BRAIN VIMT51CW24

Timers
Multifunction
Timer Type VIMT51CW24
FEATURES
• Selectable time range 0.1 s to 100 h
• 7 knob selectable functions:
Op delay on operate
In
interval
Io
interval on trigger open
Id
double interval
Dr
delay on release
R
symmetrical recycler ON first
Rb symmetrical recycler OFF first
• Automatic or manual start
• Repeatability: ≤ 0.2%
• Output: 5 A SPDT relay
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• 17.5 mm DIN-rail housing
• Combined AC and DC power supply
• LED indication for relay status and power supply ON
Description & Mode of operation:
Multi-voltage timer with 7 knob-selectable functions and 7
knob-selectable time ranges within 0.1s and 100h. For
mounting on DIN-rail. Housing 17.5 mm wide suitable both
for back and front panel mounting.
Wide power supply range: 12 to 240 VAC/DC.
Function Op - Delay on operate
The time period begins as soon as the trigger contact is
closed.
At the end of the set delay time the relay operates and does
not release until the trigger contact is closed again or the
power supply is disconnected. If the trigger contact is
closed before the end of the delay time, the device resets
and a new time period starts.
Function In - Interval
The relay operates and the time period begins as soon as the
trigger contact is closed. The relay releases at the end of this
period or when the power supply is disconnected. The relay
operates again when the trigger contact is closed again. If the
trigger contact is closed before the end of the delay time, the
device resets and a new time period starts.
Function Io - Interval on trigger open
The relay operates and the time period begins as soon as
the trigger contact is opened. At the end of the set delay or
when the power supply is disconnected the relay releases.
The relay operates again when the trigger contact is opened
again. If the trigger contact is opened before the end of the
delay time the relay keeps ON and a new time period
begins.
Function Id - Double interval
The relay operates and the time period begins as soon as
the trigger contact is closed. The relay releases at the end of
this period or when the power supply is disconnected.
When the trigger contact is opened the relay operates again
for the set delay period. If the trigger contact is opened
before the end of the first time period the second one
begins; if the trigger contact is closed before the end of the
second time period the device resets and the first time period begins again.
Function Dr - Delay on release
The relay operates as soon as the trigger contact is closed.
The time period begins when the trigger contact is opened.
The relay releases at the end of the set delay time or when
the power supply is disconnected. The relay operates again
when the input contact is closed again. If it is opened
before the end of the delay time the relay keeps ON, a new
time period begins as soon as the contact is closed again.
Function R - Symmetrical recycler, ON-time period first
The relay operates and the time period begins as soon as
the input contact is closed. After the set delay period the
relay releases for the same time period. This sequence continues with equal ON- and OFF-time periods until the power
supply is interrupted.
Function Rb - Symmetrical recycler, OFF-time period first
The time period begins as soon as the input contact is
closed. The relay is OFF during the set delay period, after
this time it operates for the same time period. This
sequence continues with equal OFF- and ON-time periods
until the power supply is interrupted.
Additional Load
It's possible to wire an additional load (i.e. a relay) between
pins Y1 and A2, driven by the trigger contact without damaging the device.
Yellow LED working mode
Timing: Slow blinking
Relay ON: See operation diagrams
Incorrect knobs position: Fast blinking
www.dold-relay.com
1
VIMT51
Specifications
Output:
Timing:
Time ranges
Knob selectable
Setting accuracy
Repeatability
Time variation
Within rated power supply
Within ambient temperature
Reset
Manual reset of time and/or
relay
Pulse duration
Power supply interruption
Automatic start
Output
Rated insulation voltage
Contact Ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
0.1 to 1 s
1 to 10 s
6 to 60 s
60 to 600 s
0.1 to 1 h
1 to 10 h
10 to 100 h
≤ 5%
≤ 0.2%
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand
voltage
≤ 0.05%/V
≤ 0.2%/°C
Close the trigger contact
between pins A1 and Y1
≥ 100 ms
≥ 200 ms
Connect pins A1 and Y1
General:
Power ON delay
Indication for
Power supply ON
Output relays ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Housing
Dimensions
Material
Weight
Screw terminals
Tightening torque
CE Marking
EMC
Immunity
Emissions
2
1xSPDT or relay
250 VAC (rms)
µ
5 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 5 A, 250 V, cos ϕ = 1)
< 7200 operations/h
2 kVAC (rms)
2.5 kV (1.2/50 µs)
Supply:
≤ 100 ms
Power supply
Rated operational voltage
through terminals A1, A2:
LED, green
LED, yellow
(flashing when timing)
(EN 60529)
IP 20
2 (IEC 60664)
-20° to +60°C, R.H. < 95%
-30° to +80°C, R.H. < 95%
Voltage interruption
Rated operational power
AC supply:
DC supply:
17.5 x 81 x 67.2 mm
PA66
Note: on the Y1 terminal is
mounted a flexible unipolar
red cable (N07V-K, 1 mm2,
40 mm in lenght, unsheated
sides)
75 g
Max. 0.5 Nm according to
IEC EN 60947
Yes
Electromagnetic Compatibillity
According to EN 61000-6-2
According to EN 61000-6-3
Overvoltage cat. II
(IEC 60664, IEC 60038)
12 to 240 VDC + 10% -15%
and 12 to 240 VAC
+ 10% -15%, 45 to 65 Hz
≤ 10 ms
4 VA
1.5 W
Time Setting:
Upper knob:
Setting of function:
Op - delay on operate
In - interval
Io - interval on trigger open
Id - double interval
Dr - delay on release
R - symmetrical recycler
(ON first)
Rb - symmetrical recycler
(OFF first)
www.dold-relay.com
Centre knob:
Time setting on relative scale:
1 to 10 with respect to the
chosen range.
Lower knob:
Setting of time range
VIMT51
Operating Diagrams:
Function Op - Delay on operate - Manual start
Function In - Interval - Manual start
Power supply
Power supply
Trigger input
Trigger input
T
ON
T
T
ON
Relay ON
T
Relay ON
OFF
OFF
LED
LED
Function Op - Delay on operate - Automatic start
Function In - Interval - Automatic start
Power supply
ON
Power supply
T
T
ON
Relay ON
T
T
Relay ON
OFF
OFF
LED
LED
Function Id - Double interval
Function Io - Interval on trigger open
Power supply
Power supply
Trigger input
Trigger input
ON
T
T
ON
T
T
Relay ON
Relay ON
OFF
OFF
LED
LED
Function Dr - Delay on release
Function R - Symmetrical recycler (ON first)
Power supply
Power supply
Trigger input
Trigger input
T
ON
ON
Relay ON
T
T
T
T
Relay ON
OFF
OFF
LED
LED
Function Rb - Symmetrical recycler (OFF first)
Power supply
Trigger input
ON
T
T
T
T
Relay ON
OFF
LED
www.dold-relay.com
3
VIMT51
Wiring Diagram:
Dimensions:
17.5
67.2
2
4
www.dold-relay.com
45
81
18.7