CELDUC SILD845160

celpac
S/CLP/SILD845160/E/28/05/2004
page 1 / 5GB
AC Semiconductor Contactor
pitch 22,5mm with Diagnostic
compact size and DIN rail mounting.
SILD845160
❏ Ready to use Single-Phase Relay: " Install it & Forget it!"
Zero cross model : 70-280VAC
50A back to back thyristors on output
TMS2 technology - I2t value > 1500A2s
I2t values on request to 5 000A2s.
Output : 70-280VAC 32A(*)
Input : 3 -32VDC - I<10mA
Diagnostic : 30VDC - 100mA
PATENTED !
❏ Model with diagnostic : status of the SSR and the load .
Normally closed status output .
Without external power supply .
Status visualization by yellow LED (*) .
Status output can be chained.
❏ This zero cross model switch ON in case of overvoltage .
❏ Large control range : 3-32VDC with an input
current < 10 mA on all the range.
Green LED visualization on the input.
❏ IP20 housing
❏ Low zero cross voltage ( <15V)
❏ Mounting and dismounting on DIN rail without any
tool or directly mountable on panel.
❏ Designed in conformity with EN60947-4-3
(IEC947-4-3) and EN60950
-UL-cUL
Dimensions :
28A
(*) see conditions (thermal curve page 4)
Mains
230VAC
50hz
(*) : was Red on the first pieces.
-
Output
status
+
diag
SSR
Typical
application:
5kW resistor
(AC-51 load)
on 230 VAC
+
-
Input
Control
CHARGE/LOAD

Proud to serve you
All technical caracteristics are subject to change without previous notice.
Caractéristiques sujettes à modifications sans préavis.
celduc
r
e
l
a
i
s
celpac
S/CLP/SILD845160/E/28/05/2004
page 2 / 5GB
Control characteristics (at 25°C)
Symbol
Uc
Ic
Uc off
Min
3
<10
2
green
32
42
2kV
2KV
Urv
Uclamp
Input : Ic = f( Uc)
Unit
V
mA
V
V
V
12
10
8
Ic ( mA)
Paramètre / Parameter
Control voltage
Control current (@ Uc )
Release voltage
Input LED
Reverse voltage
Clamping voltage
Input immunity : EN61000-4-4
Input immunity : EN61000-4-5
DC
Nom Max
5-12-24 32
<10
<10
6
4
2
0
0
2
4
6
8 10 12 14 16 18 20 22 24 26 28 30 32
Uc ( VDC)
Output characteristics (at 25°C)
Parameter
Load voltage
Operating range
Peak voltage
Switch ON voltage in case of overvoltage
Zero cross level
Latching voltage
AC-51 nominal current : permanent
AC-53 nominal current
Non repetitive overload current
On state voltage drop (typical value)
Dynamic resistance (typical value)
Conditions
on the thyristors
Ie nom
( see Fig. 2 page 3)
tp=10ms (Fig. 3)
@ 25°C
Output Power dissipation (typical value)
Thermal resistance between junction to air
Off state leakage current
Minimum load current
Turn on time
Turn off time
Operating frequency range
Off state dv/dt
Maximum di/dt non repetitive
I2t (<10ms)
Conducted immunity level
Conducted immunity level
Short circuit protection
@Ue, 50Hz
Uc nom DC ,f=50Hz
Uc nom DC ,f=50Hz
IEC 1000-4-4 (burst)
IEC 1000-4-5(schocks)
FERRAZ
General characteristics (at 25°C)
Input to output insulation
Output to status insulation
Output to case insulation
Insulation resistance
Rated impulse voltage
Protection level / CEI529
Pollution degree
Vibration resistance 10 -55 Hz according to CEI68 :
Shocks resistance according to CEI68 ( on DIN rail / with screws)
Ambient temperature (with no icing or condensation)
Storage temperature (with no icing or condensation)
Ambient humidity
Weight
Conformity
Conformity
Ui
Ui
Ui
Ri
Uimp
double amplitude
HR
Symbol
Ue
Uemin-max
Up
Uclamp
Usync
Ua
Ie AC-51
Ie AC-53
Itsm
Vt
rt
Typ.
230
70-280
1200
900-950
14
12
consult us
550
0,9
8
Unit
V rms
V rms
V
V
V
V
A rms
A rms
A
V
mΩ
Pd
0,81xIe+0,08xIe2
W
32
Rthj/a
Ilk
Iemin
ton max
toff max
f
dv/dt
di/dt
I2t
3,3 (2,5)
K/W
<5
mA
100
mA
10
ms
10
ms
40-440
Hz
500
V/µs
50
A/µs
1500
A2s
4kV criterion B
4kV criterion B
gRC 25A/32A/50A/63A 14x51
4000
2500
4000
100 (@500VDC)
4000
IP20
2
1,5
30/50
-40 /+80
-40/+100
40 to 85
260
EN60947-4-3 (IEC947-4-3)
UL/cUL pending
VRMS
VRMS
VRMS
MΩ
V
mm
g
°C
°C
%
g

celduc
r
e
l
a
i
www.celduc.com
s
Rue Ampère B.P. 4
42290 SORBIERS - FRANCE
E-Mail : [email protected]
Fax +33 (0) 4 77 53 85 51
Service Commercial France Tél. : +33 (0) 4 77 53 90 20
Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19
celpac
S/CLP/SILD845160/E/28/05/2004
page 3 / 5/GB
Status output answer characteristics (at 25°C)
Paramètre / Parameter
Conditions
Symbol
Voltage range
Us
Output current
Id
On resistance
Rdson
Open delay (faults)
Uenom
to1
Total open delay (faults)
Uenom
to2
Closed mains delay
Uenom, Uc=0V
tc1
Closed mains delay
Uenom, Uc=Ucnom
tc2
Maximum cable length for open load ( maximum load due to capacitor)
Min
1
0
Nom
12-24
0,1
Max
32
0,1
2
Unit
V
A
Ω
ms
ms
ms
ms
m
70
120
20
20
40
Diagnostic description
Control
Control
LED
Load
SSR
Status LED Output status Notices
0
No
x
x
Open
1
No
x
x
Open
0
Yes
OK
OK
closed
1
Yes
OK
OK
closed
0
Yes
Open
OK
Open
0
Yes
OK
short-circuit
Open
1
Yes
Open
OK
Open
1
Yes
OK
short-circuit
Open
Reaseau
/ Mains
ON
Mains
ABSENCE RESEAU
/ OPEN MAINS
Synoptic :
Commande
/ Control
CHARGE COUPEE
OFF
THYRISTORS EN COURTCIRCUIT
/ SHORT-CIRCUIT SCR
/ OPEN LOAD
Courant
/ Current
Ouvert/
Open
Sortie d'état /
Status output
ton
toff
Fermé/
Closed
to1
to2
tc1
to1
to2
tc2
to1
to2
• The red LED luminosity depends on :
- Ue voltage.
- Control : ON,OFF
- Load type.
• The status outputs can be connected in
serial for only one information.
• NPN/ PNP output is possible with status
( insulation with the control) and no power
supply for the relay.
• In case of using with a mains voltage
lower than specifications, the SSR works
correctly, but an alarm status can be given
with control OFF.
In this case, the status works only with
control ON with the diagnostic of open
load or SSR short-circuit.
* Status (static output) is normally closed
without failure on the relay and the load,
and the yellow LED is switched ON :
That means there is
- voltage across the SSR without control.
- current inside the SSR with control .
* In case of failure on the load ( opened)
or on the SSR (short-circuited) :
- the status is opened .
- the yellow LED is switched OFF .
tc1
Led de commande
/ Control LED
Led d'état
/ Status LED
Mains
70-280V
Important :
In case of long wiring cable between the SSR
and the load ( > 25 meters), it is possible than
the diagnostic system can't detect an open load.
Ic
1 L1
A1
Fuse
Control
Uc
A2
Id
green
Vds
Status
Load
red
2 T1

celduc
r
e
l
a
i
www.celduc.com
s
Rue Ampère B.P. 4
42290 SORBIERS - FRANCE
E-Mail : [email protected]
Fax +33 (0) 4 77 53 85 51
Service Commercial France Tél. : +33 (0) 4 77 53 90 20
Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19
celpac
S/CLP/SILD845160/E/28/05/2004
page 4 / 5/GB
Thermal specifications.
♦ The curve "1" gives the limits of the product. The temperature reached are acceptable for the components. These
values are in compliance with most of SSRs manufacturers.
In a cabinet with a minimum of ventilation or a non permanent current, these values are correct.
45
40
35
1
30
The curve "2" gives the limits of the product according
to EN60947-4-3 with a maximum rise temperature of 50°C
(@40°C) for a permanent working and in air calm ( test
during 8 hours).
I(A)
♦
25
20
2
15
For a non permanent current, you can calcule the average power = Pd x duty cycle and check the rise temperature : ∆Tj = Pd x Rthj/a (Pd and Rthj/a are given page 2)).
The junction temperature must not exceed 125°C at the
maximum ambient temperature. The maximum current is
limited to the size of the thyristors = 50A.
♦
10
5
0
0
5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85
The thermal constant (Cth) of the product is 7 minutes.
That means the rise temperature is only 63% of the stabilized temperature after a running time of
7 minutes.
♦
Tambient(°C)
fig 2
Overload current.
Fig.3 Surge current : Itsm (Apeak) = f(t) for 50A models with Itsm =550A
1 - No repetitive Itsm is given without voltage
reapplied . This curve is used for the
determination of the protection.
600
Itsm (Apeak)
2 - Repetitive Itsm is given for inrush current
with initial Tj = 70°C. In normal working , this
curve musn't be exceed. Be carefull, the
repetition of the surge current decrease the
lifetime SSR's .
1
400
No repetive surge current without voltage reapplied.
2
200
Repetive surge current with voltage reapplied.
0
0,01
fig 3
0,1
1
t (s)
Panel Mounting
Mounting and dismounting on DIN rail without any tool.
M5
Drill for vertical can be adjusted
Mounting
DIN rail connected to
protection wire (ground) .
Dismounting
10
M4
88±2mm
12,7mm
♦ Warning ! semiconductor relays don't provide any galvanic insulation between the load and the mains. Always use in conjunction
with an adapted circuit breaker with isolation feature or a similar device in order to ensure a reliable isolation in the event of wrong function
and when the relay must be insulated from the mains (maintenance ; if not used for a long duration ...).

celduc
r
e
l
a
i
www.celduc.com
s
Rue Ampère B.P. 4
42290 SORBIERS - FRANCE
E-Mail : [email protected]
Fax +33 (0) 4 77 53 85 51
Service Commercial France Tél. : +33 (0) 4 77 53 90 20
Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19
celpac
S/CLP/SILD845160/E/28/05/2004
page 5 / 5GB
Connections .
♦ For the output terminals, the wire cross sections must be
adapted to the load current and to the overcurrent protection device
characteristics. The relay rated voltage must be adapted to the mains
rated voltage.
♦ celpac
wires
(mm2)
L
L
torques
screwdriver
screwdriver
control
1 x(0,75-->2,5)
L = 6mm
use screw clamp connections.
0,4N.m
(0,6N.m max)
3,5x0,5mm
1,2N.m
(1,8N.m max)
Pozidriv2/
0,8x5,5 (1x6)
Power
1x(1,5-->16) 1 x(1,5-->10)
L = 10mm
Mounting
♦ Only
in vertical position:
The user should protect heat sensitive materials as well as persons against any contacts with the
heatsink. For non vertical mounting , the load current must be 50% lower than the rated one . For a
good cooling, the SSR needs an air convection. Less convection air produces an abnormal heating.
Keep a distance between the upper SSR and the lower SSR. In case of no space between two SSR
(zero space between two SSRs) , please reduce the load current. For further details refer to below :
♦ Derating
current with no space between SSRs
AC-51 nominal currents are given with a space of 22,5mm between each SSR, for a
permanent current during a minimum time of 8 hours in air calm according to IEC60947-4-3. In case
of non permanent currents or in case of SSRs are mounted with no space, you must check the heatsink
temperature never exceed 90°C. When the SSRs are mounted side to side ( no space between each relay) a derating current of 25% must be take into account.
A forced cooling ( fan inside the cabinet) improves significantly the thermal performances.
vertical
position
80mm
Typical application :
LOADS
SILD product is designed mainly for AC-51 résistive load. For other loads, check the inrush current at turn ON and possible overvoltages at turn OFF or consult us :
* AC-55b : Incandescent lamps : Inrush current is generally 10 times In during few 10ms.
So limit the nominal current at about 15A.
Fuse
Fusible
Protection :
2
2
To protect the SSR against a short-circuit of the load , use a fuse with a I t value = 1/2 I t value
specified page 2. A test has been made with FERRAZ fuse ( see page 2).
It is possible to protect SSR by MCB ( miniature circuit breaker). In this case, see application note (
SSR protection) and use a SSR with high I2t value (5000A2s minimum).
diagnostic
outputs in
serie
+
-
-
+
+
-
L1 Diag
L1 Diag
T1
T1
EMC :
♦ Immunity
:
We give in our data-sheets, the immunity level of our SSRs according to the main standards for
this type of products : EN61000-4-4 &5. You can see the high immunity level in comparison with the
products on the market.
♦ Emission:
SSRs are complex devices which must be interconnected with other equipment (loads,
cables,etc.) to form a system. Because the other equipment or the interconnections may not be under
the control of celduc, it shall be the responsibility of the system integrator to ensure that systems
containing SSRs comply with the requirements of any rules and regulations applicable at the system
level.. Consult celduc laboratory which can make some tests in your application.

celduc
r
e
l
a
i
- +
- +
A2 A1
A2 A1
control
control
Load
Charge
N
N
www.celduc.com
s
Rue Ampère B.P. 4
42290 SORBIERS - FRANCE
E-Mail : [email protected]
Fax +33 (0) 4 77 53 85 51
Service Commercial France Tél. : +33 (0) 4 77 53 90 20
Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19