BRAIN DMB51CW24

Multifunction Timers
Types DMB51
Product Description
Multi-voltage timer with 7 knob-selectable functions and 7
knob-selectable time ranges within 0.1s and 100h.
Housing 17.5 mm wide suitable for back and front panel
mounting. Wide power supply range: 12 to 240 VAC/DC.
Property
• Selectable time range 0.1 s to 100 h
• 7 knob selectable functions:
Op delay on operate
In
interval
Io
interval on trigger open
Id
double interval
Dr
delay on release
R
symmetrical recycler ON first
Rb symmetrical recycler OFF first
• Automatic or manual start
• Repeatability: ≤ 0.2%
• Output: 5 A SPDT
• For mounting on DIN-rail in accordance with DIN/EN 50 022
• 17.5 mm DIN-rail housing (DIN 43880)
• Combined AC and DC power supply
• LED indication for relay status and power supply ON
Output Specifications
Type Selection
Mounting
Output
Housing
DIN-rail
SPDT
Mini-D
Supply:
12 to 240 VAC/DC
Supply Specifications
Power supply
Rated operational voltage
through terminals:
Voltage interruption
Rated operational power
≤ 10 ms
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Housing
Dimensions
Material
Weight
Screw terminals
Tightening torque
Approvals
CE Marking
EMC
Immunity
Emissions
AC 1
DC 12
Small inductive loads AC 15
DC 13
5 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 5 A, 250 V, cos ϕ = 1)
< 7200 operations/h
Mechanical life
Electrical life
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand
voltage
4 VA
1.5 W
General Specifications
Power ON delay
Indication for
Power supply ON
Output relays ON
SPDT
250 VAC (rms)
μ
Resistive loads
Overvoltage cat. II
(IEC 60664, IEC 60038)
12 to 240 VDC + 10% -15%
and 12 to 240 VAC
+ 10% -15%, 45 to 65 Hz
AC supply:
DC supply:
Output
Rated insulation voltage
Contact Ratings (AgSnO2)
2 kVAC (rms)
2.5 kV (1.2/50 μs)
≤ 100 ms
Time Specifications
LED, green
LED, yellow
(flashing when timing)
(EN 60529)
IP 20
2 (IEC 60664)
-20° to +60°C, R.H. < 95%
-30° to +80°C, R.H. < 95%
Time ranges
Knob selectable
17.5 x 81 x 67.2 mm
PA66
75 g
Max. 0.5 Nm according to
IEC EN 60947
UL, CSA
RINA
Yes
Electromagnetic Compatibillity
According to EN 61000-6-2
According to EN 61000-6-3
Setting accuracy
Repeatability
Time variation
Within rated power supply
Within ambient temperature
Reset
Manual reset of time and/or
relay
Pulse duration
Power supply interruption
Automatic start
www.dold-relay.com
0.1
6
0.1
10
to
to
to
to
1 s ,1 to 10 s
60 s ,60 to 600 s
1 h ,1 to 10 h
100 h
≤ 5%
≤ 0.2%
≤ 0.05%/V
≤ 0.2%/°C
Close the trigger contact
between pins A1 and Y1
≥ 100 ms
≥ 200 ms
Connect pins A1 and Y1
1
DMB51CW24
Time Setting
Upper knob:
Setting of function:
Op - delay on operate
In - interval
Io - interval on trigger open
Id - double interval
Dr - delay on release
R - symmetrical recycler
(ON first)
Rb - symmetrical recycler
(OFF first)
Centre knob:
Time setting on relative scale:
1 to 10 with respect to the
chosen range.
Lower knob:
Setting of time range
Mode of Operation
Function Op
Delay on operate
The time period begins as
soon as the trigger contact
is closed.
At the end of the set delay
time the relay operates and
does not release until the
trigger contact is closed
again or the power supply is
disconnected. If the trigger
contact is closed before the
end of the delay time, the
device resets and a new
time period starts.
Function Io
Interval on trigger open
The relay operates and the
time period begins as soon
as the trigger contact is
opened. At the end of the
set delay or when the power
supply is disconnected the
relay releases. The relay
operates again when the
trigger contact is opened
again. If the trigger contact
is opened before the end of
the delay time the relay
keeps ON and a new time
period begins.
Function In
Interval
The relay operates and the
time period begins as soon
as the trigger contact is
closed. The relay releases at
the end of this period or
when the power supply is
disconnected. The relay
operates again when the trigger contact is closed again. If
the trigger contact is closed
before the end of the delay
time, the device resets and a
new time period starts.
Function Id
Double interval
The relay operates and the
time period begins as soon
as the trigger contact is
closed. The relay releases at
the end of this period or
when the power supply is
disconnected.
When the
trigger contact is opened
the relay operates again for
the set delay period. If the
trigger contact is opened
before the end of the first
time period the second one
begins; if the trigger contact
is closed before the end of
the second time period the
device resets and the first
time period begins again.
Function Dr
Delay on release
The relay operates as soon
as the trigger contact is
closed. The time period
begins when the trigger contact is opened. The relay
releases at the end of the
set delay time or when the
power supply is disconnected. The relay operates again
when the input contact is
closed again. If it is opened
before the end of the delay
time the relay keeps ON, a
new time period begins as
soon as the contact is
closed again.
Function R
Symmetrical recycler, ONtime period first
The relay operates and the
time period begins as soon
as the input contact is
closed. After the set delay
period the relay releases for
the same time period. This
sequence continues with
equal ON- and OFF-time
periods until the power supply is interrupted.
Function Rb
Symmetrical recycler,
OFF-time period first
The time period begins as
soon as the input contact is
closed. The relay is OFF
during the set delay period,
after this time it operates for
the same time period. This
sequence continues with
equal OFF- and ON-time
periods until the power supply is interrupted.
Additional Load
It's possible to wire an additional load (i.e. a relay)
between pins Y1 and A2,
driven by the trigger contact
without
damaging
the
device.
Yellow
LED
working
mode
Timing: Slow blinking
Relay ON: See operation
diagrams
Incorrect knobs position:
Fast blinking
Operating Diagrams
Function Op - Delay on operate - Manual start
Function In - Interval - Manual start
Power supply
Power supply
Trigger input
Trigger input
ON
Relay ON
T
T
ON
T
OFF
OFF
LED
T
Relay ON
LED
www.dold-relay.com
2
DMB51CW24
Operating Diagrams (cont.)
Function Op - Delay on operate - Automatic start
Function In - Interval - Automatic start
Power supply
ON
Power supply
T
T
T
ON
Relay ON
T
Relay ON
OFF
OFF
LED
LED
Function Id - Double interval
Function Io - Interval on trigger open
Power supply
Power supply
Trigger input
Trigger input
T
ON
T
T
ON
T
Relay ON
Relay ON
OFF
OFF
LED
LED
Function Dr - Delay on release
Function R - Symmetrical recycler (ON first)
Power supply
Power supply
Trigger input
Trigger input
T
ON
T
ON
Relay ON
T
T
T
Relay ON
OFF
OFF
LED
LED
Function Rb - Symmetrical recycler (OFF first)
Power supply
Trigger input
ON
T
T
T
T
Relay ON
OFF
LED
Dimensions
67.2
17.5
18.7
45
3 5.5
81
A1 15 Y1
16 18 A2
2
Wiring Diagram
www.dold-relay.com
3