GAMEWELL-FCI GW

GW-UDACT
Universal Digital Alarm
Communication Transmitter
Description
The Gamewell-FCI Universal Digital Alarm Communicator
Transmitter (GW-UDACT) is designed for use with all
Gamewell-FCI 600 Series Fire Alarm Control Panels. The
GW-UDACT transmits system status to UL-Listed Central
Station Receivers via the public switched telephone network.
The GW-UDACT is compact in size and may be mounted
externally in a separate cabinet. EIA-485 annunciator communications bus and regulated 24-volt connections are
required.
The GW-UDACT is capable of transmitting the status of
software zones (Alarm and Trouble), System Trouble,
Panel Off-Normal, Supervisory, Bell Trouble, Low Battery,
and AC Fail. GW-UDACT is capable of transmitting the status of all zones associated with each panel. Reporting is in
the form of software zones or groups (up to 256). Each
zone can be programmed for fire, waterflow, supervisory,
etc.
NOTE: Descriptions regarding point capacity, listed above,
are for receivers which receive in Ademco Contact ID format. See chart on page 2 for compatible receivers.
Engineer’s Specifications
The Universal Digital Alarm Communicator Transmitter
(UDACT) shall continuously supervise the state of each of
two connected Telco Lines (at approximately one-minute
intervals) by a Line-DC level measurement. If supervision
fails, a Line #1 or Line #2 Trouble event will be reported.
Once a line has been restored, a Line Trouble Restored
event will be reported. The product will always report
events sorted in the order in which they are received/recognized. The UDACT shall be capable of reporting multiple
events to a single account number, within a single call session. Up to three attempts for a single message not yet
reported will be made within a single call attempt. A failure
to communicate to either or both accounts will generate a
corresponding event which will be queued for reporting.
The unit shall be a Gamewell-FCI model GW-UDACT. The
unit shall be capable of reporting Alarm, Trouble, Supervisory, and Waterflow events and event-specific restorals for
each of up to 256 groups or software zones.
GW-UDACT
Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Maximum of 14 point trouble messages transmitted.
Dual phone lines and telephone line voltage detect.
Surface-mount technology and mounts directly in panel.
Compact in size: 6.75" x 4.25" (17.145 x 10.795 cm).
Built-in programmer.
Built-in four-character red seven-segment LED display.
Manual test report function.
Communicates vital system status including:
- Independent zone fire alarm and non-fire alarm.
- Independent zone trouble and non-zone trouble.
- Independent zone supervisory.
- AC (mains) power loss (programmable).
- Low battery and earth fault.
- System off-normal.
- 12 or 24 hour test signal.
- Abnormal test signal per UL requirements.
- EIA-485 communication bus failure.
Annunciation of UDACT troubles including: loss of phone
lines, communication failure with either central station, total
communication failue.
Troubleshoot mode converts keypad to DTMF touchpad.
Individual LEDs for: power, EIA-485 loss, manual test, kissoff,
comm fail, primary line seize, secondary line seize, and
modem communications.
Open collector relay driver for total communications failure or
UDACT trouble.
Real-time clock.
Extensive transient protection.
SIGNALING
S521 7300-1288:147
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell.fci.com
CS-2501 Rev. B page 1 of 3
©2006 Gamewell-FCI. All rights reserved.
Compatible Receivers
Format #
(Addresses 16 & 42)
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
4 + 1 Ademco Express
4 + 2 Ademco Express
3 + 1/Standard/1800/2300
Ademco
685 (1)
Silent
Knight
9000
4
4
4
4 (2)
4
4 (2)
4
4 (2)
ITI
CS-4000
(3)
4
FBI
CP220FB
Osborne
Hoffman
Models
1&2
4
4
4 (4)
4 (8)
4
4 (4)
4
4 (4)
4
4 (4)
4
4 (4)
4
4 (4)
4
4
4
Radionics
600/
6500
(5)
Sescoa
300R
(7)
4 (5,6)
Sur-Gard
MLR-2
(9)
4
4
4
4
4
4
4
4
4
4
4
4
4
4
(NOT USED)
3+1/Standard/1900/1400
(NOT USED)
4+1/Standard/1800/2300
4
4 (5)
(NOT USED)
4+1/Standard/1900/1400
4
4 (2)
4
4 (2)
4
4 (2)
(NOT USED)
4+2/Standard/1800/2300
4
4 (5)
(NOT USED)
4+2/Standard/1900/1400
(NOT USED)
Ademco Contact ID
4
4F
(NOT USED)
With 685-8 Line Card with Rev 4.4d software.
With 9002 Line Card Rev 9035 software or 9032 Line Card with 9326A software.
Rev. 4.0 software.
FBI CP220FB Rec-11 Line Card with Rev 2.6 software and a memory card with Rev 3.8 software.
Model 6500 with Rev 600 software.
Model 6000 with Rev 204 software.
With Rev B control card at Rev 1.4 software and Rev C line card at Rev 1.5 software.
Model 2 only.
Version 1.62 software.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell.fci.com
CS-2501 Rev. B page 2 of 3
Specifications:
Ordering Information:
Electrical
Part Number
Model
Standby current:
40 mA.
Current while communicating: 75 mA.
Nominal voltage:
24 volts DC.
Communication formats:
• 3+1 Standard.
• 4+1 Standard.
• 4+2 Standard.
• 4+1 and 4+2 Ademco Express.
• Ademco Contact ID
Note: Ademco Contact ID must be used for independent
zone reporting.
Mounting:
When used with the Gamewell 600 Series, the
GW-UDACT mounts directly in the panel cabinet.
Relative Humidity:
93% non-condensing
Temperature Rating:
32 F - 120 F
(0 C - 49 C)
GW-UDACT
Gamewell Universal Digital Alarm
Communicator Transmitter for use with
Gamewell 600 Series panels. Includes
operating and programming instructions, and mounting.
DACT phone cord, 7 ft. (2.13 m) long
(two required).
MCBL-7