ALLEN-BRADLEY 1755-L1

Safety PLCs
GuardPLC 2000 Safety System
1755–L1
Specifications
User Memory
Operating Voltages
Current Consumption
Operating Temperature
Storage Temperature
Operating Humidity
Shock
Vibration
Weight
Dimensions (WxHxD)
500 KB application code memory
500 KB application data memory
3.3V DC
5V DC
3.3V @ 1.5A5V @ 0.1A
0°C to 60°C (32°F to 140°F)
-40°C to 85°C (-40°F to 185°F)
5 to 95% (without condensation)
Operating: 30g non operating: 50g
Operating: 2g @ 10 to 500Hz
6.3 kg (fully equipped)
255 x 285 x 210mm
(10 x 11.22 x 8.26in)
The GuardPLC2000 CPU has one 10/100BaseT Ethernet port for
programming and configuration and two interface ports (9-pin
D-shell) for serial connections. The CPU controls all functions of
the GuardPLC 2000 system as well as communication to other
systems. LEDs display the operating modes: Run and Error for the
I/O modules; Run, Error, Stop, Programming and Forcing for the
CPU.
Typical Applications
•
•
•
•
•
•
•
Perimeter guarding for Robot/weld cells
Perimeter guarding for Packaging Machines
Entertainment industry (ride control and ski lift control)
Semi-conductor industry
Press Control
Burner Management
Shipping (rudder controls)
Features
•
•
•
•
•
•
Metal chassis
I/O self test
24V DC digital I/O
Expandable number of I/O
Multiple I/O test points
Certified by TÜV for use in applications up to SIL 3 according to
IEC 61508; EN 954–1, Category 4
• Programmed with RSLogix Guard Software
• RS–232 port for ASCII communication (read only)
• Ethernet port for programming, configuration and Peer-to-Peer
8-7
Safety PLCs
GuardPLC 2000 Safety System
Chassis 1755–A6 Power Supply 1755–PB720
The GuardPLC chassis houses the GuardPLC 2000 controller,
power supply, and up to six safety I/O modules. A filler module is
also available for unused slots (catalogue number 1755–N2).
Specifications
Description
Number of Slots
Dimensions (WxHxD)
Weight
Mounting
Catalogue Number
8-8
Expansion chassis for adding safety I/O
modules
6
255 x 285 x 210mm (10 x 11.2 x 8.3in)
3.3kg (7.2lbs)
Back-panel mounting
1755-A6
The power supply module transforms the system supply voltage
from 24V to 3.3V DC/5V DC (used for internal I/O bus). It
occupies the left-most slot of the GuardPLC 2000 chassis. The
power supply comes with a lithium battery, which has a four-year life
span, that is used for back-up. Four LEDs indicate the power supply,
battery voltage, and faults.
Safety PLCs
GuardPLC Safety Control Systems
Overview
Safety-related input modules are automatically subjected to a highgrade, cyclical self-test in both the GuardPLC 1200 and GuardPLC
2000 systems during operation. These test routines are TÜV
approved and help ensure the safe function of the respective
module. When an error is detected, the application is provided with
an “0” signal, and a detailed error message is generated optionally. If
there are minor failures in the module (no effect on the safety
function), no user diagnostic information is generated.
• The GuardPLC 2000 digital I/O module has 24 inputs and 16
outputs for signals, and the inputs and outputs are electrically
isolated in groups of eight. The GuardPLC 1200 digital I/O
module has 20 inputs and 8 outputs. In case of module error, the
outputs are switched to the de-energized state.
• The analog output module, which is available in the GuardPLC
2000 system only, the eight channels on the analog input module
can be used as eight single-ended or four differential analog
inputs for 0 to 20 mA. No mixing is allowed. The incoming
signals are converted into an integer value with a 12-bit
resolution. This value then can be used in the user program. In
case of module error, the logic outputs of the modules are
switched to the de-energized state.
• The analog output module, which is available in the GuardPLC
2000 system only, has eight analog outputs with a 12-bit
resolution. They are electrically isolated in groups of two outputs
with a common ground. The output ranges of the module can be
switched to 0 to 21 mA, 0 to 10.25V DC or -10.25 to +10.25V
DC. For each channel, the module has a switch placed on the
printed circuit board to switch the different output ranges. In
case of module error, the outputs are switched to the deenergized state.
• The counter module has two operating modes: counter mode and
decoder mode. The module has 24-bit counters with two outputs
each. The counters can operate in both directions (up and down)
and have a separate reset input. The input signals of 5V can be in
a frequency range of 0 to 1 MHz in a GuardPLC 2000 system.
Use a PC to configure the input voltage, which can be 5V or in a
range of 10 to 26.4V. In case of module error, the outputs are
switched to the de-energized state. The counter can count pulses
with direction and reset inputs up to 1 MHz in the GuardPLC
2000 system and up to 100 KHz in the GuardPLC 1200 system.
The counter module can also be used as an 8-bit gray code
encoder in the GuardPLC 2000 system or a 6-bit gray code
encoder in the GuardPLC 1200 system.
I/O Hardware
Safety Digital I/O Combination Module
Max
Maximum
Operating
Continuous Number
Catalogue
Operating Signal Delay Off-State On-State Number Voltage/ Signal Delay Current
of
Number
Voltage
(max)
Current
Current of Inputs
Type
(max)
per Output Outputs Applications
1755–
GuardPLC
GuardPLC
2000
2000
Safety
on = 70µs
on = 70 µs
applications
off = 70 µs
off = 15 µs
2mA @ 10V
2A (8A
1.5mA @
18.4requiring 24V
10-30V
13mA @
24
total per
16
5V DC
26.8V DC
DC inputs and –IB24XOB16
DC
30V
module)
GuardPLC
GuardPLC
24V DC
1200
1200
outputs
on = 120 µs
on = 15 µs
off = 200 µs
off = 90 µs
Safety Analog I/O Modules
Number of Inputs/
Outputs
4 differential or 8
single–ended inputs
— selectable
8 outputs
Data Format
12-bit signed
Integer (natural
binary)
12-bit signed
Integer (natural
binary)
Channel Update/
Resolution
Catalogue
Number
1755–
Voltage Range
Current Range
Back Plane
Current Load
±10V
0-10V DC
0-20.5mA
(with shunt)
150 mA/3.3V DC
400 mA/24V DC
12 bits (0-1000)
IF8
±10V
0-10V DC
0-20mA
150 mA/3.3V DC
400 mA / 24V DC
12 bits (0-1000)
OF8
Safety Counter Module
Inputs
Maximum Input
Frequency
Outputs
Location
2
1 MHz
4
Any unused slot
Back Plane Current Load Catalogue Number
0.1A / 24V DC without load
0.8A (3.3V DC), 0.1A (5V
1755-HSC
DC)
8-9
Safety PLCs
GuardPLC Safety Control Systems
Weights
Catalogue Number and Weight in kg (lb)
• 1754–L28BBB 0.68 (1.5)
• 1755–A6 3.3 (7.3)
• 1755–HSC 0.26 (0.57)
• 1755–IB24XOB16 0.26 (0.57)
• 1755–IF8 0.24 (0.53)
• 1755–L1 0.28 (0.62)
• 1755–OF8 0.28 (0.62)
• 1755–PB720 0.82 (1.8)
Programming Software
RSLogix Guard Software
The safety aspects of the GuardPLC Safety Control System extend
beyond the physical control platforms. Like the controllers,
programming software must also be certified to support Safety
Integrity Level 3 (SIL 3) applications and is a critical component of
the total safety system. The programming and configuration tool for
GuardPLC 2000 and GuardPLC 1200 safety controls is RSLogix
Guard software, designed to operate with Microsoft Windows NT
v4.0 or Windows 2000 operating system.
Since the RSLogix Guard software is a function block-based
programming tool, there is no need for programmers to learn a
cryptic programming language. Using such pre-defined elements as
AND and OR gates, numerical functions, counters, and timers,
programmers select and “drag” the appropriate functions onto their
workstation screen. These functions, like the controllers, have been
certified for use in applications up to SIL 3. Subsequent
programming is as easy as drawing lines to “wire” inputs and
outputs to the logical elements and making connections to hardware
by way of user-defined variables or tags.
The RSLogix Guard software is also used for system diagnosis and
debugging. It can provide the status of controller CPU and I/O and
can be used to obtain information about the application program.
8-10
Features
• Save programming and configuration time using software that’s
already certified for use in applications up to SIL 3
• Program your safety control system using pre-defined graphical
elements and a “drag and drop” palette
• Tag-based system
System Requirements
To install RSLogix Guard Programming Software on a personal
computer, you need to meet the following minimum requirements.
CPU Processor
RAM
Graphic Adaptor
Hard Disk Space
Operating System
Pentium II, 400 MHz
128M bytes
Resolution: 1024 x 768 pixels (XGA)
30M bytes (minimum) for RSLogix
Guard plus space for user defined
programs
Windows NT v4.0 or Windows 2000
Ordering Information
You can install RSLogix Guard Programming Software on a local
drive only (not a network).
Description
Catalogue Number
RSLogix Guard 1200 for GuardPLC 1200
Packaged Safety Controller
1754–PCS
• 200 variables per POU (Program Organization
Unit)
RSLogix Guard 2000 for GuardPLC 1200 and
GuardPLC 2000 Safety Controllers
• 650 variables per POU (Program Organization
1755–PCS
Unit)
• User-defined function blocks