POWER-ONE PMP11.60

PMP 11
Rectifier Module
Description
The Power-One PMP 11 rectifier module
provides cost-effective power in a high
density solution. Built on the latest
advances in the resonance switch mode
approach (soft-switching), the PMP 11 is
the next evolution in our convection
cooled rectifier series.
Optimized for telecom applications, the
module is designed to work in a multitude
of different subrack/shelf configurations
incorporating the PCU/PCS controller and
varying distribution options.
Features
• 208/240 VAC input
• 24V, 48V, or 60V DC output
• Input overvoltage disconnection
• Thermal protection
• Active load sharing
• Hot-swappable
• Up to 92% efficient
• International standards compliance
• Natural convection cooling
• Low weight
PPS 10 6500 System
Shown
www.power-one.com
PMP 11
Rectifier Module
Input
Mechanical
Dimensions
62 x 261 x 231mm
(2.4 x 10.3 x 9.1in.)
205-250V AC ±10% single phase,
(44-66Hz)
185-160V AC at reduced output power
Weight
3.1kg (6.8lbs.)
Current
(max.)
<6.8A
Cooling
Natural convection
Soft Start
<12A peak maximum 220ms
Harmonics
EN 61000-3-2
Power Factor >0.99 at max. load
Surge
Immunity
EN 61000-4-5
Fuse
T 8A
Connection
IEC-320/C14
EMC
EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B
Model
PMP 10.24A
Input
Voltage
PMP 11.48
<7.0A
PMP 11.60
<7.0A
Insulation
Enclosure
IP20
Mounting
Up to 8 modules per shelf
Other Technical Data
Safety
EN 60950
UL 1950 and IEC60950 , Class 1
CSA C22-2 No. 950
Protection
Short circuit proof, automatic
current limiting, selective shutdown
of modules at excessive output
voltage. Thermal protection
reduces the output power at
environmental temperatures above
maximum level. Thermal
protection with shut down at
>55°C. Automatic restart.* Input
over-voltage disconnection at
>275VAC with automatic reset at
>260VAC.
Output
Model
PMP 10.24A
PMP 11.48
PMP 11.60
Output Voltage
22-28V DC
44-56V DC
56-71V DC
Power (max.)
1000W
(25-28V)
1100W
(50-57.7V DC)
1100W
(60-71V DC)
Current (max.)
43A
23A
18.5A
Efficiency
>88%
>91%
>92%
(at 40-90% Load)*
Tolerance
Reinforced insulation tested at:
4.25 kV DC primary-secondary,
2.12 kV DC primary-ground,
0.75 kV DC secondary ground
Vout +/- 1%
Green LED
Power ON
Red LED
High output
voltage/ shutdown
Red LED
Low voltage/
module failure
Indications
Transient
Response
+/- 5% at load variation 10-90%
or 90-10%, recovery time 10ms
Load Sharing
<5% of nominal current
Ripple
<100mV p-p (BW. 30MHz)
Psophometric
<2mV, according to CCITT norms
Connection
EMC
Audible
Noise
<35dBA
Operating
Temperature*
-25 to +55°C up to 2000m
-25 to +45°C above 2000m
Storage
Temperature
-40 to +85°C
Radiated EMC
EN 61000-6-2, EN 61000-6-3,
FCC Part 15, Class B
Environment
Storage:
Transport:
Operation:
DIN 41612F
EN 61000-6-2, EN 61000-6-4
*Average performance for a single module.
ETS 300 019-2-1
ETS 300 019-2-2
ETS 300 019-2-3
Note: All specifications are subject to change without notification.