LEM LA25

Current Transducer LA 25-NP
IPN = 5-6-8-12-25 A
For the electronic measurement of currents : DC, AC, pulsed,
mixed, with a galvanic isolation between the primary circuit
(high power) and the secondary circuit (electronic circuit).
16080
Electrical data
IPN
IP
RM
Primary nominal r.m.s. current
Primary current, measuring range
Measuring resistance @
with ± 15 V
ISN
KN
VC
IC
Vd
Vb
@ ± 25 At max
@ ± 36 At max
25
At
0 .. ± 36
At
TA = 70°C
TA = 85°C
RM min RM max RM min RM max
100 320
100 190
Secondary nominal r.m.s. current
Conversion ratio
Supply voltage (± 5 %)
Current consumption
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
R.m.s. rated voltage 1), safe separation
basic isolation
100 315
100 185
Ω
Ω
25
mA
1-2-3-4-5 : 1000
± 15
V
10 + IS
mA
2.5
kV
600
V
1700
V
Accuracy - Dynamic performance data
X
ε
Typical accuracy @ IPN , TA = 25°C
Linearity error
L
Offset current 2) @ IP = 0, TA = 25°C
Residual current 3) @ IP = 0, after an overload of 3 x IPN
Thermal drift of IO
0°C .. + 25°C
+ 25°C .. + 70°C
- 25°C .. + 85°C
- 40°C .. + 85°C
IO
IOM
IOT
tr
di/dt
f
Response time 4) @ 90 % of IPN
di/dt accurately followed
Frequency bandwidth (- 1 dB)
± 0.5
< 0.2
Typ
± 0.05
± 0.05
± 0.06
± 0.10
%
%
Max
± 0.15
± 0.15
± 0.25
± 0.35
± 0.5
± 1.2
<1
> 50
DC .. 150
mA
mA
mA
mA
mA
mA
µs
A/µs
kHz
R IS
m
Notes :
Ambient operating temperature
Ambient storage temperature
Primary resistance per turn
@ TA = 25°C
Secondary coil resistance
@ TA = 70°C
@ TA = 85°C
Isolation resistance @ 500 V, TA = 25°C
Mass
Standards
1)
2)
3)
4)
• Closed loop (compensated) multirange current transducer using the
Hall effect
• Insulated plastic case recognized
according to UL 94-V0.
Advantages
•
•
•
•
•
•
•
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
• Current overload capability.
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
General data
TA
TS
RP
RS
Features
- 40 .. + 85
°C
- 45 .. + 90
°C
< 1.25
mΩ
110
Ω
115
Ω
> 1500
MΩ
22
g
EN 50178 : 1997
• Power supplies for welding
applications.
Pollution class 2
Measurement carried out after 15 mn functioning
The result of the coercive field of the magnetic circuit
With a di/dt of 100 A/µs.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
060327/13
Page 1/2
w w w .lem.com
Dimensions LA 25-NP
(in mm. 1 mm = 0.0394 inch)
Model + SP N°
Date code
Bottom view
Top view
Right view
Connection
IN
OUT
Back view
Number
Primary current
N o m i n a l
Turns
Primary
Primary insertion
Recommended
of primary
nominal
maximum
output current
r a t i o
resistance
i n d u c t a n c e
connections
t u r n s
IPN [ A ]
IP
ISN
KN
RP
LP
[A]
[ mA ]
[ mΩ ]
[ µH ]
5 4 3 2 1
1
25
36
25
1/1000
0.3
0.023
OUT
6 7 8 9 10
5 4 3 2 1
2
12
18
24
2/1000
1.1
6 7 8 9 10
5 4 3 2 1
8
12
24
3/1000
2.5
6 7 8 9 10
5 4 3 2 1
6
9
24
4/1000
4.4
6 7 8 9 10
5 4 3 2 1
5
7
25
5/1000
6.3
•
•
•
•
General tolerance
Fastening & connection of primary
Fastening & connection of secondary
Recommended PCB hole
IN
0.58
OUT
Mechanical characteristics
IN
0.37
OUT
5
IN
0.21
OUT
4
IN
0.09
OUT
3
IN
6 7 8 9 10
Remarks
± 0.2 mm
10 pins 0.7 x 0.6 mm
3 pins ∅ 1 mm
1.2 mm
• IS is positive when IP flows from terminals 1, 2, 3, 4, 5 to
terminals 10, 9, 8, 7, 6
• This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
060327/13
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
Page 2/2
w w w .lem.com