GAMEWELL-FCI PSD-7156

PSD-7155 SERIES
PHOTOELECTRIC SMOKE DETECTOR
DESCRIPTION
The PSD series photoelectric smoke detectors respond to a
broad spectrum of both flaming and smoldering fire conditions.
They incorporate state-of-the-art, solid-state, low-voltage
circuitry and are designed for 2-wire and 4-wire installation
with the proper base. High signal-to-noise ratio permits a
significant reduction in light baffling, thereby improving smoke
entry characteristics while reducing nuisance alarms.
Three separate detection identifications are required for alarm
confirmation. This three level detection sequence reduces
nuisance alarms. Each identification is made at two second
intervals. Digital storage of the previous identifications
provides positive and reliable detection.
Functional testing is accomplished by means of a test magnet.
This magnet test meets the requirement of the U.L. Sensitivity
Test Feature. In addition, the actual sensitivity of the detector
may be measured in direct percent per foot obscuration with a
sensitivity tester and standard voltmeter without the necessity
of removing the detector.
The companion model PSD-7156 includes a thermistor heat
detector with a 135o F setpoint and is independent of smoke
detector circuitry.
The PSD photoelectric detectors may be interchanged with
Model CPD-7051 ionization detectors. Optional bases are
available for remote test, remote indication, 4-wire operation
and/or control functions. See Table I. In addition, an MA-001
adapter is available to enable the PSD-7155 and PSD-7156 to
mount in existing Model CPD series bases.
·
·
·
·
·
·
APPROVALS
UL (Std 268)
C.S.F.M.
New York City MEA
Factory Mutual
·
S1913
7272-1076:117
346-92-E
0W3A2.AY
·
·
·
·
FEATURES
Low Profile Appearance
High Air Velocity Rating
Suitable for Mounting Inside Ducts
Flashing LED for Visual Supervision
Remote and Local Functional Test
Capability
In-place Sensitivity Measurement in
Percent per Foot Obscuration
Optional 135o F Thermistor Heat
Detector
Two and Four-wire Low Current
Design
Non-polarized
Three Level Alarm Verification
EMI/RFI Resistant
TECHNICAL SPECIFICATIONS
Nominal sensitivity
Standby voltage
Standby current
Operating temp.
Humidity
Air velocity
Area of coverage
Storage temperature
Finish
Insect screen
3.25 %/ft.
10.2 - 36.8 VDC (24 VDC nominal)
55 uA. (typical) 100 uA. peak @ 24 VDC
32o to 100o F (0o to 38o C ) per UL 268
0 - 93% RH non-condensing
4,000 ft/minute max.
30 ft. centers (900 sq. ft. max.) (smooth ceilings)
-20o to 180o F (-29o to 82o C )
Off-white texture, high impact plastic.
Polyester, 0.0280" mesh size. 54% total open screen area.
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
9020-0304/Ver. 1.8
Dimensional Data
INSTALLATION
Installation is simple because of the nonpolarized
connection. The detector mounts to the base by a
twist-to-lock action. A removable locking tab secures
the head to the base to provide a degree of vandal
resistance. Units mount directly to a 3, 3.5 or 4-inch
octagonal box, 3-inch round box, or 4-inch square box.
No adapters required.
NOTE: The number of two-wire smoke detectors
which can be accommodated per zone varies with
different control panels. Consult the control panel
instruction manual to determine the capacity.
Refer to N.F.P.A. 72, “Smoke Sensing Fire
Detectors” for spacing, location of detectors and other
guidelines.
WARNING: To prevent detector
contamination during construction, smoke
detectors must be protected from dust and
contamination until area is clean and dust
free. See NFPA 72.
MAINTENANCE
Cleaning programs should be adapted to the
individual environment in conformance with NFPA
Standard 72. We recommend, at the least, an annual
cleaning of dust from the detector head by using the
suction of a vacuum cleaner. Refer to the installation
instructions for the complete procedure.
CAUTION: Do not attempt disassembly
of the factory sealed smoke detector. This
assembly is sealed for your protection and
is not to be opened for servicing. Opening
of the detector will void the warranty.
TABLE I - DETECTOR BASE OPTIONS
Model
2-Wire
2WRLT
2WRB
Compatibility
Identifier
FE51A
FE52A
FE55A
4WRB
N/A
Description
Connects to 2-wire detection circuit via screw terminals.
As above except has output for remote test and LED indicator.
Connects to 2-wire detection circuit via wire-leads.
Has remote test feature, LED indicator and SPDT auxiliary relay
rated 1 amp. @ 30 VDC. Minimum alarm current: .019 amp.
(maximum of 1 per zone)
Connects to 4-wire detection circuit via wire-leads.
Equipped with SPDT auxiliary relay rated 2 amps. @ 30 VDC.
Minimum alarm current .015 amp.
ORDERING AND TECHNICAL INFORMATION
Model
PSD-7155
PSD-7156
MA-001
2WRM
4WRM
2040-24
RAI-2
RCM-500
Compatibility
Identifier
P55FE1
P56FE1
Description
Photoelectric smoke detector.
Photoelectric smoke detector with 135o F thermistor heat detector.
Adapter to allow mounting to existing CPD series bases.
Replacement relay component of 2WRB.
Replacement relay component of 4WRB.
End of line supervisory relay, 24 VDC.
Remote alarm indicator.
Remote alarm indicator/key test switch.
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed
by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
1997 All Rights Reserved