NI NIPS-16

Industrial Power Supplies
NI PS-15, NI PS-16, NI PS-17 NEW!
■■
■■
■■
■■
■■
■■
■■
■■
■■
24 VDC power supplies for CompactRIO,
NI CompactDAQ, Compact FieldPoint,
NI Single-Board RIO, NI Smart Cameras,
and NI touch panel computers
Full output power between
-25 and +60 °C
115/230 V autoselect input
Efficiencies up to more than 90 percent
Low input rush current
20 or 50 percent power reserves
for dynamic loads
Toolless spring-clamp terminals
for easy field connectivity
DIN-rail mounting included and
panel/side mount accessories available
-25 to 70 °C operating
temperature range
Product
Temperature
Range (°C)
Size WxHxD (mm)
Weight (g)
Part Number
90 to 132/
180 to 264 VAC
-25 to +70
32 by 124 by 117
500
781093-01
240
90 to 132/
180 to 264 VAC
-25 to +70
60 by 124 by 117
700
781094-01
480
85 to 276 VAC/
88 to 375 VDC
-25 to +70
82 by 124 by 127
1200
781095-01
Output Voltage (V)
Output Current (A)
Output Power (W)
Input Voltage
PS-15
24 to 28
5
120
PS-16
24 to 28
10
PS-17
24 to 28
20
Table 1. NI Power Supply Selection Guide
Overview and Applications
Mounting Options
The NI PS-15, PS-16, and PS-17 industrial power supplies feature long expected
The PS-15/16/17 power supplies include clips for DIN-rail mounting.
life, generous power reserves, and compact size. The 24 V supplies are ideal
National Instruments provides optional accessories for wall, panel, and side
for powering any NI CompactRIO, NI Compact FieldPoint, NI Single-Board RIO,
mounting to minimize install depth. You can couple the included DIN-rail
NI Smart Camera, NI touch panel, or NI CompactDAQ system, as well as heavy
mounting bracket with the side mount kit for a low-profile DIN-rail installation.
accessory loads such as DC motor drives. The DIN-rail system and spring clamp
terminals do not require tools and make installation fast and easy. Wide range
Product
Installed
Width
(mm)
Installed
Height
(mm)
Installed Depth
(mm)
Bracket
Weight (g)
and autoselect input voltages help you avoid user errors. The wide operating
Part
Number
temperature range and extraordinary EMI immunity enables trouble-free
199432-01
Panel mount kit
for PS-15/16/17
Equal to
PS width
143
PS depth + 7
50
199429-01
Side mount kit
for PS-15
118
145
38 (panel)/
44 (DIN)
140
199430-01
Side mount kit
for PS-16
118
145
66 (panel)/
72 (DIN)
180
199431-01
Side mount kit
for PS-17
138
145
88 (panel)/
94 (DIN)
205
operation even under harsh conditions.
Depending on the device, NI industrial power supplies guarantee power
reserves of 20 to 50 percent. For the PS-15 and PS-16, you can use this extra
current continuously for ambient temperatures under 45 °C. With these power
reserves, you may not need to oversize for dynamic loads, but you can simply
choose a unit that meets the operating requirements. In some cases, you can
select a smaller unit to save money and space.
Table 2. NI Power Supply Mounting Accessories (See the NI PS-15/16/17 User Guide
manual at ni.com/manuals for more information.)
Industrial Power Supplies
Specifications
Environmental
Specifications subject to change without notice. For complete specifications,
Operational Temperature
see the NI PS-15/16/17 User Guide manual at ni.com/manuals.
PS-15/16/17...................................... -25 to +70 °C
Dimensions and Weight
Output Derating
WxHxD (mm)
PS-15................................................. 3 W/°C (60 to 70 °C)
PS-15................................................. 32 by 124 by 117
PS-16................................................. 6 W/°C (60 to 70 °C)
PS-16................................................. 60 by 124 by 117
PS-17................................................. 12 W/°C (60 to 70 °C)
PS-17................................................. 82 by 124 by 127
Note: To meet this operating temperature range, follow the guidelines in the
Weight
user guide for your industrial power supply.
PS-15................................................. 500 g (1.1 lb)
PS-16................................................. 700 g (1.54 lb)
PS-17................................................. 1200 g (2.65 lb)
(reduce output power above 60 °C)
Storage Temperature
PS-15/16/17...................................... -40 to +85 °C
Ingress Protection (EN/IEC 60529)
Input Characteristics
PS-15/16/17...................................... IP 20
Input Voltage Range
Operating Humidity (IEC 60068-2-30)
PS-15/16 voltage............................... 90 to 132 VAC/180 to 264 VAC
PS-15/16/17...................................... 5 to 95% RH, noncondensing
PS-17 voltage.................................... 85 to 276 VAC/88 to 375 VDC
Maximum Altitude................................. 6000 m (reduce output power
PS-15/16/17 input frequency................. 50 to 60 Hz ±6%
Power Factor
Altitude Output Derating (above 2000 m)
PS-15................................................. 0.56 @120 VAC, 24 V, 5 A
PS-15................................................. 7.5 W or 5 °C per 1000 m
PS-16................................................. 0.59 @120 VAC, 24 V, 10 A
PS-16................................................. 15 W or 5 °C per 1000 m
PS-17................................................. 0.95 @120 VAC, 24 V, 20 A
PS-17................................................. 30 W or 5 °C per 1000 m
Output Characteristics
or ambient temp above 2000 m)
Pollution Degree (EN 50178).................. 2, not conductive
Output Voltage Range
Shock and Vibration
PS-15/16/17...................................... 24 to 28 VDC
Operating Vibration, Sinusoidal (IEC 60068-2-6)
Output Power (-25 to +60 °C)
PS-15/16/17...................................... 2 to 17.8 Hz: ±1.6 mm; 17.8 to 500 Hz:
PS-15 ................................................ 120 W
PS-16................................................. 240 W
Operating Shock (IEC 60068-2-27)
PS-17................................................. 480 W
PS-15/16/17...................................... 30 g, 6 ms, 20 g, 11 ms,
Output Current (-25 to +60 °C)
PS-15................................................. 5 A @24 V/ 4.3 A @28 V
Operating Vibration, Random (60060-2-64)
PS-16................................................. 10 A @24 V/ 8.6 A @28 V
PS-17................................................. 0.5 m2(s3); 2 hours/axis
2 g, 2 hours/axis
3 bumps/direction, 18 bumps total
PS-17................................................. 20 A @24 V/ 17 A @28 V
Ripple and Noise Voltage
PS-15/16............................................ 50 mVpp
PS-17................................................. 100 mVpp
Output Capacitance
PS-15................................................. 1800 µF
PS-16................................................. 7000 µF
PS-17................................................. 8500 µF
Ordering Information
NI PS-15..........................................................................................781093-01
NI PS-16..........................................................................................781094-01
NI PS-17..........................................................................................781095-01
Accessories
Panel mount kit for NI PS-15/16/17...............................................199432-01
Efficiency
BUY NOW
PS-15................................................. 89.4% @120 VAC, 24 V, 5 A
For complete product specifications, pricing, and accessory information,
call 800 813 3693 (U.S.) or go to ni.com/compactrio.
PS-16................................................. 91.0% @120 VAC, 24 V, 10 A
PS-17................................................. 92.4% @120 VAC, 24 V, 20 A
BUY ONLINE at ni.com or C ALL 800 813 36 93 (U.S.)
2
Industrial Power Supplies
Safety
Approvals
These products are designed to meet the requirements of the following
18WM
LISTED
IND. CONT. EQ.
standards of safety for electrical equipment for measurement, control, and
RECOGNIZED as Information Technology Equipment (UL 60950-1)
laboratory use:
SELV......................................................IEC/EN 60950-1
PELV......................................................EN 60204-1, EN 50178, IEC 60364-4-41
Note: For UL and other safety certifications, refer to the product label or visit
ni.com/certification, search by model number or product line, and click the
appropriate link in the Certification column.
LISTED as Industrial Control Equipment (UL 508)
GL
GL (Germanischer Lloyd) classified for marine and
offshore applications. Environmental category: C, EMC2
Online Product Certification
Refer to the product Declaration of Conformity (DoC) for additional regulatory
compliance information. To obtain product certifications and the DoC for this
Electromagnetic Compatibility
product, visit ni.com/certification, search by model number or product line,
This product meets the requirements of the following EMC standards for
and click the appropriate link in the Certification column.
electrical equipment for measurement, control, and laboratory use:
EN 61000-6-2, EN 61000-6-1
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
EN 61000-4-6, EN 61000-4-11
VDE 0160
EN 55011 Emissions; Group 1, Class A
CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A
Environmental Management
Note: For EMC compliance, operate this product according to the documentation.
Web page at ni.com/environment. This page contains the environmental
CE Compliance
regulations and directives with which NI complies, as well as other
■■
■■
■■
■■
■■
National Instruments is committed to designing and manufacturing products in
an environmentally responsible manner. NI recognizes that eliminating certain
hazardous substances from our products is beneficial not only to the environment
but also to NI customers.
For additional environmental information, refer to the NI and the Environment
This product meets the essential requirements of applicable European Directives
environmental information not included in this document.
as follows:
2006/95/EC, Low-Voltage Directive (safety)
2004/108/EC, Electromagnetic Compatibility Directive (EMC)
Waste Electrical and Electronic Equipment (WEEE)
■■
■■
EU Customers: At the end of their life cycle, all products must be sent to a
WEEE recycling center. For more information about WEEE recycling centers and
National Instruments WEEE initiatives, visit ni.com/environment/weee.htm.
BUY ONLINE at ni.com or C ALL 800 813 36 93 (U.S.)
3
NI Services and Support
your needs around the globe and through
PL
AN
MA
IN
NI has the services and support to meet
IN
TA
the application life cycle – from planning
and development through deployment and
SERVICE
NEEDS
ongoing maintenance. We offer services
P
DE
EL
OP
and service levels to meet customer
LO
Y
requirements in research, design, validation,
V
DE
and manufacturing.
Visit ni.com/services.
Local Sales and Technical Support
In offices worldwide, our staff is local to the country, giving you access to
engineers who speak your language. NI delivers industry-leading technical
support through online knowledge bases, our applications engineers,
and access to 14,000 measurement and automation professionals within NI
Developer Exchange forums. Find immediate answers to your questions at
ni.com/support.
We also offer service programs that provide automatic upgrades to your
application development environment and higher levels of technical support.
Training and Certification
Visit ni.com/ssp.
NI training is the fastest, most certain route to productivity with our products.
Hardware Services
NI training can shorten your learning curve, save development time, and reduce
maintenance costs over the application life cycle. We schedule instructor-led
System Assurance Programs
courses in cities worldwide, or we can hold a course at your facility. We also
NI system assurance programs are designed to make it even easier for you
offer a professional certification program that identifies individuals who have
to own an NI system. These programs include configuration and deployment
high levels of skill and knowledge on using NI products.
services for your NI PXI, CompactRIO, or Compact FieldPoint system. The NI Basic
Visit ni.com/training.
System Assurance Program provides a simple integration test and ensures that
Professional Services
your system is delivered completely assembled in one box. When you configure
your system with the NI Standard System Assurance Program, you can select
Our NI Professional Services team is composed of NI applications and systems
from available NI system driver sets and application development environments
engineers and a worldwide National Instruments Alliance Partner program of
to create customized, reorderable software configurations. Your system arrives
more than 600 independent consultants and integrators. Services range from
fully assembled and tested in one box with your software preinstalled. When
start-up assistance to turnkey system
you order your system with the standard program, you also receive system-
integration. Visit ni.com/alliance.
specific documentation including a bill of materials, an integration test report,
a recommended maintenance plan, and frequently asked question documents.
OEM Support
Finally, the standard program reduces the total cost of owning an NI system
We offer design-in consulting and product integration assistance if you want to
online product advisors at ni.com/advisor to find a system assurance program
use our products for OEM applications. For information about special pricing and
services for OEM customers, visit ni.com/oem.
by providing three years of warranty coverage and calibration service. Use the
to meet your needs.
Calibration Services
NI recognizes the need to maintain properly calibrated devices for highaccuracy measurements. We provide manual calibration procedures, services
to recalibrate your products, and automated calibration software specifically
designed for use by metrology laboratories. Visit ni.com/calibration.
Repair and Extended Warranty
NI provides complete repair services for our products. Express repair and
advance replacement services are also available. We offer extended warranties
to help you meet project life-cycle requirements. Visit ni.com/services.
ni.com
n
800 813 3693
National Instruments
n
[email protected]
©2009 National Instruments. All rights reserved. CompactRIO, FieldPoint, National Instruments, National Instruments Alliance Partner, NI, ni.com, and NI CompactDAQ are trademarks of National Instruments.
Other product and company names listed are trademarks or trade names of their respective companies. A National Instruments Alliance Partner is a business entity independent from National Instruments
and has no agency, partnership, or joint-venture relationship with National Instruments. 2009-11329-161-101-D