CDP8 Description Constant-Duty Power Supply The Gamewell-FCI CDP8 Constant-Duty Power Supply is a regulated, power-limited, 24 VDC, 8.0 amp. power supply which can be used anywhere a constant 24 VDC source is required. The CDP8 is suited and UL-Listed for fire alarm, access control, and general power supply applications. The Gamewell-FCI CDP8 provides four (4) power-limited, 24 VDC, 3.0 amp. outputs. Each output can be individually configured to shed its load (turn off) during a power failure to extend available standby battery power for designated critical circuits. Each output circuit is monitored for overload or shorted conditions, with the trouble condition indicated by a specific circuit trouble LED and activation of the common trouble relay. Overloaded circuits will automatically restore when the overload is removed. CDP8 Engineer’s Specifications The power supply shall provide four (4) output circuits capable of up to 3.0 amp. continuous 24 VDC each to a maximum of 8.0 amps. total. The output voltage shall be regulated and power-limited. Each output circuit shall be configurable to shed its load with the loss of the primary AC source. The Constant-Duty Power Supply shall include an internal battery charger with charging capacity of 26 AH. It shall also be operational from an externally charged battery. Operational troubles shall be indicated by seven LEDs and a common trouble Form-C relay. The supply shall also have a delayed AC Fail relay. The Constant-Duty Power Supply shall be Gamewell-FCI, model CDP8. Specifications Primary Input Power: 120 VAC, 50/60 Hz, 3.5 A or 220 V, 1.9 A, jumper-selectable. Secondary Power: 24-volt: two 7 – 26 AH batteries Battery Charging Up to 26 AH batteries Capacity: Total Output Power: 8.0 A maximum Standby Current: 0.03 A Output Ratings: 24 VDC fully regulated, 3.0 A maximum per circuit, 8.0 A total Cabinet Dimensions: 18.0" H x 12.5" W x 4.5" D (45.72 H x 31.75 W x 11.43 D cm) Features • • • • • • • • • • • Four (4) configurable monitored outputs 8.0 A, 24 VDC, fully regulated full-load output (power-limited) Seven (7) trouble and status LEDs Common trouble Form-C relay Isolated AC Fail Form-C relay Selectable AC Fail notification relay Ground fault detection 26.0 A battery-charger capability Selectable internal battery charger disable Selectable internal ground fault detection disable Selectable load shedding on AC Fail per output An ISO 9000-2000 Company SIGNALING S8240 7315-1288:163 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com CS-2283 Rev. a page 1 of 2 ©2007 by Honeywell International Inc. All rights reserved. Specifications (Continued) Ordering Information Cabinet Battery Space: Part Number Description Up to two 12 AH batteries (maximum) inside cabinet. Larger batteries require a separate battery cabinet. Relative Humidity: 10 – 93% non-condensing Temperature Rating: 32°F – 120°F (0°C – 49°C) Common Trouble 2A/30 VDC or 120 VAC Relay: AC Fail Relay: 2A/30 VDC or 120 VAC CDP8 BAT-1270 BAT-12120 30069 24 VDC, 8.0 amp. power supply with integral battery charger Battery, 12 VDC, 7 AH (two required for 24 V operation) Battery, 12 VDC, 12 AH (two required for 24 V operation) Power supervision end-of-line relay, 24VDC GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 CS-2283 Rev. a page 2 of 2 www.gamewell-fci.com