MEANWELL ISI

Modified Sine Wave DC-AC Inverter with MPPT Solar Charger
ISI-500
series
Features :
High surge power up to 1000W
Power ON-OFF switch
Protections: Bat. low alarm / Bat. low shutdown / Over temp.
/ Output short / Input polarity reverse / Over load
High frequecny design
AC Output voltage regulation : 10%
AC Output wavform : Modified sine wave
Modified models available(optional): 100/115/120VAC or 200/220/240VAC
Cooling fan ON-OFF control
Built-in 500W MPPT solar charger, MPPT efficiency: 98%(Typ.)
Built-in battery low relay contact
LED indicator for operation status
2 years warranty
SPECIFICATION
MODEL
RATED POWER
ISI-500-112
ISI-500-124
ISI-500-148
ISI-500-212
ISI-500-224
ISI-500-248
350W
500W
500W
350W
500W
500W
MAXIMUM OUTPUT POWER (Typ.) 550W for 1 minute / surge power 1000W for 30 cycles (112, 212 models : 385W for 1 minute / surge power 700W for 30 cycles)
WAVEFORM
Modified sine wave
OUTPUT
AC VOLTAGE
110V
230V
FREQUENCY
60Hz 0.5Hz
50Hz 0.5Hz
10%
AC REGULATION
Green: Inverter OK Green (flashing): Inverter OK and charging Red: abnormal
24V
24V
48V
12V
12V
LED INDICATOR
BAT. VOLTAGE
42 ~ 60VDC
10.5 ~ 15VDC
21 ~ 30VDC
42 ~ 60VDC
25A
12.5A
35A
25A
12.5A
0.4A
0.2A
0.8A
0.4A
0.2A
87%
Open & sealed Lead Acid
87%
86%
88%
88%
BATTERY TYPE
VOLTAGE RANGE
20 ~ 40V
Note.3,4 10.5 ~ 15VDC
DC CURRENT (Typ.)
INPUT
35A
NO LOAD CURRENT DRAW
0.8A
OFF MODE CURRENT DRAW 1mA
EFFICIENCY (Typ.)
SOLAR
PANEL
INPUT
48V
21 ~ 30VDC
VOLTAGE RANGE
Note.1 85%
35 ~ 80V
70 ~ 160V
70 ~ 160V
15A
7.5A
20 ~ 40V
15A
35 ~ 80V
MAX. SHORT CIRCUIT CURRENT 15A
15A
7.5A
RATED CHARGE POWER (Typ.) 350W
14V
500W
28V
500W
56V
350W
14V
500W
28V
500W
25A
14V
20A
28V
10A
56V
25A
14V
20A
28V
25A
20A
10A
25A
20A
30A
22V
15A
44V
40A
11V
30A
22V
21V
42V
10.5V
21V
MAX. CHARGE VOLTAGE
SOLAR
CHARGER MAX. CHARGE CURRENT
CHARGER MAX. CHARGING VOLTAGE
OUTPUT
MAX. CHARGING CURRENT
FUSE
40A
BATTERY BAT. LOW ALARM
Note.4 11V
INPUT
PROTECTION BAT. LOW SHUTDOWN Note.4 10.5V
By internal fuse
REVERSE POLARITY
OVER TEMPERATURE
OUTPUT
PROTECTION OUTPUT SHORT
OVER LOAD
70
65
10
56V
10A
56V
10A
15A
44V
42V
10
Protection type : Shut down o/p voltage, re-power on to recover ; by internal RTH9 detect on power transistor
Protection type : Shut down o/p voltage, re-power on to recover
Protection type : Shut down o/p voltage, re-power on to recover ; >105% load @ 60 sec.
FUNCTION BAT. LOW RELAY CONTACT Open : Battery low ; Short : Battery ok
WORKING TEMP.
Note.2 -20 ~ +40 @ 100% load ; 60 @ 50% load
20% ~ 90% RH non-condensing
WORKING HUMIDITY
ENVIRONMENT
o
STORAGE TEMP., HUMIDITY -30 ~ +70 / -22 ~ +158 F, 10 ~ 95% RH
VIBRATION
LVD
WITHSTAND VOLTAGE
EMC
OTHERS
NOTE
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
EN60950-1
None
Bat. I/P - AC O/P:3.0KVAC
AC O/P - FG:1.5KVAC
ISOLATION RESISTANCE
EMC EMISSION
EMS IMMUNITY
Bat. I/P-AC O/P, Bat. I/P-FG, AC O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 class A
Compliance to FCC part 15 class A
None
Compliance to EN61000-4-2,3,8
MTBF
81.1K hrs min.
DIMENSION
PACKING
205*158*67mm (L*W*H)
1.92Kg; 6pcs/12.5Kg/1.55CUFT
MIL-HDBK-217F (25oC)
1.Efficiency is tested by 350W, linear load at 13V, 26V, 52V input voltage.
2.Output derating capacity referenced by curve 1.
3.Output derating capacity referenced by curve 2.
4.The tolerance of each voltage value by models is:112/212
0.5V;124/224
1V;148/248
2V.
5.All parameters not specified above are measured at rated load, 25 of ambient temperature.
File Name:ISI-500-SPEC 2011-09-22
ISI-500
Modified Sine Wave DC-AC Inverter with MPPT Solar Charger
ISI
500
112 A
A :TYPE
B :TYPE
C :TYPE
D :TYPE
E :TYPE
U :TYPE
12:12VDC
Bat. Voltage: 24:24VDC
48:48VDC
Modified sine wave inverter
+MPPT solar charger
Output:
O/P Wattage:500W
1:110VAC
2:230VAC
series
A OUTLET
B OUTLET
C OUTLET
D OUTLET
E OUTLET
U OUTLET
AC Output Receptacles (optional)
Receptacle type
TYPE-A
(Standard)
TYPE-B
(Standard)
TYPE-C
(Optional)
TYPE-D
(Optional)
TYPE-E
(Optional)
TYPE-U
(Optional)
USA
EUROPE
AUSTRALIA
U.K
JAPAN
UNIVERSAL
Country
Certificate
Non
Mechanical Specification
Unit:mm
5
4
3
Input Terminal Pin No. Assignment
2 1
_
67
Pin No.
1
2
3
Assignment
FG
Solar POS(+)
Solar NEG(-)
Pin No.
4
5
Assignment
Battery POS(+)
Battery NEG(-)
SOLAR INPUT
_
BATTERY INPUT
Derating Curve
Reverse Polarity
Will Damage The Unit.
100
11
7.62
Air flow
direction
6.35
80
42.5
LOAD (%)
13
18
8.9
9
60
50
40
7
20
-20
0
10
20
30
40
50
60
70
(HORIZONTAL)
ENVIRONMENT TEMPERATURE ( )
120
205
CURVE 1
100
LOAD (%)
80
60
40
20
10.5VDC
11.5VDC
15VDC
(HORIZONTAL)
147
BATTERY INPUT VOLTAGE (V)
CURVE 2
158
AC OUTPUT
OFF
Bat. Low Status
alarm
Type-A
AC OUTPUT
ON
ON
OFF
Bat. Low Relay Connector :
JST B-XH or equivalent
Open
Short
Battery low
Battery OK
Bat. Low Status
alarm
Type-B
File Name:ISI-500-SPEC 2011-09-22