celpac S/CLP/SILD845160/E/28/05/2004 page 1 / 5GB AC Semiconductor Contactor pitch 22,5mm with Diagnostic compact size and DIN rail mounting. SILD845160 ❏ Ready to use Single-Phase Relay: " Install it & Forget it!" Zero cross model : 70-280VAC 50A back to back thyristors on output TMS2 technology - I2t value > 1500A2s I2t values on request to 5 000A2s. Output : 70-280VAC 32A(*) Input : 3 -32VDC - I<10mA Diagnostic : 30VDC - 100mA PATENTED ! ❏ Model with diagnostic : status of the SSR and the load . Normally closed status output . Without external power supply . Status visualization by yellow LED (*) . Status output can be chained. ❏ This zero cross model switch ON in case of overvoltage . ❏ Large control range : 3-32VDC with an input current < 10 mA on all the range. Green LED visualization on the input. ❏ IP20 housing ❏ Low zero cross voltage ( <15V) ❏ Mounting and dismounting on DIN rail without any tool or directly mountable on panel. ❏ Designed in conformity with EN60947-4-3 (IEC947-4-3) and EN60950 -UL-cUL Dimensions : 28A (*) see conditions (thermal curve page 4) Mains 230VAC 50hz (*) : was Red on the first pieces. - Output status + diag SSR Typical application: 5kW resistor (AC-51 load) on 230 VAC + - Input Control CHARGE/LOAD Proud to serve you All technical caracteristics are subject to change without previous notice. Caractéristiques sujettes à modifications sans préavis. celduc r e l a i s celpac S/CLP/SILD845160/E/28/05/2004 page 2 / 5GB Control characteristics (at 25°C) Symbol Uc Ic Uc off Min 3 <10 2 green 32 42 2kV 2KV Urv Uclamp Input : Ic = f( Uc) Unit V mA V V V 12 10 8 Ic ( mA) Paramètre / Parameter Control voltage Control current (@ Uc ) Release voltage Input LED Reverse voltage Clamping voltage Input immunity : EN61000-4-4 Input immunity : EN61000-4-5 DC Nom Max 5-12-24 32 <10 <10 6 4 2 0 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 Uc ( VDC) Output characteristics (at 25°C) Parameter Load voltage Operating range Peak voltage Switch ON voltage in case of overvoltage Zero cross level Latching voltage AC-51 nominal current : permanent AC-53 nominal current Non repetitive overload current On state voltage drop (typical value) Dynamic resistance (typical value) Conditions on the thyristors Ie nom ( see Fig. 2 page 3) tp=10ms (Fig. 3) @ 25°C Output Power dissipation (typical value) Thermal resistance between junction to air Off state leakage current Minimum load current Turn on time Turn off time Operating frequency range Off state dv/dt Maximum di/dt non repetitive I2t (<10ms) Conducted immunity level Conducted immunity level Short circuit protection @Ue, 50Hz Uc nom DC ,f=50Hz Uc nom DC ,f=50Hz IEC 1000-4-4 (burst) IEC 1000-4-5(schocks) FERRAZ General characteristics (at 25°C) Input to output insulation Output to status insulation Output to case insulation Insulation resistance Rated impulse voltage Protection level / CEI529 Pollution degree Vibration resistance 10 -55 Hz according to CEI68 : Shocks resistance according to CEI68 ( on DIN rail / with screws) Ambient temperature (with no icing or condensation) Storage temperature (with no icing or condensation) Ambient humidity Weight Conformity Conformity Ui Ui Ui Ri Uimp double amplitude HR Symbol Ue Uemin-max Up Uclamp Usync Ua Ie AC-51 Ie AC-53 Itsm Vt rt Typ. 230 70-280 1200 900-950 14 12 consult us 550 0,9 8 Unit V rms V rms V V V V A rms A rms A V mΩ Pd 0,81xIe+0,08xIe2 W 32 Rthj/a Ilk Iemin ton max toff max f dv/dt di/dt I2t 3,3 (2,5) K/W <5 mA 100 mA 10 ms 10 ms 40-440 Hz 500 V/µs 50 A/µs 1500 A2s 4kV criterion B 4kV criterion B gRC 25A/32A/50A/63A 14x51 4000 2500 4000 100 (@500VDC) 4000 IP20 2 1,5 30/50 -40 /+80 -40/+100 40 to 85 260 EN60947-4-3 (IEC947-4-3) UL/cUL pending VRMS VRMS VRMS MΩ V mm g °C °C % g celduc r e l a i www.celduc.com s Rue Ampère B.P. 4 42290 SORBIERS - FRANCE E-Mail : [email protected] Fax +33 (0) 4 77 53 85 51 Service Commercial France Tél. : +33 (0) 4 77 53 90 20 Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19 celpac S/CLP/SILD845160/E/28/05/2004 page 3 / 5/GB Status output answer characteristics (at 25°C) Paramètre / Parameter Conditions Symbol Voltage range Us Output current Id On resistance Rdson Open delay (faults) Uenom to1 Total open delay (faults) Uenom to2 Closed mains delay Uenom, Uc=0V tc1 Closed mains delay Uenom, Uc=Ucnom tc2 Maximum cable length for open load ( maximum load due to capacitor) Min 1 0 Nom 12-24 0,1 Max 32 0,1 2 Unit V A Ω ms ms ms ms m 70 120 20 20 40 Diagnostic description Control Control LED Load SSR Status LED Output status Notices 0 No x x Open 1 No x x Open 0 Yes OK OK closed 1 Yes OK OK closed 0 Yes Open OK Open 0 Yes OK short-circuit Open 1 Yes Open OK Open 1 Yes OK short-circuit Open Reaseau / Mains ON Mains ABSENCE RESEAU / OPEN MAINS Synoptic : Commande / Control CHARGE COUPEE OFF THYRISTORS EN COURTCIRCUIT / SHORT-CIRCUIT SCR / OPEN LOAD Courant / Current Ouvert/ Open Sortie d'état / Status output ton toff Fermé/ Closed to1 to2 tc1 to1 to2 tc2 to1 to2 • The red LED luminosity depends on : - Ue voltage. - Control : ON,OFF - Load type. • The status outputs can be connected in serial for only one information. • NPN/ PNP output is possible with status ( insulation with the control) and no power supply for the relay. • In case of using with a mains voltage lower than specifications, the SSR works correctly, but an alarm status can be given with control OFF. In this case, the status works only with control ON with the diagnostic of open load or SSR short-circuit. * Status (static output) is normally closed without failure on the relay and the load, and the yellow LED is switched ON : That means there is - voltage across the SSR without control. - current inside the SSR with control . * In case of failure on the load ( opened) or on the SSR (short-circuited) : - the status is opened . - the yellow LED is switched OFF . tc1 Led de commande / Control LED Led d'état / Status LED Mains 70-280V Important : In case of long wiring cable between the SSR and the load ( > 25 meters), it is possible than the diagnostic system can't detect an open load. Ic 1 L1 A1 Fuse Control Uc A2 Id green Vds Status Load red 2 T1 celduc r e l a i www.celduc.com s Rue Ampère B.P. 4 42290 SORBIERS - FRANCE E-Mail : [email protected] Fax +33 (0) 4 77 53 85 51 Service Commercial France Tél. : +33 (0) 4 77 53 90 20 Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19 celpac S/CLP/SILD845160/E/28/05/2004 page 4 / 5/GB Thermal specifications. ♦ The curve "1" gives the limits of the product. The temperature reached are acceptable for the components. These values are in compliance with most of SSRs manufacturers. In a cabinet with a minimum of ventilation or a non permanent current, these values are correct. 45 40 35 1 30 The curve "2" gives the limits of the product according to EN60947-4-3 with a maximum rise temperature of 50°C (@40°C) for a permanent working and in air calm ( test during 8 hours). I(A) ♦ 25 20 2 15 For a non permanent current, you can calcule the average power = Pd x duty cycle and check the rise temperature : ∆Tj = Pd x Rthj/a (Pd and Rthj/a are given page 2)). The junction temperature must not exceed 125°C at the maximum ambient temperature. The maximum current is limited to the size of the thyristors = 50A. ♦ 10 5 0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 The thermal constant (Cth) of the product is 7 minutes. That means the rise temperature is only 63% of the stabilized temperature after a running time of 7 minutes. ♦ Tambient(°C) fig 2 Overload current. Fig.3 Surge current : Itsm (Apeak) = f(t) for 50A models with Itsm =550A 1 - No repetitive Itsm is given without voltage reapplied . This curve is used for the determination of the protection. 600 Itsm (Apeak) 2 - Repetitive Itsm is given for inrush current with initial Tj = 70°C. In normal working , this curve musn't be exceed. Be carefull, the repetition of the surge current decrease the lifetime SSR's . 1 400 No repetive surge current without voltage reapplied. 2 200 Repetive surge current with voltage reapplied. 0 0,01 fig 3 0,1 1 t (s) Panel Mounting Mounting and dismounting on DIN rail without any tool. M5 Drill for vertical can be adjusted Mounting DIN rail connected to protection wire (ground) . Dismounting 10 M4 88±2mm 12,7mm ♦ Warning ! semiconductor relays don't provide any galvanic insulation between the load and the mains. Always use in conjunction with an adapted circuit breaker with isolation feature or a similar device in order to ensure a reliable isolation in the event of wrong function and when the relay must be insulated from the mains (maintenance ; if not used for a long duration ...). celduc r e l a i www.celduc.com s Rue Ampère B.P. 4 42290 SORBIERS - FRANCE E-Mail : [email protected] Fax +33 (0) 4 77 53 85 51 Service Commercial France Tél. : +33 (0) 4 77 53 90 20 Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19 celpac S/CLP/SILD845160/E/28/05/2004 page 5 / 5GB Connections . ♦ For the output terminals, the wire cross sections must be adapted to the load current and to the overcurrent protection device characteristics. The relay rated voltage must be adapted to the mains rated voltage. ♦ celpac wires (mm2) L L torques screwdriver screwdriver control 1 x(0,75-->2,5) L = 6mm use screw clamp connections. 0,4N.m (0,6N.m max) 3,5x0,5mm 1,2N.m (1,8N.m max) Pozidriv2/ 0,8x5,5 (1x6) Power 1x(1,5-->16) 1 x(1,5-->10) L = 10mm Mounting ♦ Only in vertical position: The user should protect heat sensitive materials as well as persons against any contacts with the heatsink. For non vertical mounting , the load current must be 50% lower than the rated one . For a good cooling, the SSR needs an air convection. Less convection air produces an abnormal heating. Keep a distance between the upper SSR and the lower SSR. In case of no space between two SSR (zero space between two SSRs) , please reduce the load current. For further details refer to below : ♦ Derating current with no space between SSRs AC-51 nominal currents are given with a space of 22,5mm between each SSR, for a permanent current during a minimum time of 8 hours in air calm according to IEC60947-4-3. In case of non permanent currents or in case of SSRs are mounted with no space, you must check the heatsink temperature never exceed 90°C. When the SSRs are mounted side to side ( no space between each relay) a derating current of 25% must be take into account. A forced cooling ( fan inside the cabinet) improves significantly the thermal performances. vertical position 80mm Typical application : LOADS SILD product is designed mainly for AC-51 résistive load. For other loads, check the inrush current at turn ON and possible overvoltages at turn OFF or consult us : * AC-55b : Incandescent lamps : Inrush current is generally 10 times In during few 10ms. So limit the nominal current at about 15A. Fuse Fusible Protection : 2 2 To protect the SSR against a short-circuit of the load , use a fuse with a I t value = 1/2 I t value specified page 2. A test has been made with FERRAZ fuse ( see page 2). It is possible to protect SSR by MCB ( miniature circuit breaker). In this case, see application note ( SSR protection) and use a SSR with high I2t value (5000A2s minimum). diagnostic outputs in serie + - - + + - L1 Diag L1 Diag T1 T1 EMC : ♦ Immunity : We give in our data-sheets, the immunity level of our SSRs according to the main standards for this type of products : EN61000-4-4 &5. You can see the high immunity level in comparison with the products on the market. ♦ Emission: SSRs are complex devices which must be interconnected with other equipment (loads, cables,etc.) to form a system. Because the other equipment or the interconnections may not be under the control of celduc, it shall be the responsibility of the system integrator to ensure that systems containing SSRs comply with the requirements of any rules and regulations applicable at the system level.. Consult celduc laboratory which can make some tests in your application. celduc r e l a i - + - + A2 A1 A2 A1 control control Load Charge N N www.celduc.com s Rue Ampère B.P. 4 42290 SORBIERS - FRANCE E-Mail : [email protected] Fax +33 (0) 4 77 53 85 51 Service Commercial France Tél. : +33 (0) 4 77 53 90 20 Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19