GFPS-9 Description Gamewell-FCI Power Supply 9 The Gamewell-FCI Power Supply 9 (GFPS-9) panel provides two (2) Class A, Style Z, or four (4) Class B, Style Y notification appliance circuits. Each circuit is rated at 3 amperes, with a total capacity of 9 amperes per panel. These circuits may be programmed to activate by groups or various combinations by connection to one (1) or two (2) existing Class A or B notification appliance circuits with operating voltages ranging from 9 to 30 VDC. Either noncoded or coded operation is possible. In addition, the GFPS-9 can provide a temporal pattern output from a noncoded input. A unique feature allows for programmable synchronized outputs for strobes by three (3) different major manufacturers, System Sensor, Faraday, or Gentex. The GFPS-9 contains its own battery charger capable of maintaining batteries of up to 35 AH. The cabinet provides space for a set of 7 A/H batteries. Larger batteries would require a separate battery box. It is supervised for ground fault, over-current, open circuits and low battery conditions. These conditions light the appropriate trouble LED and automatically open the notification appliance circuit used for activation, transmitting a trouble signal to the main fire alarm control panel. The ground fault detection circuit may be disabled. The unit contains a set of dry, Form “C” trouble actuated auxiliary contacts, rated 2.5 amp. @ 24 VDC (resistive). Transfer of these contacts for AC power failure is programmable and can be delayed for a period of six (6) hours. This delay feature may be disabled. GFPS-9 Features • • • • • • • A power limited, non-resettable auxiliary power output up to three (3) amperes is also available. The panel can be programmed via DIP switch to disconnect this output from the batteries 30 seconds after AC power failure, in order to avoid running down the batteries from current devices such as door holders, etc. UL® Listed as a fire alarm accessory for use with any Gamewell-FCI or other UL Listed fire alarm controls Two (2) Class A (Style Z), or four (4) Class B (Style Y) notification appliance circuits Programmable temporal pattern output including ANSI S3.41 High current 9 amp. total output Integral strobe synchronization feature for strobes by three (3) manufacturers Integral ground fault detection Form “C” trouble contacts with delayed AC failure indication An ISO 9000-2000 Company SIGNALING UL® is a registered trademark of Underwriters Laboratories Inc. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9020-60236 Rev. A2 page 1 of 2 ©2012 by Honeywell International Inc. All rights reserved. Specifications Operating Power: Standby Battery Circuit: Supervisory Current: Alarm Current: Alarm Output: Dimensions: Operating Temperature: Relative Humidity: Ordering Information 120 VAC, 3.6 amp. 60 Hz Model 24 VDC (nominal) 7 ampere/ hours, max. 0.075 amp. 0.175 amp. (excluding notification appliances) 9.0 amp. max. @ 24 VDC (nominal) 16" H x 12.25" W x 3" D (40.64 x 30.88 x 7.62 cm) GFPS-9 Gamewell-FCI Power Supply-9 GFPS-9RB 9A Power Supply Replacement PCB Description 32° to 120° F (0° to 49° C) 10 to 85% @ 86° F (non-condensing) GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9020-60236 Rev. A2 page 2 of 2 www.gamewell-fci.com