V AC
440R-C23137
230V AC
440R-C23136
Dimensions—mm (inches) Block Diagram
45 (1.77)
99 (3.89)
A1 S33 S34 S52 S11 13
23
51
X3 S11(+) S12 S21(-) S22 41
S12
13 23 33 41 51
K1
S52
S21
114.5
(4.5)
X4
A2
33
51
K2
Y30
Y1
S22
Y31
Y2
14 24 34 42 52
Y32 Y35 42
52
X1 X2 14
24
52
34
Typical Wiring Diagrams
+24V DC
+24V DC
Safety gate
Reset
Light Curtain
Out2
Out 1
open
closed
L1 L2 L3
A1 S11 S12 S21 S22 S52 S11 Y31 S33 S34 13 23 33 41 51
L1 L2 L3
A1 S11 S12 S21 S22 S52 S11 Y31 S33 S34 13 23 33 41 51
K1
K1
MSR131RTP
MSR131RTP
K2
A2 X1 X2 X3 X4 Y30 Y32 Y35 Y2 Y1 14 24 34 42 52
K1 K2
Ground
Output
Active
M
A2 X1 X2 X3 X4 Y30 Y32 Y35 Y2 Y1 14 24 34 42 52
M
K1
Ground
Inputs
Closed
Light Curtain, Monitored Manual Reset,
Monitored Output
Output Inputs
Active Closed
Single Channel Safety Gate, Automatic Reset,
No Output Monitoring
+24V DC
+24V DC
Reset
Safety
Mat
E-Stop
L1 L2 L3
A1 S11 S12 S21 S22 S52 S11 Y31 S33 S34 13 23 33 41 51
L1 L2 L3
A1 S11 S12 S21 S22 S52 S11 Y31 S33 S34 13 23 33 41 51
K1
MSR131RTP
MSR131RTP
K1
K2
K2
A2 X1 X2 X3 X4 Y30 Y32 Y35 Y2 Y1 14 24 34 42 52
Ground
A2 X1 X2 X3 X4 Y30 Y32 Y35 Y2 Y1 14 24 34 42 52
M
K1 K2
Ground
Dual Channel E-Stop, Monitored Manual Reset,
Monitored Output
L1
Light Curtain
Out1 Out 2
Safety Mat, Automatic Reset, No
Output Monitoring
Light Curtain
Out1 Out 2
L1 L2 L3
+24V DC
Reset
A1 S11 S12 S21 S22 S52 S11 Y31 S33 S34 13 23 33 41 51
K1
MSR131RTP
Output Inputs
Active Closed
L1
+24V DC
Reset
A1 S11 S12 S21 S22 S52 S11 Y31 S33 S34 13 23 33 41 51
MSR131RTP
K2
A2 X1 X2 X3 X4 Y30 Y32 Y35 Y2 Y1 14 24 34 42 52
+24V DC Ground
Output
Active
K1 K2
L1 L2 L3
K1
K2
N
M
K1 K2
Output Inputs
Active Closed
A2 X1 X2 X3 X4 Y30 Y32 Y35 Y2 Y1 14 24 34 42 52
M
Inputs
Closed
115/230V AC Supply, 24V DC, Light Curtain,
Monitored Manual Reset, Monitored Output
N
+24V DC Ground
Output
Active
K1 K2
M
Inputs
Closed
115/230V AC Supply, 24V DC, Light Curtain,
Monitored Manual Reset, No Output Monitoring
4-41