GAMEWELL-FCI CPD-7051

CPD-7051
IONIZATION SMOKE DETECTOR
DESCRIPTION
The CPD-7051 dual chamber ionization smoke detector
senses both visible and invisible products of combustion and
is designed for 2-wire and 4-wire system operation. The 360o
smoke entry characteristic permits maximum smoke
response from any direction.
To assure that the detector is functioning, an LED pulses
approximately every 4 seconds to allow for visual
supervision of the detector. Under alarm condition, the LED
lights constantly at full brilliance. An optional base is
available to provide a remote LED function.
A unique gated output circuit design provides improved
stability and transient suppression. Special signal processing
techniques verify the presence of smoke before the detector
will alarm.
Installation of the detector is easy and quick because of
non-polarized connections. The detector head is fixed to the
base by a twist-lock action.
Both functional and sensitivity testing of the device may be
accomplished by means of a test magnet. This simulates the
effect of smoke (approximately 1.3 % per foot obscuration)
entering the chamber.
In addition, the actual sensitivity of the detector may be
measured in direct readout of percent per foot obscuration
with a sensitivity tester and standard voltmeter without the
necessity of removing the detector.
An insect screen protecting the chamber is used to avoid
potential nuisance alarms.
CPD-7051 ionization detectors may be inter-changed with
PSD-7155 or PSD-7156 photoelectric detectors. Optional
bases are available for remote test, indication, 4-wire
operation and/or control functions. See Table 1. In addition,
an MA-001 adapter is available to enable the CPD-7051 to
mount in existing CPD series bases.
APPROVALS
UL (Std 268)
Factory Mutual
C.S.F.M.
New York City MEA
S 1913
0W3A2.AY
7271-1076:115
346-92-E
•
•
•
•
•
•
•
•
•
FEATURES
High Air Flow Dual Chamber
Flashing LED for Visual Supervision
Remote and Local Functional Test
Capability
In-place Sensitivity Measurement in
Percent per Foot Obscuration
Two and Four-wire Low Current
Design
Non-polarized
Surface Mount Technology
High Altitude Operation
Interchangeable Bases
TECHNICAL SPECIFICATIONS
Nominal sensitivity
Standby voltage
Standby current
Operating temperature
Humidity
Air velocity
Altitude
Area of coverage
Radioactive source
1.3 %/ft.
10.2 to 36.8 VDC (24 VDC nominal)
45 uA. (typical) 100 uA. peak @ 24 VDC
32o to 100o F (0o to 49o C)
0-93% relative humidity (non-condensing)
1,000 feet per minute, gusts to 2,000 fpm per UL268
Up to 7,500 feet
30 ft. centers (900 sq. ft. max.) (smooth ceilings)
0.7 microcuries Americium 241 (sealed)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell-fci.com
9020-0303 Rev. H
1 of 2
DIMENSIONAL DATA
INSTALLATION
Installation is simple because of the non-polarized
connection. The detector mounts to the base by a
twist-to-lock action. A removable locking tab secures
the head to the base to provide a degree of vandal
resistance. Units mount directly on a 3-inch round box,
3, 3.5 or 4-inch octagonal box, and 4-inch square box.
No adapters required.
NOTE: The number of two-wire smoke detectors
which can be accommodated per zone varies with the
different control panels. Consult the control panel
instruction manual to determine the capacity.
Refer to N.F.P.A. 72, Chapter 5-3 “Smoke Sensing
Fire Detectors” for spacing, location of detectors and
other guidelines.
WARNING: To prevent detector contamination
during construction, smoke detectors must be
protected from dust and contamination until the
area is clean and dust free. See NFPA 72
MAINTENANCE
Cleaning programs should be adapted to the
individual environment in conformance with NFPA
Standard 72. We recommend, at the least, an annual
cleaning of dust from the detector head by using the
suction from a vacuum cleaner. Refer to the
installation instructions for the complete
procedure.
CAUTION: Do not attempt disassembly of the
factory sealed smoke detector. This assembly
is sealed for your protection and is not to be
opened for servicing. Opening of the detector
will void the warranty.
TABLE I
DETECTOR BASE OPTIONS
Model
2-Wire
2WRLT
2WRB
Compatibility
Identifier
FE51A
FE52A
FE55A
4WRB
N/A
Description
Connects to 2-wire detection circuit via screw terminals.
As above except has output for remote test and LED indicator.
Connects to 2-wire detection circuit via wire-leads.
Has remote test feature, LED indicator and SPDT auxiliary relay
rated 1 amp. @ 30 VDC. Minimum alarm current: .019 amp.
(maximum of 1 per zone)
Connects to 4-wire detection circuit via wire-leads.
Equipped with SPDT auxiliary relay rated 2 amp. @ 30 VDC.
Minimum alarm current .015 amp.
TABLE II
ORDERING INFORMATION
Model
CPD-7051
MA-001
2WRM
4WRM
2040-24
RAI-2
RCM-500
Compatibility
Identifier
I51FE1
Description
Ionization smoke detector.
Adapter to allow mounting to existing CPD series bases.
Relay component of 2WRB.
Relay component of 4WRB
End of line supervisory relay, 24 VDC.
Remote alarm indicator.
Remote alarm indicator /key test switch.
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed
©2006 All Rights Reserved.
by Gamewll-FCI for their use. Specifications subject to change without notice.
2 of 2
9020-0303 Rev. H