Product Data Sheet
AC/DC POWER SUPPLY
SX500
FEATURES
DESCRIPTION
z Active Power Factor Correction
The SX500 is a compact 500 watt Power Factor
Corrected, single output power supply. Active current sharing circuitry with ORing diodes, together with
control functions and alarm options, simplifies N+1
redundant applications.
z Active Current Sharing With ORing Diodes
z FCC/VDE Class B EMI Filter
z Optional Active Inrush Current Limit
z Compact Size: 10” x 4.85” x 2.19”
AGENCY APPROVALS
z Optional SCR Crowbar
z Optional Cover With Fan
Internet: http://www.cdpowerelectronics.com
Power Electronics Division, United States
Power Electronics Division, Europe
3400 E Britannia Drive, Tucson, Arizona 85706
Phone: 520.295.4100 Fax: 520.770.9369
C&D Technologies (Power Electronics) Ltd.
132 Shannon Industrial Estate, Shannon, Co. Clare, Ireland
Tel: +353.61.474.133
Fax:+353.61.474.141
SX500 10/98 REV B
Page 1
Input Specifications
Parameter
Conditions
Operating Range
Min
47-63 Hz
Typ
90
Max
Units
264
VAC
30
APK
60
APK
Inrush Current Limiting
Thermistor
120 VAC, cold start
240 VAC, cold start
Active Current Limit
264 VAC
Efficiency
Nominal line and full load
Power Factor Correction (PFC)
19
APK
75
%
0.99
Meets EN61000-3-2 (formerly IEC 555-2)
Remote Sense
Remote Sense is provided and will compensate for 1.0V
of line drop. Remote Sense leads are protected against
open, short and reversal.
Remote On/Off (Optional)
The power supply is turned on with a TTL logic ‘1’ (or open)
signal and turned off by a switch closure or TTL logic ‘0’
referenced to (-) sense terminal. Consult the factory for
other options.
Over Voltage Protection
Output #1: 115% of nominal voltage is typical.
The power supply will latch off until AC power is cycled.
Over Current Protection
Automatic recovery upon fault removal.
Transient Response
The peak output voltage excursion will not exceed 2% and
will recover within 1% in 200 msec for a 25% step load.
Reverse Voltage Protection
The output is protected to rated load.
Page 2
Power Fail Signal
Upon AC input voltage removal, the power fail signal drops
to logic zero at least 10msec before loss of DC output.
Upon AC input turn-on, signal remains low until output is in
regulation. Consult the factory for other options.
N+1 Load Share
Output has active load sharing circuitry. Units will load
share within 1% of the Maximum Rated Load.
Over Temperature Protection
Thermal switch turns off power supply if overheating occurs
and automatically restarts.
Safety
UL/CUL Recognized: UL File Number E13164 (1950)
TUV License Number: R9773309 (EN60950) (IEC950)
Cooling
The unit is designed to operate with 30 CFM of airflow.
DC Power Good Signal
The signal is activated by a ±10% loss of regulation Active
low or high; TTL Level; common with (-) sense. Consult the
factory for other options.
SX500 10/98 REV B
Output Voltages and Maximum Rated Loads
VOUT
OUTPUT
IMAX
SX500-U1A
±24V
21A
26A
SX500-U1B
±28V
18A
22A
MODEL NUMBER
IPK
SX500-U1C
±36V
14A
17A
SX500-U1D
±48V
10.5A
12.5A
Output Specifications
Parameter
Limits
Regulation
Line
± 0.2%
Load
±0.5%
Minimum Load
0.1A
Hold-Up Time
20mSec at Full Load
Parameter
Conditions
Min
Voltage Adjustment Range
PARD
20 MHz bandwidth
Typ
Max
Units
±5
%
0.5
% P-P
Temperature
Operating
Storage
Temperature Coefficient (TC)
SX500 10/98 REV B
After half hour warm-up
0
50
°C
-20
+85
°C
± 0.02
% /°C
Page 3
Mechanical
8.500
0.700
0.040
COVER
2.148
1.300
0.550
J9
3.900
PIN 1
4.850
AIR FLOW
TB2
PIN 1
10.00
6-32 THD
(4x)
0.620
3.190
NOTES:
All measurements are in inches
FAN MOUNTED ON COVER ADDS 1.30”.
COOLING: The SX500 is designed to operate with 30 CFM airflow.
SHOCK AND VIBRATION: The SX500 family meets the requirements of MIL STD-810D. (Vibration-Method 514.3 Procedure 1. Shock-Method 516.3 Procedure 1.)
WEIGHT: Approximately 4 lbs.
Connector Specifications
Pin Specifications
Terminal Block 1
J9 Connector
Terminal Block 2
Molex No. 22-28-1093
POS
FUNCTION
POS
FUNCTION
1
Ground
1
+V
PIN
2
AC Neutral
2
+V
1
- Sense
3
AC Line
3
-V
2
+ Sense
4
-V
3
Current Share
4
Remote Inhibit
5
Power Fail
6
DC OK
FUNCTION
7
Sync
8
Signal Ground
9
N/C
Standard Options are shown, consult factory for other available options.
The information provided herein is believed to be reliable; however, C&D TECHNOLOGIES assumes no responsibility for inaccuracies or omissions. C&D TECHNOLOGIES
assumes no responsibility for the use of this information, and all use of such information shall be entirely at the user’s own risk. Prices and specifications are subject to
change without notice. No patent rights or licenses to any of the circuits described herein are implied or granted to any third party. C&D TECHNOLOGIES does not authorize
or warrant any C&D TECHNOLOGIES product for use in life support devices/systems or in aircraft control applications.
Page 4
SX500 10/98 REV B