POWER-ONE PMP7

PMP 7
Rectifier Module
Description
The Power-One PMP 7 rectifier module
provides a cost-effective power solution
in the highest possible density. Built on
the latest advances in the resonance
switch mode approach (soft-switching),
the PMP 7 is the next evolution in our
small convection cooled rectifier series.
Optimized for telecom applications, the
module is designed to work in a multitude
of different subrack/shelf configurations
incorporating the Power-One PCU
controller and various distribution
options.
Features
• 208/240 VAC input
• 24V, 48V, or 60V DC output
• Input overvoltage disconnection
• Thermal protection
• Active load sharing
• Hot-swappable
• Up to 92% efficient
• International standards compliance
• Natural convection cooling
PPS 7 3500 System
Shown
• Low weight
www.power-one.com
PMP 7
Rectifier Module
Mechanical
Input
Model
PMP 7.24
PMP 7.48
Input
Voltage
205-250V AC ±10% single phase,
(44-66Hz) (-15% for PMP7.60)
185-160V at reduced output power
Current
(max.)
<3.55A
<4.35A
Dimensions
62 x 129 x 232mm
(2.4 x 5.1 x 9.1in.)
Weight
1.65kg (3.6lbs.)
Cooling
Natural convection
<4.35A
Soft Start
<11A peak
max. 5ms
Harmonics
EN 61000-3-2
Power Factor >0.99 at max. load
Surge
Immunity
EN 61000-4-5
Fuse
T 6,3A
Connection
IEC-320/C14
EMC
<15.5A peak
max. 5ms
PMP 7.60
<20A peak
max. 5ms
Insulation
Enclosure
IP20
Mounting
In 19” subrack up to 5 modules
Other Technical Data
Safety
EN 60950
UL 1950 and IEC60950 , Class 1
CSA C22-2 No. 950
Protection
Short circuit proof, automatic
current limiting, selective shutdown
of modules at excessive output
voltage. Thermal protection
reduces the output power at
environmental temperatures above
maximum level. Shut down at
>75°C with an automatic restart.*
Input over-voltage disconnection at
>275VAC with automatic reset at
>260VAC.
EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B
Output
Model
PMP 7.24
PMP 7.48
PMP 7.60
Output
Voltage
22.5-28VDC
45-56VDC
56-70.5VDC
Power (max.)
560W
672W
635W
Current
(max.)
20A
12A
9A
Efficiency
>89.5%
(at 40-90% load)*
Reinforced insulation tested at:
4.25 kV DC primary-secondary,
2.12 kV DC primary-ground,
0.75 kV DC secondary ground
>92%
>92%
Green LED
Power ON
Red LED
High output
voltage/ shutdown
Red LED
Low voltage/
module failure
Indications
Tolerance
Vout +/- 1%
Transient
Response
+/- 5% at load variation 10-90%
or 90-10%, recovery time 10ms
Load Sharing
<5% of nominal current
Audible
Noise
<35dBA
Ripple
<100mV p-p (BW. 30MHz)
Operating
Temperature*
-25 to +55°C up to 2000m
-25 to +45°C above 2000m
Psophometric
<2mV, according to CCITT norms
Storage
Temperature
-40 to +85°C
Radiated EMC
EN 61000-6-2, EN 61000-6-3,
FCC Part 15, Class B
Environment
Storage:
Transport:
Operation:
Connection
EMC
DIN 41612F
EN 61000-6-2, EN 61000-6-4
*Average performance for a single module.
ETS 300 019-2-1
ETS 300 019-2-2
ETS 300 019-2-3
Note: All specifications are subject to change without notification.
11V0005-028 PMP 7 V3.0
www.power-one.com