SYSTEMSENSOR H24

A U D I B L E / V I S I B L E
N O T I F I C A T I O N
Wall-Mount Horns, Strobes,
and Horn/Strobes
Models Available*
Horn/Strobes
P1215
P2415
P2430
P24110
P121575
P241575
P2475
Strobes
S1215
S2415
S2430
S24110
S121575
S241575
S2475
Horn/Strobe
Strobe
Horn
Back Box Skir t
Horns
H12/24
*Refer to Ordering Information for other
configurations
Product Overview
Meet UL and ADA signaling requirements
Lower current draw
More devices per loop
Lower installed cost
Universal mounting plate included
Accessory mounting plates available
Field-selectable horn tones
Electromechanical / 3kHz
Temporal 3 / Non-temporal 3
High / Low dBA output
Available in 15, 15/75, 30, 75, and 110
candela
Synchronizable horns and strobes with
Sync•Circuit™ module
Aesthetic design
System Sensor’s SpectrAlert® wall-mount series includes a complete line of electronic
horns, strobes, and horn/strobes. Intended for primary signaling use, SpectrAlert
products meet UL1971, UL464, and Americans with Disabilities Act requirements.
Technology. With its extremely efficient reflector design and Xenon flash tube,
SpectrAlert offers current draw reductions as high as 40% over previous generation designs. By consuming less current, the flexibility to connect more devices
per loop is possible, for a lower installed cost.
Installation. SpectrAlert products offer installation ease which also lowers the
installed cost. By taking up no room in the back box, SpectrAlert strobes and
horn/strobes make wiring connections simpler and faster. Each SpectrAlert
includes a universal mounting plate for 4″ square and single gang back box
mounting. Accessory mounting plates are also available for small footprint or
surface mount applications.
Flexibility. SpectrAlert offers the flexibility to meet a broad range of
requirements. The SpectrAlert horns and horn/strobes feature a number of
field-selectable/reversible horn tones. For visible requirements, SpectrAlert
strobes and horn/strobes are available in a wide variety of configurations to
address non-sleeping area, sleeping area, and corridor requirements.
Offerings include 24-volt models at 15, 15/75, 30, 75, and 110 candela,
and 12-volt devices at 15 and 15/75 candela.
Aesthetics. To meet building owner aesthetic requirements, SpectrAlert
incorporates a stylish, low profile design. And this aesthetic is consistent across
all SpectrAlert wall-mount products.
Engineering Specifications
General
Horn/Strobe Combination
SpectrAlert horns, strobes and horn/strobes shall be capable of mounting to a standard 4″ x 4″x 11/ 2″ back box or a
single gang 2″ x 4″ x 17/ 8″ back box using the universal
mounting plate included with each SpectrAlert product.
Also, SpectrAlert products, when used in conjuction
with the accessory Sync•Circuit Module, shall be powered from a non-coded power supply and shall operate
on 12 or 24 volts. 12 volt rated devices shall have an
operating voltage range of 10.7–17 volts. 24-volt rated
devices shall have an operating voltage range or 20–30
volts. SpectrAlert products shall have an operating temperature of 32° to 120°F and operate from a regulated
DC or full wave rectified, unfiltered power supply.
Horn/Strobe shall be a System Sensor SpectrAlert Model
listed to UL 1971 and UL 464 and shall be
approved for fire protective service. Horn/strobe shall
be wired as a primary signaling notification appliance
and comply with the Americans with Disabilities Act
requirements for visible signaling appliances, flashing at
1Hz over the strobe’s entire operating voltage range.
The strobe light shall consist of a xenon flash tube and
associated lens/reflector system. The horn shall have two
tone options, two audibility options (at 24 volts) and the
option to switch between a temporal 3 pattern and a
non-temporal continuous pattern. Strobes shall be powered
independently of the sounder with the removal of factory
installed jumper wires. The horn on horn/strobe models
shall operate on a coded or non-coded power supply
(the strobe must be powered continuously).
Horn
Horn shall be a System Sensor SpectrAlert Model
capable of operating at 12 and 24 volts. Horn shall be
listed to UL 464 for fire protective signaling systems. The
horn shall have two tone options, two audibility options
(at 24 volts) and the option to switch between a temporal
3 pattern and a non-temporal continuous pattern. All horn
models shall operate on a coded power supply.
Strobe
Strobe shall be a System Sensor SpectrAlert Model
listed to UL 1971 and be approved for fire protective
service. The strobe shall be wired as a primary signaling
notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances, flashing at 1Hz over the strobe’s entire operating
voltage range. The strobe light shall consist of a xenon
flash tube and associated lens/reflector system.
Synchronization Module
Module shall be a System Sensor Sync•Circuit
listed to UL 464 and shall be approved for fire protective
service. The module shall synchronize SpectrAlert strobes
at 1Hz and horns at temporal 3. Also, the module shall
silence the horns on horn/strobe models, while operating
the strobes, over a single pair of wires. The module shall
be capable of mounting to a 411/16″ x 411/16″x 21/8″ back
box and shall control two Style Y (class B) or one Style Z
(class A) circuit. Module shall be capable of multiple zone
synchronization by daisy chaining multiple modules
together and re-synchronizing each other along the chain.
The module shall not operate on a coded power supply.
Specifications
Walk Test SpectrAlert horn/strobe and horn only
work on “walk tests” with time durations of
4 seconds or greater
Input Terminals
12 to 18 AWG
Dimensions
Strobe and horn/strobe with universal plate
5″ x 5 5/8″ x 2 15/16″
Strobe and horn/strobe with small
footprint plate
3 3/8″ x 5 5/8″ x 2 5/16″
Horn with universal mounting plate
5″ x 5 5/8″ x 1 5/16″
Horn without mounting plate
2 15/16″ x 5 5/16″ x 1 5/16″
Weight, horn only
7.2 oz.
Weight, strobe and horn/strobe
8.8 oz.
Mounting
4″ x 4″ x 1 1/2″ or 2″ x 4″ x 1 7/8″
standard boxes
Indoor Operating Temperature
32°F to 120°F (0°C to 49°C)
Maximum humidity
95% as tested per UL464
Weatherproof (horn and horn/strobes)
Operating Temperature
32°F to 150°F (0°C to 66°C)
(outdoor strobe only)
–40°F to 158°F (–40°C to 70°C)
ULC Canadian Models
–40°C to 66°C
Voltages
12 or 24VDC and FWR unfiltered
Operating voltage range*
12V: 10.5-17V; 24V: 20-30V
Operating voltage range*
(with Sync•Circuit module, MDL)
12V, 11-17V; 24V, 20-30V
* These products should be operated within their rated
voltage range; UL does, however, test functional
integrity to -20% and +10% of manufacturer's stated
ranges.
U.S. Patent Numbers
5,593,569
5,914,665
6,049,446
SpectrAlert Current Draw Table
Strobe Only
Average Current (mA)
12V Models
10.5V
12V
17V
20V
In Rush Current (mA)
Peak Current (mA)
24V Models
24V
12V Models
30V
10.5V
12V
12V Models
24V Models
17V
20V
24V
30V
10.5V
12V
24V Models
17V
20V
24V
30V
Candela
DC FWR DC FWR DC FWR DC FWR DC FWR DC FWR
DC FWR DC FWR DC FWR DC FWR DC FWR DC FWR
DC FWR DC FWR DC FWR DC FWR DC FWR DC FWR
15
133 159 114 157 81 128 50
61
43
60
38
60
460 460 450 460 420 480 135 204 135 208 135 185
80 108 92
124 140 190 97 129 116 152 147 198
15/75
168 182 142 171 99 150 56
65
49
64
44
62
490 520 490 520 460 480 150 199 150 207 150 198
76 104 88
126 160 185 97 135 116 164 147 211
30
NA
NA
NA
NA
NA
NA
84
67
82
58
72
NA
NA
NA
NA NA
NA 183 201 183 219 183 216
NA
NA
NA
NA NA
NA
75
NA
NA
NA
NA
NA
NA 145 170 123 159 102 141
NA
NA
NA
NA NA
NA 350 440 340 460 330 480
NA
NA
NA
NA NA
NA 190 240 230 280 290 380
110
NA
NA
NA
NA
NA
NA 169 220 140 191 115 174
NA
NA
NA
NA NA
NA 460 560 450 570 420 620
NA
NA
NA
NA NA
NA 190 230 220 290 290 370
78
97 129 116 152 147 198
Horn/Strobe 30 cd
Horn Only
Average Current (mA)
High/Low Temp/
Tone
Volume
Non
ElectroHigh
Temp
mech.
Non
Low
Temp
Non
3000 Hz High
Temp
Interrupt.
Non
Low
Temp
Non
12V Models
10.5V
12V
DC FWR DC FWR
10 11 10 10
10 16 10 19
NA NA NA NA
NA NA NA NA
11 13 11 11
11 17 11 21
NA NA NA NA
NA NA NA NA
Average Current (mA)
24V Models
17V
20V
24V
DC FWR DC FWR DC FWR
14 14 19 21 25 18
14 25 17 29 23 34
NA NA 11 12 13 13
NA NA 12 16 14 19
16 16 24 26 28 23
14 28 19 34 27 39
NA NA 14 14 17 15
NA NA 13 18 16 21
30V
DC FWR
29 26
30 42
17 15
17 24
37 33
35 45
21 19
22 25
Horn/Strobe 15 cd
High/Low Temp/
Tone
Volume
Non
ElectroHigh
Temp
mech.
Non
Low
Temp
Non
3000 Hz High
Temp
Interrupt.
Non
Low
Temp
Non
12V Models
10.5V
12V
DC FWR DC FWR
143 170 124 167
143 170 124 167
NA NA NA NA
NA NA NA NA
144 172 125 168
144 173 125 168
NA NA NA NA
NA NA NA NA
30V
DC FWR
87 98
88 114
75 87
75 96
95 105
93 117
79 91
80 97
Average Current (mA)
24V Models
17V
20V
24V
DC FWR DC FWR DC FWR
95 142 69 82 68 78
95 142 67 90 66 94
NA NA 61 73 56 73
NA NA 62 77 57 79
97 144 74 87 71 83
95 146 69 95 70 99
NA NA 64 75 60 75
NA NA 63 79 59 81
30V
DC FWR
67 87
68 103
55 76
55 85
75 94
73 106
59 80
60 86
Horn/Strobe 1575 cd
High/Low Temp/
Tone
Volume
Non
ElectroHigh
Temp
mech.
Non
Low
Temp
Non
3000 Hz High
Temp
Interrupt.
Non
Low
Temp
Non
20V
DC FWR
164 191
163 188
156 182
157 182
169 196
164 192
159 184
158 188
24V Models
24V
30V
DC FWR DC FWR
148 167 131 167
146 169 132 169
136 162 119 156
137 162 119 157
151 172 139 174
150 175 137 177
140 164 123 160
139 163 124 162
Horn/Strobe 110 cd
Average Current (mA)
High/Low Temp/
Tone
Volume
Non
ElectroHigh
Temp
mech.
Non
Low
Temp
Non
3000 Hz High
Temp
Interrupt.
Non
Low
Temp
Non
24V Models
24V
DC FWR
92 100
90 116
80 95
81 101
95 105
94 121
84 97
83 103
Horn/Strobe 75 cd
Average Current (mA)
High/Low Temp/
Tone
Volume
Non
ElectroHigh
Temp
mech.
Non
Low
Temp
Non
3000 Hz High
Temp
Interrupt.
Non
Low
Temp
Non
20V
DC FWR
97 105
95 113
89 96
90 98
102 108
97 116
92 96
91 100
12V Models
10.5V
12V
17V
DC FWR DC FWR DC FWR
178 193 152 181 113 164
178 193 152 181 113 164
NA NA NA NA NA NA
NA NA NA NA NA NA
179 195 152 183 115 166
179 196 152 183 113 168
NA NA NA NA NA NA
NA NA NA NA NA NA
Average Current (mA)
24V Models
20V
24V
DC FWR DC FWR
75 86 74 82
73 94 72 98
67 77 62 77
68 81 63 83
80 91 77 87
75 99 76 103
70 79 66 7969 83 65 85
30V
DC FWR
73 88
74 104
61 77
61 86
81 95
79 107
65 81
66 87
High/Low Temp/
Tone
Volume
Non
ElectroHigh
Temp
mech.
Non
Low
Temp
Non
3000 Hz High
Temp
Interrupt.
Non
Low
Temp
Non
20V
DC FWR
188 241
186 238
180 232
181 232
193 246
188 242
183 234
182 232
24V Models
24V
30V
DC FWR DC FWR
165 209 144 200
163 211 145 202
153 204 132 189
154 204 132 190
168 214 152 207
167 217 150 210
157 206 136 193
156 205 137 195
Sound Output Guide (dBA)
UL Reverberant Room dBA @ volts DC
Temporal
Low Tone
High Tone
Non-Temporal
Low Tone
High Tone
Anechoic Room Peak dBA @ 10ft./volts DC
Electromechanical
3000 HZ Interrupted
Electromechanical
3000 HZ Interrupted
10.5
NA
NA
75
75
12
NA
NA
75
75
17
NA
NA
79
79
20
75
75
82
82
24
75
79
82
85
30
79
79
82
85
10.5
NA
NA
94
94
12
NA
NA
95
95
17
NA
NA
98
98
20
94
94
100
100
24
96
96
101
101
30
98
98
102
102
Electromechanical
3000 HZ Interrupted
Electromechanical
3000 HZ Interrupted
NA
NA
79
79
NA
NA
79
82
NA
NA
85
85
79
82
85
88
82
82
88
88
85
85
88
88
NA
NA
94
93
NA
NA
95
95
NA
NA
98
98
94
94
100
100
96
96
101
101
98
98
102
102
SpectrAlert Ordering Information
Horn/Strobes
Canada
Latin America
Strobes
Canada
Latin America
Horns
Canada
Sync•Circuit
Module
Canada
Small Footprint Mounting
Plate for Single Gang Only
Sur face Mount Back Box Skir t
Universal Mounting
Plate (replacement)
Weatherproof Back Box
Red
P1215
P121575
P2415
P241575
P2430
P2475
P24110
P121575K (weatherproof)
P241575K (weatherproof)
P2475K (weatherproof)
P24110K (weatherproof)
P241575P (no lettering)
P241575AG (AGENT)
P241575EV (EVAC)
P2415A
P241575A
P2475A
P24110A
P241575KA (weatherproof)
P2475KA (weatherproof)
P24110KA (weatherproof)
P241575F (FUEGO)
S1215
S121575
S2415
S241575
S2430
S2475
S24110
S121575K (weatherproof)
S241575K (weatherproof)
S2475K (weatherproof)
S24110K (weatherproof)
S241575P (no lettering)
S241575AG (AGENT)
S241575EV (EVAC)
S2415A
S241575A
S2475A
S24110A
S241575KA (weatherproof)
S2475KA (weatherproof)
S24110KA (weatherproof)
S241575F (FUEGO)
H12/24
H12/24K (weatherproof)
HC12/24A
HC12/24KA
MDL
MDLA
White
P1215W
P121575W
P2415W
P241575W
P2430W
P2475W
P24110W
—
—
—
—
P241575PW
—
—
P2415WA
P241575WA
P2475WA
P24110WA
—
—
—
—
S1215W
S121575W
S2415W
S241575W
S2430W
S2475W
S24110W
—
—
—
—
S241575PW
—
—
S2415WA
S241575WA
S2475WA
S24110WA
—
—
—
—
H12/24W
—
HC12/24WA
—
MDLW
MDLWA
Voltage
12
12
24
24
24
24
24
12
24
24
24
24
24
24
24
24
24
24
24
24
24
24
12
12
24
24
24
24
24
12
24
24
24
24
24
24
24
24
24
24
24
24
24
24
12/24
12/24
12/24
12/24
12/24
12/24
Candela
15
15/75
15
15/75
30
75
110
15/75
15/75
75
110
15/75
15/75
15/75
15
15/75
75
110
15/75
75
110
15/75
15
15/75
15
15/75
30
75
110
15/75
15/75
75
110
15/75
15/75
15/75
15
15/75
75
110
15/75
75
110
15/75
NA
NA
NA
NA
NA
NA
Avg. mA*
@Nom. VDC
124
152
68
74
92
148
165
124
74
148
165
74
74
74
68
74
148
165
74
148
165
74
114
142
43
49
67
123
140
142
49
123
140
49
49
49
43
49
123
140
49
123
140
49
10/25
10/25
10/25
10/25
10/11
10/11
Avg. mA*
@Nom.FWR**
167
181
78
82
100
167
209
167
82
167
209
82
82
82
78
82
167
209
82
167
209
82
157
171
60
64
82
159
191
171
64
159
191
64
64
64
60
64
149
191
64
149
191
64
10/18
10/18
10/18
10/18
12/15
12/15
S-MP
BBS
S-MPW
BBSW
NA
NA
NA
NA
NA
NA
NA
NA
D-MP
WBB
D-MPW
—
NA
NA
NA
NA
NA
NA
NA
NA
Notes: Agency Listings – Indoor models: UL, ULC, FM, CSFM, MEA. Weatherproof models: UL, CSFM (strobe only), MEA, ULC.
All of these SpectrAlert products are designed for wall mount only. All weatherproof models must use weatherproof back box model WBB. Installation of less than 75 candela strobes may be permissible under the equivalent facilitation clause of the ADAAG (Sec. 2.2). However, it is the responsibility of the person or entity designing the fire
alarm system to determine the acceptability of less than 75 candela strobes. All 15/75 candela strobes or horn/strobes are recommended for 20′ × 20′ rooms or less.
*Horn and horn/strobe current draws assume horn is set at temp 3, electromechanical tone and high audibility.
** FWR = Full Wave Rectified
System Sensor Sales and Service
System Sensor Headquarters
3825 Ohio Avenue
St. Charles, IL 60174
Ph: 800/SENSOR2
Fx: 630/377-6495
Documents-on-Demand
800/736-7672 x3
www.systemsensor.com
System Sensor Canada
Ph: 905.812.0767
Fx: 905.812.0771
System Sensor in China
Ph: 86.29.524.6253
Fx: 86.29.524.6259
System Sensor – Far East
Ph: 85.22.191.9003
Fx: 85.22.736.6580
System Sensor Europe
Ph: 44.1403.276500
Fx: 44.1403.276501
System Sensor in Singapore
Ph: 65.6273.2230
Fx: 65.6273.2610
System Sensor – Australia
Ph: 613.54.281.142
Fx: 613.54.281.172
© 2002 System Sensor. The company reserves the right to change product specifications without notice.
System Sensor – India
Ph: 91.124.637.1770 x.2700
Fx: 91.124.637.3118
A05-0936-010•9/02•#1002